Installation Instructions
1.1.5Floor Pedestal Installation
Floor pedestals are optional equipment that provide clearance for bottom cable entry or exit for FPC units not installed on raised flooring. The pedestals are adjustable over a limited range (approxi- mately
! CAUTION
Floor pedestals may be
1.Insert the pedestal threaded shaft into the pedestal holes in the cabinet base as shown in Figures 1 and 2.
2.Adjust the pedestal height by turning the welded nut/shaft assembly into or out of the pedestal base as required.
3.Lock the height by tightening the jam nut against the pedestal base.
The pedestal may be anchored to the floor by means of the four holes in the base. Locations of floor pedestals are shown in Figures 1 and 2.
Figure 4 Floor pedestal details
3" | Threaded |
(76mm) | Shaft |
| Washer |
| Welded Nut |
| Jam Nut |
Pedestal
Base
.56" (14mm) diameter mounting holes
(57mm)
6"
(152mm) square
(57mm)
(57mm) (57mm)
7