Installation Instructions
Signal Reference Grid
If the unit is used to supply power to a computer room or area that is equipped with a signal reference grid or a grounded
1.3.4Grounding Electrode Conductor for FPCs With Transformer
Required by code - The Liebert FPC with transformer must be grounded according to the safety practices of NEC
As shown in Figure 12, the grounding electrode conductor is run from the unit to the nearest effec- tively grounded location (listed in order of preference):
•Building steel
•Metal water pipe
•Other made grounding electrode
The grounding electrode conductor’s size is based on the secondary circuit conductors. Table 10 shows the minimum recommended grounding electrode conductor according to the NEC (Table
Table 10 Minimum grounding electrode conductor size (AWG)
| Output Voltage | ||
kVA |
|
|
|
208V | 380V | 415V | |
|
|
|
|
15 | 8 | 8 | 8 |
|
|
|
|
30 | 8 | 8 | 8 |
|
|
|
|
50 | 4 | 8 | 8 |
|
|
|
|
75 | 2 | 6 | 6 |
|
|
|
|
100 | 0 | 4 | 4 |
|
|
|
|
125 | 0 | 2 | 2 |
|
|
|
|
150 | 00 | 2 | 2 |
|
|
|
|
200 | 00 | 0 | 0 |
|
|
|
|
225 | 00 | 0 | 0 |
|
|
|
|
300 | 00 | 0 | 0 |
|
|
|
|
AWG wire size based on 75°C copper conductors
Recommended methods for running the grounding electrode conductor (arranged by preference for system performance; as acceptable by local and other applicable codes):
•Outside of conduit (where not subject to damage)
•Inside
•Inside
•Inside ferrous conduit, bonded to the ferrous conduit at both ends, as acceptable by local and other applicable codes
16