Briggs & Stratton 01938-0, 01815-0 manual Before Initial START-UP, System Control Panel, Engine Oil

Page 12

Briggs & Stratton Power Products Home Generator

Installation Manual

System Control Panel

Figure 11 depicts the Home Standby Generator control panel, located inside the generator housing. Brief descriptions of the controls used during installation. More information may be found in the operator’s Manual.

Figure 11 — Home Standby Generator Control Panel

Set Exercise

Circuit

Switch

Breaker

Diagnostic

LED

Hour Meter

AUTO/OFF/

MANUAL

15 Amp Switch

Fuse

AUTO/OFF/MANUAL Switch

This three-position switch is the most important control on the system and is used as follows:

AUTO” position is the normal operating position. If a utility power outage is sensed, the system will start the generator.When utility power is restored, lets the engine stabilize internal temperatures, shuts off the generator, and waits for the next utility power outage.

OFF” position turns off running generator, prevents unit from starting and resets any detected faults.

MANUAL” position starts the engine after a short amount of time. It is used for maintenance or diagnostic functions.

15 Amp Fuse

Protects the Home Standby Generator DC control circuits. If the fuse has ‘blown’ (melted open) or was removed, the engine cannot crank or start. Replace the fuse using ONLY an identical BUS AGC 15A fuse. One spare fuse is supplied with the unit.

BEFORE INITIAL START-UP

Engine Oil

This engine is shipped from the factory filled with the recommended oil. Before starting the engine, check oil level and ensure that engine is serviced as described in the engine operator’s manual.

CAUTION

Any attempt to crank or start the engine before it has been properly serviced with the recommended oil will result in equipment failure.

Refer to engine manual for oil fill information.

Damage to equipment resulting from failure to follow this instruction will void warranty.

Oil Considerations

Your Home Standby Generator is equipped with an engine that has been pre-run at the factory and does not require the traditional “break-in” procedure.

The system is filled with synthetic oil (API SJ/CF 5W- 30W).This allows for system operation in the widest range of temperature and climate conditions.

NOTE: The use of synthetic oil DOES NOT alter the required oil change intervals described in the engine operator’s manual.

Battery Connection

The Home Standby Generator is supplied with a 12 Volt DC,AGM type, 33 Amp-Hour, valve regulated battery. It is a sealed, lead-acid rechargeable battery. It is installed in the unit and the battery cables are connected at the factory.The unit’s 15 Amp fuse, which isolates the battery and prevents the unit from starting, has been removed for shipping.The battery will lose some charge charge prior to installation of the generator. If battery voltage is below 12 Volts, charge the battery.

IMPORTANT: If battery voltage is below 5 Volts, it may not take a charge and you will need a new battery.

Charging the Battery

If it is necessary to charge the battery, proceed as follows:

1.Set the generator's “AUTO/OFF/MANUAL” switch to OFF.

2.Remove the 15 Amp fuse from the control panel.

3.Disconnect the negative battery cable to the negative battery terminal (indicated by NEGATIVE, NEG, or (-).

CAUTION

Failure to disconnect negative battery cable will result in equipment failure.

DO NOT attempt to jump start the battery.

Damage to equipment resulting from failure to follow this instruction will void warranty.

4.Charge battery with battery charger at 2 Amps until battery holds 12 Volts.

