Emerson FPC user manual Low Voltage Terminal Strip, Wiring, Factory

Page 25

Installation Instructions

Figure 15 Typical control wiring for units without monitoring

 

Low Voltage

 

21

 

 

Terminal Strip

 

 

 

 

20

 

 

 

 

 

 

 

 

19

 

 

 

 

18

 

 

 

 

17

 

 

 

 

16

 

 

 

 

15

 

 

 

 

14

 

 

 

 

13

 

 

 

 

12

 

 

 

 

11

 

 

 

 

10

 

Wiring

Overtemp Alarm N.O. W208

9

 

8

 

Overtemp Alarm N.C. W207

7

 

-Supplied

Alarm Com. W206

6

 

N.O. REPO W205

5

 

24VDC W204

4

 

REPO Com. W203

3

 

Factory

 

N.C. REPO

W202

2

 

24VDC

W201

1

 

 

Building

A

7

4

 

 

 

 

 

Interface

 

 

1

 

Relay

R

 

3

 

 

 

 

 

 

B

9

6

S Overtemp

Alarm Output

BLK

WHT N.O. REPO GRN

N.C. REPO

Remove jumper when Normally Closed (N.C.)

REPO is used

NOTES

1.All switching devices are to be suitable for switching low current 24VDC. Minimum recommended wire size is 18AWG stranded copper with 300V insulation.

All wiring and devices are field supplied except where noted. See installation manual for detailed installation procedures.

2.Low voltages terminal strip may be located in unit or low voltage control junction box.

3.The total load on the 24VDC supply (both N.O. and N.C. REPO circuits) must be limited to 1A.

4.Multiple normally open (N.O.) REPO switches may be paralleled.

Multiple normally closed (N.C.) REPO switches may be connected in series. all lamps (if used) are connected in parallel.

5.The summary alarm contacts are rated for 0 to 30VAC or VDC, 0.5A, 10W maximum.

21

Image 25
Contents Liebert FPC Page Table of Contents Figures Important Safety Instructions Unpacking and Preliminary Inspection Unpacking and InstallationHandling Considerations Inch cabinet weight Cutout Dimensions cooling airflow Footprint and Floor cable accessFront FrontLocation Considerations Unit PreparationLiebert FPC heat output See Notes 2 Front and rear access is required. See Notes 1Full Load Heat Output Unit kVA BTU/Hr kW Floor pedestal details Floor Pedestal InstallationPower and Control Wiring Additional Distribution Mounting & WiringInput Power Connections Liebert FDC Distribution MountingElectrical connection location for 23 584mm cabinet FPC15000 Rev FPC15002 Rev Suggested minimum input wire size data Main input circuit breaker interrupting rating Main input junction box electrical connections 4 wire Junction Box InstallationLow-voltage control junction box dimensions, typical Main input power junction box dimensions, typicalEquipment Grounding System GroundingGrounding Electrode Conductor for FPCs With Transformer Signal Reference GridMinimum grounding electrode conductor size AWG Output VoltageSystemTypical Liebert FPC without transformer grounding Typical Liebert FPC With transformer grounding arrangementOutput Power Connections Liebert FPC +24VDC Liebert FPCUnit EPO MainLow Voltage Terminal Strip WiringFactory Optional Customer Alarm Inputs Summary Typical control wiring for units with monitoringWarranty ChecklistsInternal Inspection StartupPanelboard main circuit breaker torque specifications Torque specifications, generalBranch circuit breaker torque specifications Terminal block compression lug torque specificationsUnit Serial Number Unit Model Number Date InspectionStartup Monitoring System Check-Out Customer Alarms Normal System Shutdown Startup ProceduresNormal System Turn on Manual RestartAlarm Present/Silence Power Monitor PanelBasic Monitor Panel Units Without Monitoring FPC16000Operating Instructions RS-232 Ascii port customer commands Ascii interface default parametersParameter Default Field # Data item Units Monitored parameters data definitionsRepair Inspection and CleaningInspection Schedule Page Iti Ne tTi n That