Briggs & Stratton 30000 SERIES Controls, Automatic Operation Sequence, Setting Exercise Timer

Page 19

Controls

See the Operator’s Manual for complete description of the home generator controls.

Operation

Automatic Operation Sequence

The generator’s control panel houses a logic control circuit board. This control board constantly monitors utility power source voltage. Should that voltage drop below a preset level, control board action will signal the engine to crank and start.

When utility source voltage is restored above a preset voltage level, the engine is signaled to shut down.

The actual system operation is not adjustable and is sequenced by sensors and timers on the control board, as follows:

Utility Voltage Dropout Sensor

This sensor monitors utility source voltage.

If utility source voltage drops below about 70 percent of the nominal supply voltage, the sensor energizes a 10 second timer. The timer is used to ‘sense’ brown- outs.

Once the timer has expired, the engine will crank and start.

Utility Voltage Pickup Sensor

This sensor monitors utility power supply voltage. When that voltage is restored above 80 percent of the nominal source voltage, a time delay starts timing and the engine will go to engine cool-down.

Engine Cool-down Timer

When the load is transferred back to the utility power source, the engine cool-down timer starts timing.

The timer will run for about one minute, then the generator will stop.

Minimum engine run time is 5 minutes.

Setting Exercise Timer

The home generator is equipped with an exercise timer that will start and exercise the system once every seven days. During this exercise period, the unit runs for approximately 20 minutes and then shuts down. Electrical load transfer DOES NOT occur during the exercise cycle (unless an utility power outage occurs).

A button on the control panel is labeled “Set Exercise” (see System Control Panel). The specific day and the specific time of day this button is pressed is programmed into the control board memory. This date and time is then used to automatically initiate the system exercise cycle. The “SET EXERCISE” legend on the control panel will flash until the set exercise cycle is set.

To perform the Set Exercise procedure:

1.Choose the day and time you want your home generator to exercise.

2.On that day and time, press and hold down the “Set Exercise” button for three seconds.

NOTE: “SET EXERCISE” will flash until the button is pressed for three seconds, then “SET EXERCISE” will illuminate for 5 seconds, and finally turn off.

3.The unit will then start and run it’s 20 minute exercise cycle.

For example, if you press the “Set Exercise” button on Sunday morning at 10:00 AM, the unit will run an immediate exercise cycle and an exercise cycle every following Sunday at 10:00 AM (+/- 1/2 hour).

NOTE: “Set Exercise” will only work if the unit is in the Automatic mode and this exact procedure is followed. The exerciser will need to be re-set if the 15 Amp fuse is removed or changed, or if the 12 Volt DC battery is disconnected.

If you want to change the day and time the unit exercises, simply perform the “Set Exercise” procedure at the exact weekday and time you want it to take place.

Installation Inspection

Complete the ”Installation Checklist” as you make the inspection. Ensure all items have been filled-in and all signatures have been obtained. Mail the white copy (and emissions statement, if completed) to:

Briggs & Stratton Power Products Warranty Registration

P. O. Box 239

Jefferson, WI 53549-0239

More detailed Operating, Maintenance and Troubleshooting information is given in the Operator’s Manual.

19

Image 19
Contents Series Liquid-Cooled Home Generator System Model Number Model Revision Serial Number Where to Find UsDate of Purchase Generator EngineTable of Contents Hazard Symbols and Meanings Safety RulesBRIGGSandSTRATTON.COM Page Never operate generator without protective housing or covers Installation Generator Location Home Generator LocationGeneral Location Guidelines Female NPT Electrical and Fuel Inlet LocationsLifting the Generator Concrete SlabGaseous Fuel System Access DoorsTo Open an Access Door To Close an Access DoorNo leakage is permitted Natural Gas LP Vapor Fuel ConsumptionLP Vapor Natural Pole Connector Plug System Connectors+12 Volt DC, .5 Amp Output Internal auxiliary power supply Grounding the Generator Fault Detection SystemTo install the remote LED indicator Generator AC Connection SystemSystem Control Panel Final Installation ConsiderationsFuel Conversion BatteryFuel Supply System Initial Start-up No LoadVoltage Phi Lamda Schematic/ Wiring Diagram Operation Setting Exercise TimerInstallation Inspection ControlsBRIGGSandSTRATTON.COM Manual de Instalación y Arranque Número de Modelo Revisión Número de Serie Dónde encontrarnosFecha de compra Generador MotorMandos Utilización Instrucciones importantes de seguridad InstalaciónSímbolos de Peligro y Significados Conserve estas instruccionesAte para arriba el pelo largo y quite la joyería Tensión peligrosaNo modifique al generador en ninguna forma PrecauciónInstalación Ubicación del Generador Ubicación del Sistema de Generador de DomésticoPautas Generales para la Ubicación del Generador Ubicación de las entradas eléctricas y de combustible Solera de concretoElevación del Generador Para abrir una puerta de acceso Puertas de AccesoPara cerrar una puerta de acceso No encienda un cigarrillo o fume Sistema de combustible gaseosoVapor de Gas Dimensiones de la Cañería de CombustibleConsumo de Combustible Gas Natural Vapor de PLCableado para toma de 10 polos Conexiones de SistemaSistema de Detección de Fallas Sistema de Conexión de c.a. del GeneradorConexión a Tierra del Generador Interconexiones del Circuito de ControlConsideraciones finales para la instalación Panel de Control del SistemaNota no utilice una batería de ciclo profundo Sistema de Suministro de CombustibleArranque inicial sin carga BateríaTensión Phi Lamda Conversión de combustibleUtilización MandosSecuencia de operación automática Inspección posterior a la instalación Configuración del temporizador de prácticaTemporizador de enfriamiento del motor BRIGGSandSTRATTON.COM Manuel d’Installation et Démarrage Numéro de modèle Révision Numéro de série Où nous trouverDate d’achat Génératrice MoteurCommandes Fonctionnement Directives de sécurité importantes InstallationDirectives de sécurité importantes Symboles de Danger et MoyensSécurité Tension dangereuse Avis Précautions Lors du Déballage Responsabilités de l’InstallateurDescription de l’équipement Responsabilités de l’AcheteurDégagement Autour de la Génératrice Emplacement du Génératrice d’état d’AttenteDirectives Générales Concernant l’Emplacement Installez l’unité à l’extérieur SeulementSoulèvement de la Génératrice Dalle de bétonPour fermer une porte d’accès Instalación CommandesPortes d’Accès Pour ouvrir une porte d’accèsAucune fuite ne peut être tolérée Le système de combustible gazeuxGrosseur du Tuyau de Combustible Consommation de CombustibleGas Naturel Vapeur PL Propane GazEntretien Dépannage Garantie Connexions de systèmeSystème de Détection des Pannes Interconnexions du Circuit de CommandeSécurité Instalación Commandes Mise à la Masse de la GénératriceFusible de 15 Ampères Tableau de Commande du SystèmeConsidérations pour l’installation finale Huile à Moteur Interrupteur de systèmeDémarrage initial sans charge Système de refroidissementBatterie Système d’Alimentation en CombustibleLamda Conversion du combustibleTension Tout en observant l’afficheur de l’analyseur d’oxygèneSéquence de fonctionnement automatique CommandesCapteur de Prise en Charge de la Tension de Service FonctionnementRéglage de la minuterie de cycle d’exercice Vérification installationThis page reserved