Emerson FPC user manual Inch cabinet weight

Page 7

Installation Instructions

Figure 1 Typical cabinet and floor planning dimension data, 23" (584mm) cabinet, 15-125 kVA

Overall Dim.

39-1/2" (1003mm) Including hinge and bezel projection

Overhead clearance

of 18" (457mm) recommended

for cooling airflow

Minimum side

clearance of 42" (1067mm) recommended for service access if unit is equipped with distribution monitoring option

Overall Dimension

 

 

25.2" (640mm)

 

 

including side

 

 

panels

1.2"

 

 

6"

 

(30mm)

34" (864mm)

(152mm)

11-1/2" (292mm)

1.2"

 

 

6" (152mm)

(30mm)

Front

 

 

 

78-1/2" (1995mm)

Shaded area indicates

 

cable access and

 

cooling airflow

Footprint and Floor

Cutout Dimensions

Shaded areas indicate recommended clearance of 42" (1067mm) at front and rear for service access

23-

.4"

36

1/2"

(597mm)

(925mm)

Unit Base Outline

For units with bottom cable access, clearance of 6" (152mm) below unit is recommended for cooling airflow and cable entry/exit

Cabinet Dimensional Data

36.4" (925mm)

Unit Base Outline

Front

Floor Pedestals available from 6" (152mm) to 18"

Optional Floor Pedestals

23-1/2" (597mm)

3.2" (81mm)

8.3"

(211mm)

Dia. location 3/4" (19mm) typical

.56" (14mm) diameter; 4 holes typical

(457mm)

6" (152mm) 6" (152mm)

Table 1

23-inch cabinet weight

 

 

 

 

Weight, lb (kg)

 

Unit

 

 

 

 

 

 

 

 

 

Without

kVa

 

60Hz

50Hz

 

Transformer

15

 

1010 (458)

1060 (480)

 

750 (340)

 

 

 

 

 

 

30

 

1090 (494)

1140 (517)

 

750 (340)

 

 

 

 

 

 

50

 

1160 (526)

1235 (560)

 

750 (340)

 

 

 

 

 

 

75

 

1350 (612)

1450 (658)

 

800 (363)

 

 

 

 

 

 

100

 

1540 (699)

1665 (755)

 

800 (363)

 

 

 

 

 

 

125

 

1650 (748)

1775 (805)

 

800 (363)

 

 

 

 

 

 

3

Image 7
Contents Liebert FPC Page Table of Contents Figures Important Safety Instructions Unpacking and Preliminary Inspection Unpacking and InstallationHandling Considerations Inch cabinet weight Front Footprint and Floor cable accessCutout Dimensions cooling airflow FrontLocation Considerations Unit PreparationLiebert FPC heat output See Notes 2 Front and rear access is required. See Notes 1Full Load Heat Output Unit kVA BTU/Hr kW Floor pedestal details Floor Pedestal InstallationLiebert FDC Distribution Mounting Additional Distribution Mounting & WiringPower and Control Wiring Input Power ConnectionsElectrical connection location for 23 584mm cabinet FPC15000 Rev FPC15002 Rev Suggested minimum input wire size data Main input circuit breaker interrupting rating Main input power junction box dimensions, typical Junction Box InstallationMain input junction box electrical connections 4 wire Low-voltage control junction box dimensions, typicalEquipment Grounding System GroundingOutput Voltage Signal Reference GridGrounding Electrode Conductor for FPCs With Transformer Minimum grounding electrode conductor size AWGSystemTypical Liebert FPC without transformer grounding Typical Liebert FPC With transformer grounding arrangementOutput Power Connections Liebert FPC Main Liebert FPC+24VDC Unit EPOLow Voltage Terminal Strip WiringFactory Optional Customer Alarm Inputs Summary Typical control wiring for units with monitoringStartup ChecklistsWarranty Internal InspectionTerminal block compression lug torque specifications Torque specifications, generalPanelboard main circuit breaker torque specifications Branch circuit breaker torque specificationsUnit Serial Number Unit Model Number Date InspectionStartup Monitoring System Check-Out Customer Alarms Manual Restart Startup ProceduresNormal System Shutdown Normal System Turn onFPC16000 Power Monitor PanelAlarm Present/Silence Basic Monitor Panel Units Without MonitoringOperating Instructions RS-232 Ascii port customer commands Ascii interface default parametersParameter Default Field # Data item Units Monitored parameters data definitionsRepair Inspection and CleaningInspection Schedule Page That Ne tIti Ti n