INSTALLATION

Essential Circuit Selection

When selecting the essential circuits that will be switched to “Standby Power,” it is important that the sum of the combined circuit loads does not exceed the wattage/amperage capacity of the generator.To help you with your selection of essential circuits, please consider the following:

Add up the total wattage of all electrical devices to be connected at one time.This total should NOT be greater than the generator’s wattage capacity.

The rated wattage of lights can be taken from light bulbs. The rated wattage of tools, appliances and motors can usually be found on a data plate or decal affixed to the device.

If the appliance, tool or motor nameplate does not list wattage, multiply volts times the ampere rating to determine watts (Volts x Amps = Watts).

Some electric motors (induction types) require about three times more watts of power for starting than for running.This surge lasts for only a few seconds. Be sure you allow for this high starting wattage when selecting electrical devices that will be energized by the Home Generator System:

Figure the watts required to start the largest motor.

Add that to the total running watts of all other connected loads.

This Briggs & Stratton Home Generator System complies with the following “stationary standby power rating”:

The standby power rating is applicable for supplying power for the duration of normal power interruption. NO sustained overload capability is available for this rating.

This rating is applicable to installations served by a reliable normal utility source.This rating is only applicable to variable loads with an average load factor of 80% of the standby rating.The standby rating is only applicable for optional standby power where the generator set serves as the backup to the normal utility source.

Use the “Wattage Reference Guide” provided and mark those circuits you consider “critical” or “essential”. Make sure you and your installer consider the system’s altitude above sea level and the ambient temperature range when determining total generator load.

IMPORTANT: When using the 100 Amp or 200 Amp transfer switch with the Home Generator System, you must turn off any non essential loads. Failure to turn off non

essential loads could overload the generator causing it to shut down. Some examples of non essential loads are as follows:

Pool pump

Hot tub

Electric hot tub and/or pool heaters

Central air conditioners

Electric hot water heaters

Electric range and/or oven

Arc welder

Non essential electric heaters

UNPACKING

Refer to the Installation Manual for detailed unpacking instructions, if desired.

Delivery Inspection

After removing the carton, carefully inspect the Home Generator System for any damage that may have occurred during shipment.

IMPORTANT: If loss or damage is noted at time of delivery, have the person(s) making delivery note all damage on the freight bill and affix his signature under the consignor's memo of loss or damage. If loss or damage is noted after delivery, separate the damaged materials and contact the carrier for claim procedures. Missing or damaged parts are not warranted.

Shipment Contents

The Home Generator System is supplied with:

Home Generator System

Pre-attached mounting pad

One 24” flexible hook-up hose

Installation and start-up manual

Operator’s manual

Illustrated parts list manual

Installation checklist

Two access door keys

Four lifting hole plugs

Oil fill spout

One spare 15A fuse

2 Pole connector - 240V from house

10 Pole connector - Sensing and control wires

Air intake engine cover

Alternator cover

Diagnostic LED kit (red LED/plate/screws (2))

8

Image 8
Contents 12000 Table of Contents Important Safety Rules Hazard Symbols and MeaningsSafety Rules Installation Assistance IntroductionOwner Orientation For the Home OwnerHome Generator System Location Fuel FactorsGenerator Location Essential Circuits Device Running WattsDelivery Inspection Shipment ContentsUnpacking Know Your Home Generator System Unit Data Decal located on base Identifies unit byManual Over-Ride Switch With system switch Know Your System Control PanelTo Close an Access Door Access DoorsTo Open an Access Door Battery Connection Before Initial START-UPEngine Oil Gaseous Fuel SystemSetting Exercise Timer To perform the Set Exercise procedureAutomatic Operation Servicing the SystemFault Detection System Oil Temperature High Transfer Switch FaultLow Voltage Generator Engine Fail To StartGenerator Maintenance To Clean the GeneratorWhen Calling the Factory StorageTroubleshooting Problem Cause CorrectionPage Limited Warranty Tabla DE Contenido Instrucciones Importantes DE Seguridad PeligroAdvertencia Símbolos de Peligro y SignificadosPrecaución Los generadores producen un voltaje muy poderosoConserve Estas Instrucciones IntroducciónOrientación Para EL Propietario Asistencia para la instalaciónFactores Relacionados con el Combustible Ubicación del Generador de ReservaUbicación del Generador Distancias Desde el GeneradorDispositivo Vatiaje de Circuitos FundamentalesPautas Generales para la Ubicación del Generador Desempaque Inspección al Momento de la EntregaContenido de la Caja Selección de los Circuitos FundamentalesConozca SU Generador Doméstico DE Reserva Conozca EL Panel DE Control DEL Sistema Fusible de 15 Amperios Protege los circuitos de control dePara cerrar una puerta de acceso Puertas de AccesoPara abrir una puerta de acceso Antes DEL Arranque Inicial Aceite de MotorConexión de la Batería Sistema de Combustible GaseosoConfiguración del Temporizador de Práctica Operación AutomáticaVerificación de la Operación Automática Paro del SistemaSistema DE Detección DE Fallas Baja Tensión El Motor no ArrancaBaja Frecuencia Sobrevelocidad del MotorMantenimiento DEL Generador AlmacenamientoCambio del Aceite del Motor Para Limpiar el GeneradorReparacion DE Averias Notas Garantía Limitada Table DES Matières Symboles de Danger et Moyens AvertissementNE touchez PAS les fils dénudés ou les boîtiers Aide à lInstallation Conservez CES InstructionsIntroduction Conseils AU PropriétaireEmplacement du Génératrice d’état d’Attente Emplacement de la GénératriceFacteurs Relatifs au Combustible Dégagement Autour de la GénératriceAppareil Watts Directives Générales Concernant lEmplacementCircuits Essentiels Déballage Vérification de la LivraisonContenu de la Boîte Sélection des Circuits EssentielsDécalque Apposé sur lUnité situé sur la base Identifie FAMILIARISEZ-VOUS Avec Votre Groupe ÉlectrogèneBouchon de Remplissage dHuile Enlevez-le pour effectuer La position normale de fonctionnement est la position Pour fermer une porte d’accès Portes dAccèsPour ouvrir une porte d’accès Avant LE Démarrage Initial Huile à MoteurBranchement de la Batterie Système de Combustible GazeuxFonctionnement Automatique Arrêt du SystèmeVérification du Fonctionnement Automatique Réglage de la Minuterie du Cycle dExerciceSystème DE Détection DES Pannes Réarmement du Système de Détection des PannesAucun DEL Batterie déchargée Faible Tension de la BatterieBasse Tension Le Moteur Ne Démarre PasBasse Fréquence Emballement du MoteurEntretien DU Générateur RemisageVidange de lHuile Moteur Pour Nettoyer le GénérateurDépannage Remarques Remarques Garantie Limitée