12

Image 12
Contents 10kW / 12kW Rated Table of Contents Installer ResponsibilitiesEquipment Description Customer ResponsibilitiesImportant Safety Rules Hazard Symbols and MeaningsRotating Parts Electrical Shock Amp fuse Before working on the equipmentInstallation Procedures Fuel and Electrical Inlet Dimensions Lifting the GeneratorConduit Attachment AreaAccess Doors BatteryInsert DoorInstallation Manual To Remove an Access Door To Install an Access DoorGaseous Fuel System From Fuel To Home StandbyFuel Consumption Fuel Pipe Sizing10ft 15ft 20ft 30ft 40ft 50ft 60ft 70ft 80ft 90ft 100ft LoadVolt DC, .5 Amp Output Internal power supply Know Your System Control BoardRemote LED Output Fault Detection System To install the remote LED panelGenerator AC Connection System Grounding the GeneratorBattery Connection Before Initial START-UPSystem Control Panel Engine OilServicing the Battery To configure the fuel system for LP useDo not dispose of battery in a fire Fuel System SelectionEngine Adjustment Install the 15 Amp fuse in the control panelInitial START-UP no Load Engine Cool-down Timer Adjustment NutAutomatic Operation Sequence Utility Voltage Dropout SensorSetting Exercise Timer Installation InspectionTo perform the Set Exercise procedure Fuel Comparison Chart Physical Properties Butane Propane Natural GasWithdrawal Rate 32F 20F 10F 30F 40F Tabla DE Contenido Descripción DEL EquipoResponsabilidades DEL Cliente Responsabilidades DEL InstaladorPrecaución AdvertenciaSímbolos de Peligro y Significados ExplosiónProcedimientos DE Instalación Dimensiones de la Entrada para Electricidad y Combustible Elevación del GeneradorNPT 13.5Puertas de Acceso ParaPara Retirar una Puerta de Acceso Entrada de CombustibleSistema DE Combustible Gaseoso Advertencia Para Instalar una Puerta de AccesoFigura 19 Manómetro Instalado Transitoriamente Dimensiones de la Cañería de Combustible Consumo de CombustibleModelo Gas Natural Vapor de PL Gas Natural peso específico =Conozca LA Tarjeta DE Control DE SU Sistema Sistema de Conexión de c.a. del Generador Conexión a Tierra del GeneradorInterconexiones del Circuito de Control Sistema de Detección de FallasAntes DEL Arranque Inicial DEL Motor Panel de Control del SistemaAceite de Motor Conexión de la BateríaPara configurar el sistema de combustible para uso de LP PeligroSelección DEL Sistema DE Combustible Sistema de Suministro de CombustibleArranque Inicial SIN Carga Instale el fusible de 15 Amperios en el panel de controlFije el interruptor AUTO/OFF/MANUAL en la posición Ajuste del Motor Del ReguladorCargue el generador al valor nominal de gas natural Configuración DEL Temporizador DE Práctica Secuencia DE Operación AutomáticaInspección Posterior a LA Instalación Cuadro de Comparación de Combustibles Propiedades físicas Butano Propano Gas naturalTasa de consumo 32F 20F 10F 30F 40F Responsabilités DE Linstallateur Guide dInstallationTable DES Matières Description DE LéquipementSymboles de Danger et Moyens AvertissementExplosion Feu Procédures Dinstallation Directives Générales Concernant lEmplacement Soulèvement de la GénératriceConnecteur de tuyauterie De combustible Tuyau ici Tuyau fourni par linstallateur Portes dAccèsPour Pour enlever une porte daccèsPour installer une porte daccès LE Système DE Combustible Gazeux AvertissementLe groupe électrogène a été réglé en usine pour Il faudrait inclure une sortie pour manomètreConsommation de Combustible Grosseur du Tuyau de CombustibleModèle Gas Naturel Vapeur PL Gaz Naturel densité = 0,65Sortie de panneau DEL à distance Interconnexions du Circuit de Commande Tableau de Commande du SystèmeSystème de Branchement C.A. de la Génératrice Mise à la Masse de la GénératriceAvant LE Démarrage Initial DU Moteur Huile à MoteurBranchement de la Batterie Sélection DU Système DE Combustible Système dAlimentation en CombustibleRéglez linterrupteur AUTO/OFF/MANUAL sur Auto Entretien de la BatterieDémarrage Initial Sans Réglage du MoteurRéglez linterrupteur AUTO/OFF/MANUAL sur Manual Du RégulateurVérification Installation Séquence DE Fonctionnement AutomatiqueRéglage DE LA Minuterie DE Cycle Dexercice Charte de Comparaison des Combustibles Propriétés physiques Butane Propane Gaz naturelDensité 31,26 Poids† Indice d’octane Recherche