Emerson FPC Torque specifications, general, Panelboard main circuit breaker torque specifications

Page 28

Equipment Inspection and Startup

Table 11 Torque specifications, general

 

Electrical connections

Electrical connections

 

with 1 Belleville washer

with 2 Belleville washers

 

 

 

 

 

 

 

Torque

 

Torque

 

 

 

 

 

 

 

 

lb-in

 

N-m

lb-in

 

N-m

 

 

 

 

 

 

 

Bolt shaft size, in./mm

 

 

 

 

 

 

 

 

 

 

 

 

1/4 / M6

40

 

4.5

80

 

9.0

 

 

 

 

 

 

 

5/16 / M8

80

 

9.0

180

 

18.0

 

 

 

 

 

 

 

3/8 / M10

120

 

13.6

240

 

27.1

 

 

 

 

 

 

 

1/2 / M12

480

 

54.3

 

 

 

 

 

 

 

 

Input and output breakers

 

 

 

 

 

 

 

 

 

 

 

 

Up to 150 amp

80

 

9.0

160

 

18.0

 

 

 

 

 

 

 

175 - 500A

120

 

13.6

240

 

27.1

 

 

 

 

 

 

 

Table 12 Panelboard main circuit breaker torque specifications

 

Torque

 

lb-in

N-m

Busbar-to-breaker

240

27.1

Table 13 Branch circuit breaker torque specifications

Breaker size

lb-in

N-m

 

 

 

Up to 30 amp

20

4.0

 

 

 

40 to 100 amp

20

5.1

 

 

 

Table 14 Terminal block compression lug torque specifications

AWG wire size

Torque

 

 

or range

lb-in

N-m

 

 

 

#14 - #10

35

4.0

 

 

 

#8

40

4.5

 

 

 

24

Image 28
Contents Liebert FPC Page Table of Contents Figures Important Safety Instructions Unpacking and Preliminary Inspection Unpacking and InstallationHandling Considerations Inch cabinet weight Footprint and Floor cable access Cutout Dimensions cooling airflowFront FrontUnit Preparation Location ConsiderationsLiebert FPC heat output See Notes 2 Front and rear access is required. See Notes 1Full Load Heat Output Unit kVA BTU/Hr kW Floor Pedestal Installation Floor pedestal detailsAdditional Distribution Mounting & Wiring Power and Control WiringInput Power Connections Liebert FDC Distribution MountingElectrical connection location for 23 584mm cabinet FPC15000 Rev FPC15002 Rev Suggested minimum input wire size data Main input circuit breaker interrupting rating Junction Box Installation Main input junction box electrical connections 4 wireLow-voltage control junction box dimensions, typical Main input power junction box dimensions, typicalSystem Grounding Equipment GroundingSignal Reference Grid Grounding Electrode Conductor for FPCs With TransformerMinimum grounding electrode conductor size AWG Output VoltageTypical Liebert FPC With transformer grounding arrangement SystemTypical Liebert FPC without transformer groundingOutput Power Connections Liebert FPC Liebert FPC +24VDCUnit EPO MainLow Voltage Terminal Strip WiringFactory Typical control wiring for units with monitoring Optional Customer Alarm Inputs SummaryChecklists WarrantyInternal Inspection StartupTorque specifications, general Panelboard main circuit breaker torque specificationsBranch circuit breaker torque specifications Terminal block compression lug torque specificationsInspection Unit Serial Number Unit Model Number DateStartup Monitoring System Check-Out Customer Alarms Startup Procedures Normal System ShutdownNormal System Turn on Manual RestartPower Monitor Panel Alarm Present/SilenceBasic Monitor Panel Units Without Monitoring FPC16000Operating Instructions RS-232 Ascii port customer commands Ascii interface default parametersParameter Default Monitored parameters data definitions Field # Data item UnitsRepair Inspection and CleaningInspection Schedule Page Ne t ItiTi n That