Alarms - Upon occurrence of any of the following alarms, the alarm message appears on the LCD dis- play, the Alarm Present/Silence switch is illuminated, and the audible alarm is activated. Pressing the “Alarm Present/Silence” switch silences the audible alarm. After the alarm condition is corrected, the alarm can be reset by pressing the “Alarm Present/Silence” switch when prompted by the LCD display or by way of any Central Monitoring System.

Output Overvoltage - Indicates one or more of the output phase voltages has exceeded the pre- set limit (normally +6% of nominal). The high output voltage should be verified and corrective action taken. In the absence of other procedures, a normal (orderly) system shutdown should be performed to prevent load equipment damage.

Output Undervoltage - Indicates one or more of the output phase voltages has exceeded the preset limit (normally -13% of nominal). The low output voltage should be verified and corrective action taken. In the absence of other procedures, a normal (orderly) system shutdown should be performed to prevent load equipment damage.

Output Voltage THD - Indicates that the voltage distortion on one or more of the output phases has exceeded the preset limit (normally 10% THD). The cause of the high output voltage distor- tion should be investigated and corrective action (if any) taken.

•Transformer Overtemp - Indicates a unit transformer overtemperature condition. The cause of the overtemperature condition should be investigated and corrected. Possible causes include unit overload, excessive non-linear loading, inadequate ventilation, high or low input voltage, or monitoring malfunction. Failure to correct the overtemperature condition may result in an auto- matic system shutdown due to the second stage of overtemperature sensing.

Output Overcurrent - Indicates one or more of the output phase currents has exceeded the pre- set limit (normally 95% of the unit’s full load amp rating). The overcurrent condition should be verified and corrective action taken. In the absence of other procedures, some of the output loads should be turned off to reduce unit loading. If unbalanced phase currents exist, some of the loads should be shifted from the higher loaded phase(s) to the lower loaded phase(s).

Neutral Overcurrent - Indicates that the neutral current has exceeded the preset limit (nor- mally 95% of the unit’s full load amp rating). The overcurrent condition should be verified and investigated to see if corrective action is required. In some cases, high neutral current indicates phase current unbalance which should be corrected. Where high neutral currents are the result of harmonic load currents, all affected components (including output wiring) should be verified to be suitable for the current.

Frequency Deviation - Indicates that the output frequency has exceeded preset limits (nor- mally Ø0.5 Hz). The frequency deviation should be verified and the cause investigated and cor- rected.

Phase Sequence Error - Indicates that the output phase sequence is not A, B, C. The phase sequence should be verified and corrective action taken. Three-phase loads sensitive to phase sequence should not be operated without proper phase sequence.

Phase Loss - Indicates that one or more of the phase voltages is low or missing. The low voltage condition should be verified and corrective action taken. In the absence of other procedures, a nor- mal (orderly) shutdown should be performed to prevent equipment damage.

Ground Overcurrent - Indicates the system ground current has exceeded the preset limit (nor- mally 5 amps). The overcurrent condition should be verified and corrective action taken. Possible causes are wiring errors, ground faults, or excessive leakage current.

Customer Alarms (5) - Indicates customer-designated alarms. The cause and corrective action depend on the nature of the alarm. See 1.3.6 - Control Wiring Connections for contact closure connection information.

31

Image 35
Contents Liebert FPC Page Table of Contents Figures Important Safety Instructions Handling Considerations Unpacking and InstallationUnpacking and Preliminary Inspection Inch cabinet weight Front Footprint and Floor cable accessCutout Dimensions cooling airflow FrontLocation Considerations Unit PreparationFull Load Heat Output Unit kVA BTU/Hr kW See Notes 2 Front and rear access is required. See Notes 1Liebert FPC heat output Floor pedestal details Floor Pedestal InstallationLiebert FDC Distribution Mounting Additional Distribution Mounting & WiringPower and Control Wiring Input Power ConnectionsElectrical connection location for 23 584mm cabinet FPC15000 Rev FPC15002 Rev Suggested minimum input wire size data Main input circuit breaker interrupting rating Main input power junction box dimensions, typical Junction Box InstallationMain input junction box electrical connections 4 wire Low-voltage control junction box dimensions, typicalEquipment Grounding System GroundingOutput Voltage Signal Reference GridGrounding Electrode Conductor for FPCs With Transformer Minimum grounding electrode conductor size AWGSystemTypical Liebert FPC without transformer grounding Typical Liebert FPC With transformer grounding arrangementOutput Power Connections Liebert FPC Main Liebert FPC+24VDC Unit EPOFactory WiringLow Voltage Terminal Strip Optional Customer Alarm Inputs Summary Typical control wiring for units with monitoringStartup ChecklistsWarranty Internal InspectionTerminal block compression lug torque specifications Torque specifications, generalPanelboard main circuit breaker torque specifications Branch circuit breaker torque specificationsUnit Serial Number Unit Model Number Date InspectionStartup Monitoring System Check-Out Customer Alarms Manual Restart Startup ProceduresNormal System Shutdown Normal System Turn onFPC16000 Power Monitor PanelAlarm Present/Silence Basic Monitor Panel Units Without MonitoringOperating Instructions Parameter Default Ascii interface default parametersRS-232 Ascii port customer commands Field # Data item Units Monitored parameters data definitionsInspection Schedule Inspection and CleaningRepair Page That Ne tIti Ti n