Briggs & Stratton 040229, 040212, 040213 manual Fault Detection System

Page 14

MAINTENANCE

FAULT DETECTION SYSTEM

The generator may have to run for long periods of time with no operator present. For that reason, the system is equipped with sensors that automatically shut down the generator in the event of potentially damaging conditions, such as low oil pressure, high oil temperature, over speed, and other conditions.

Low Battery Voltage

This fault is indicated by fault code FC_1 and one blink on the LED indicator.This condition occurs if the generator cannot start because the starting battery output power is below that needed to crank the engine. Causes for this problem may be a faulty battery or trickle charger circuit.

To remedy the problem, contact your local service center to check the battery trickle charge output. Remove the

15 Amp fuse and disconnect the battery from the generator. Take the battery to a local battery store for analysis.

The generator's control panel has a digital display to show fault codes. An extra LED indicator is installed at a convenient inside location.The LED will turn on and off in a series of blinks if certain problems are detected in your HGS.The blink pattern is repeated with a brief pause between each series.The fault code as shown on the control panel, and the number of blinks on the mounting plate, indicates the detected fault and as follows:

Fault Codes / LED Flashes

Fault Description

FC_1 / 1

Low battery voltage

FC_2 / 2

Low oil pressure

FC_3 / 3

Low voltage

FC_4 / 4

Engine fail to start

FC_5 / 5

Low frequency

FC_6 / 6

Engine overspeed

FC_7 / 7

Oil temperature high

FC_8 / 8

Transfer switch fault

Reset Fault Detection System

The operator must reset the fault detection system each time it activates.To do so, place the system switch in the OFF position for 5 seconds or more. Return the Home Generator System to service after correcting the problem by placing the system switch in the AUTO position.

A description of each fault and suggested remedies are as follows:

No LED - Discharged Battery

This condition is caused by a completely discharged battery.To remedy the problem, remove the 15 Amp fuse and disconnect the battery from the generator.Take the battery to a local battery store for analysis.

Replace the battery after it has been fully recharged, connecting the NEGATIVE cable last. Install the 15 Amp fuse.

Replace the battery after it has been fully recharged, connecting the NEGATIVE cable last. Install the 15 Amp fuse.

Low Oil Pressure

This fault is indicated by fault code FC_2 and two blinks on the LED indicator.The unit is equipped with an oil pressure switch (Figure 4) using normally closed contacts that are held open by engine oil pressure during operation. Should oil pressure drop below the 8 psi range, switch contacts close and the engine is shut down.

Figure 4 — Low Oil Pressure & High Temp. Switches

 

High

 

Temperature

Oil

Switch

Pressure

 

Switch

 

Oil Drain

 

Fitting

 

To remedy the low oil pressure condition, add the recommended oil to the FULL mark on the dipstick.

If low oil pressure condition still exists, engine will start, then shut down after about 20 seconds and diagnostic LED will flash. In this case, contact an authorized service facility.

14

Image 14
Contents 12000 Table of Contents Important Safety Rules Hazard Symbols and MeaningsSafety Rules Owner Orientation Installation AssistanceIntroduction For the Home OwnerHome Generator System Location Fuel FactorsGenerator Location Essential Circuits Device Running WattsDelivery Inspection Shipment ContentsUnpacking Know Your Home Generator System Unit Data Decal located on base Identifies unit byManual Over-Ride Switch With system switch Know Your System Control Panel To Close an Access Door Access Doors To Open an Access Door Engine Oil Battery ConnectionBefore Initial START-UP Gaseous Fuel SystemAutomatic Operation Setting Exercise TimerTo perform the Set Exercise procedure Servicing the SystemFault Detection System Low Voltage Generator Oil Temperature HighTransfer Switch Fault Engine Fail To StartWhen Calling the Factory Generator MaintenanceTo Clean the Generator StorageTroubleshooting Problem Cause CorrectionPage Limited Warranty Tabla DE Contenido Advertencia Instrucciones Importantes DE SeguridadPeligro Símbolos de Peligro y SignificadosPrecaución Los generadores producen un voltaje muy poderosoOrientación Para EL Propietario Conserve Estas InstruccionesIntroducción Asistencia para la instalaciónUbicación del Generador Factores Relacionados con el CombustibleUbicación del Generador de Reserva Distancias Desde el GeneradorDispositivo Vatiaje de Circuitos FundamentalesPautas Generales para la Ubicación del Generador Contenido de la Caja DesempaqueInspección al Momento de la Entrega Selección de los Circuitos FundamentalesConozca SU Generador Doméstico DE Reserva Conozca EL Panel DE Control DEL Sistema Fusible de 15 Amperios Protege los circuitos de control dePara cerrar una puerta de acceso Puertas de AccesoPara abrir una puerta de acceso Conexión de la Batería Antes DEL Arranque InicialAceite de Motor Sistema de Combustible GaseosoVerificación de la Operación Automática Configuración del Temporizador de PrácticaOperación Automática Paro del SistemaSistema DE Detección DE Fallas Baja Frecuencia Baja TensiónEl Motor no Arranca Sobrevelocidad del MotorCambio del Aceite del Motor Mantenimiento DEL GeneradorAlmacenamiento Para Limpiar el GeneradorReparacion DE Averias Notas Garantía Limitada Table DES Matières Symboles de Danger et Moyens AvertissementNE touchez PAS les fils dénudés ou les boîtiers Introduction Aide à lInstallationConservez CES Instructions Conseils AU PropriétaireFacteurs Relatifs au Combustible Emplacement du Génératrice d’état d’AttenteEmplacement de la Génératrice Dégagement Autour de la GénératriceAppareil Watts Directives Générales Concernant lEmplacementCircuits Essentiels Contenu de la Boîte DéballageVérification de la Livraison Sélection des Circuits EssentielsDécalque Apposé sur lUnité situé sur la base Identifie FAMILIARISEZ-VOUS Avec Votre Groupe ÉlectrogèneBouchon de Remplissage dHuile Enlevez-le pour effectuer La position normale de fonctionnement est la position Pour fermer une porte d’accès Portes dAccèsPour ouvrir une porte d’accès Branchement de la Batterie Avant LE Démarrage InitialHuile à Moteur Système de Combustible GazeuxVérification du Fonctionnement Automatique Fonctionnement AutomatiqueArrêt du Système Réglage de la Minuterie du Cycle dExerciceAucun DEL Batterie déchargée Système DE Détection DES PannesRéarmement du Système de Détection des Pannes Faible Tension de la BatterieBasse Fréquence Basse TensionLe Moteur Ne Démarre Pas Emballement du MoteurVidange de lHuile Moteur Entretien DU GénérateurRemisage Pour Nettoyer le GénérateurDépannage Remarques Remarques Garantie Limitée