Emerson Signal Reference Grid, Grounding Electrode Conductor for FPCs With Transformer

Page 20

Installation Instructions

Signal Reference Grid

If the unit is used to supply power to a computer room or area that is equipped with a signal reference grid or a grounded raised-floor stringer system, a grounding conductor should be connected from the system ground bus to the grid or floor system. This conductor should be stranded or braided #8 AWG or larger, and as short as practical. Less than 3 ft. (1m) is recommended.

1.3.4Grounding Electrode Conductor for FPCs With Transformer

Required by code - The Liebert FPC with transformer must be grounded according to the safety practices of NEC 250-26. A local grounding electrode conductor is recommended in addition to the equipment safety ground which is normally run with the input power conductors. (See Figures 5 through 8.)

As shown in Figure 12, the grounding electrode conductor is run from the unit to the nearest effec- tively grounded location (listed in order of preference):

Building steel

Metal water pipe

Other made grounding electrode

The grounding electrode conductor’s size is based on the secondary circuit conductors. Table 10 shows the minimum recommended grounding electrode conductor according to the NEC (Table 250-66).

Table 10 Minimum grounding electrode conductor size (AWG)

 

Output Voltage

kVA

 

 

 

208V

380V

415V

 

 

 

 

15

8

8

8

 

 

 

 

30

8

8

8

 

 

 

 

50

4

8

8

 

 

 

 

75

2

6

6

 

 

 

 

100

0

4

4

 

 

 

 

125

0

2

2

 

 

 

 

150

00

2

2

 

 

 

 

200

00

0

0

 

 

 

 

225

00

0

0

 

 

 

 

300

00

0

0

 

 

 

 

AWG wire size based on 75°C copper conductors

Recommended methods for running the grounding electrode conductor (arranged by preference for system performance; as acceptable by local and other applicable codes):

Outside of conduit (where not subject to damage)

Inside non-metallic conduit

Inside non-ferrous conduit

Inside ferrous conduit, bonded to the ferrous conduit at both ends, as acceptable by local and other applicable codes

16

Image 20
Contents Liebert FPC Page Table of Contents Figures Important Safety Instructions Handling Considerations Unpacking and InstallationUnpacking and Preliminary Inspection Inch cabinet weight Footprint and Floor cable access Cutout Dimensions cooling airflowFront FrontUnit Preparation Location ConsiderationsFull Load Heat Output Unit kVA BTU/Hr kW See Notes 2 Front and rear access is required. See Notes 1Liebert FPC heat output Floor Pedestal Installation Floor pedestal detailsAdditional Distribution Mounting & Wiring Power and Control WiringInput Power Connections Liebert FDC Distribution MountingElectrical connection location for 23 584mm cabinet FPC15000 Rev FPC15002 Rev Suggested minimum input wire size data Main input circuit breaker interrupting rating Junction Box Installation Main input junction box electrical connections 4 wireLow-voltage control junction box dimensions, typical Main input power junction box dimensions, typicalSystem Grounding Equipment GroundingSignal Reference Grid Grounding Electrode Conductor for FPCs With TransformerMinimum grounding electrode conductor size AWG Output VoltageTypical Liebert FPC With transformer grounding arrangement SystemTypical Liebert FPC without transformer groundingOutput Power Connections Liebert FPC Liebert FPC +24VDCUnit EPO MainFactory WiringLow Voltage Terminal Strip Typical control wiring for units with monitoring Optional Customer Alarm Inputs SummaryChecklists WarrantyInternal Inspection StartupTorque specifications, general Panelboard main circuit breaker torque specificationsBranch circuit breaker torque specifications Terminal block compression lug torque specificationsInspection Unit Serial Number Unit Model Number DateStartup Monitoring System Check-Out Customer Alarms Startup Procedures Normal System ShutdownNormal System Turn on Manual RestartPower Monitor Panel Alarm Present/SilenceBasic Monitor Panel Units Without Monitoring FPC16000Operating Instructions Parameter Default Ascii interface default parametersRS-232 Ascii port customer commands Monitored parameters data definitions Field # Data item UnitsInspection Schedule Inspection and CleaningRepair Page Ne t ItiTi n That