INSTALLATION

Figure 1 — Home Generator System Clearances

Exhaust Port

Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drifting, you may need to construct a windbreak to protect the unit.

Install the generator as close as possible to the Transfer Switch to reduce the length of wiring and conduit.

Install the generator as close as possible to the fuel supply to reduce length of pipes.

IMPORTANT: Laws or local codes may regulate the distance to the fuel supply.

The Home Generator System is shipped already attached to its mounting pad. Unless mandated by local code, a concrete slab is not required.

If mandated by local code, construct a concrete slab at least 3 inches thick and 6 inches longer and wider than the unit. Attach unit to slab with 1/4” diameter (minimum) masonry anchor bolts long enough to retain the unit.

Essential Circuits

As a Home Generator System owner, it is important that you clearly identify the circuits in your building that are "essential" to you.

It is important that your installer understand which circuits you want to include as "Essential Circuits". Depending on the power consumed by these circuits, most or all of them can be switched to the Home Generator System for the duration of normal power interruption.

The wattage reference guide shown in Figure 2 will assist you with your decision-making process. It provides the wattage used by many ordinary household devices. Use it as a guide when selecting your essential circuits. Review this information with your installer and ask about any technical considerations that might affect the cost of your installation.

Figure 2 — Wattage Reference Guide

 

Device

Running

 

Watts

 

 

 

Air Conditioner (12,000 Btu)*

1700

 

Air Conditioner (24,000 Btu)*

3800

 

Air Conditioner (40,000 Btu)*

6000

 

Battery Charger (20 Amp)

500

 

Circular Saw (6-1/2")

800 to 1000

 

Clothes Dryer (Electric)*

5750

 

Clothes Dryer (Gas)*

700

 

Clothes Washer*

1150

 

Coffee Maker

1750

 

Compressor (1 HP)*

2000

 

Compressor (1/2 HP)*

1400

 

Compressor (3/4 HP)*

1800

 

Curling Iron

700

 

Dehumidifier*

650

 

Electric Blanket

400

 

Electric Range (per element)

1500

 

Electric Skillet

1250

 

Freezer*

700

 

Furnace Fan (3/5 HP)*

875

 

Garage Door Opener*

500 to 750

 

Hair Dryer

1200

 

Hand Drill

250 to 1100

 

Iron

1200

 

Jet Pump*

800

 

Light Bulb

100

 

Microwave Oven

700 to 1000

 

Milk Cooler*

1100

 

Oil Burner on Furnace

300

 

Oil Fired Space Heater (140,000 Btu)

400

 

Oil Fired Space Heater (30,000 Btu)

150

 

Oil Fired Space Heater (85,000 Btu)

225

 

Radio

50 to 200

 

Refrigerator

700

 

Slow Cooker

200

 

Submersible Pump (1 HP)*

2000

 

Submersible Pump (1/2 HP)*

1500

 

Submersible Pump (1-1/2 HP)*

2800

 

Sump Pump*

800 to 1050

 

Table Saw (10")*

1750 to 2000

 

Television

200 to 500

 

Toaster

1000 to 1650

*Allow three (3) times listed watts for starting device

7

Image 7
Contents 12000 Table of Contents Hazard Symbols and Meanings Important Safety RulesSafety Rules For the Home Owner Installation AssistanceIntroduction Owner OrientationGenerator Location Fuel FactorsHome Generator System Location Device Running Watts Essential CircuitsUnpacking Shipment ContentsDelivery Inspection Unit Data Decal located on base Identifies unit by Know Your Home Generator SystemKnow Your System Control Panel Manual Over-Ride Switch With system switchTo Open an Access Door Access DoorsTo Close an Access Door Gaseous Fuel System Battery ConnectionBefore Initial START-UP Engine OilServicing the System Setting Exercise TimerTo perform the Set Exercise procedure Automatic OperationFault Detection System Engine Fail To Start Oil Temperature HighTransfer Switch Fault Low Voltage GeneratorStorage Generator MaintenanceTo Clean the Generator When Calling the FactoryProblem Cause Correction TroubleshootingPage Limited Warranty Tabla DE Contenido Símbolos de Peligro y Significados Instrucciones Importantes DE SeguridadPeligro AdvertenciaLos generadores producen un voltaje muy poderoso PrecauciónAsistencia para la instalación Conserve Estas InstruccionesIntroducción Orientación Para EL PropietarioDistancias Desde el Generador Factores Relacionados con el CombustibleUbicación del Generador de Reserva Ubicación del GeneradorPautas Generales para la Ubicación del Generador Circuitos FundamentalesDispositivo Vatiaje de Selección de los Circuitos Fundamentales DesempaqueInspección al Momento de la Entrega Contenido de la CajaConozca SU Generador Doméstico DE Reserva Fusible de 15 Amperios Protege los circuitos de control de Conozca EL Panel DE Control DEL SistemaPara abrir una puerta de acceso Puertas de AccesoPara cerrar una puerta de acceso Sistema de Combustible Gaseoso Antes DEL Arranque InicialAceite de Motor Conexión de la BateríaParo del Sistema Configuración del Temporizador de PrácticaOperación Automática Verificación de la Operación AutomáticaSistema DE Detección DE Fallas Sobrevelocidad del Motor Baja TensiónEl Motor no Arranca Baja FrecuenciaPara Limpiar el Generador Mantenimiento DEL GeneradorAlmacenamiento Cambio del Aceite del MotorReparacion DE Averias Notas Garantía Limitada Table DES Matières Avertissement Symboles de Danger et MoyensNE touchez PAS les fils dénudés ou les boîtiers Conseils AU Propriétaire Aide à lInstallationConservez CES Instructions IntroductionDégagement Autour de la Génératrice Emplacement du Génératrice d’état d’AttenteEmplacement de la Génératrice Facteurs Relatifs au CombustibleCircuits Essentiels Directives Générales Concernant lEmplacementAppareil Watts Sélection des Circuits Essentiels DéballageVérification de la Livraison Contenu de la BoîteBouchon de Remplissage dHuile Enlevez-le pour effectuer FAMILIARISEZ-VOUS Avec Votre Groupe ÉlectrogèneDécalque Apposé sur lUnité situé sur la base Identifie La position normale de fonctionnement est la position Pour ouvrir une porte d’accès Portes dAccèsPour fermer une porte d’accès Système de Combustible Gazeux Avant LE Démarrage InitialHuile à Moteur Branchement de la BatterieRéglage de la Minuterie du Cycle dExercice Fonctionnement AutomatiqueArrêt du Système Vérification du Fonctionnement AutomatiqueFaible Tension de la Batterie Système DE Détection DES PannesRéarmement du Système de Détection des Pannes Aucun DEL Batterie déchargéeEmballement du Moteur Basse TensionLe Moteur Ne Démarre Pas Basse FréquencePour Nettoyer le Générateur Entretien DU GénérateurRemisage Vidange de lHuile MoteurDépannage Remarques Remarques Garantie Limitée