Emerson Liebert FPC heat output, See Notes 2 Front and rear access is required. See Notes 1

Page 10

Installation Instructions

Figure 3 Recommended minimum service and ventilation clearances

Minimum clearance of 18" (457mm) above unit is recommended for cooling airflow

See Notes 2 and 3.

Front and rear access is required. See Notes 1 and 2.

NOTE

Minimum clearance of 6" (152mm) below unit is recommended for cable entry and exit

1. Service access is required at the front and rear.

2.Service access clearance dimensions: 36" (914mm) for units up to 150V to ground. 42" (1067mm) for units over 150V to ground.

3.Service access is required on the left side, if unit is equipped with Liebert Distribution Monitoring Option.

Table 3

Liebert FPC heat output

 

 

 

 

 

 

Full Load

 

 

 

Heat Output

 

Unit kVA

 

BTU/Hr (kW)

 

15

 

2,500 (0.73)

 

 

 

 

 

30

 

4,600 (1.35)

 

 

 

 

 

50

 

6,200 (1.82)

 

 

 

 

 

75

 

8,150 (2.39)

 

 

 

 

 

100

 

9,900 (2.90)

 

 

 

 

 

125

 

11,500 (3.37)

 

 

 

 

 

150

 

12,500 (3.66)

 

 

 

 

 

200

 

15,500 (4.54)

 

 

 

 

 

225

 

15,800 (4.63)

 

 

 

 

 

300

 

18,450 (5.40)

 

 

 

 

 

6

Image 10
Contents Liebert FPC Page Table of Contents Figures Important Safety Instructions Unpacking and Preliminary Inspection Unpacking and InstallationHandling Considerations Inch cabinet weight Front Footprint and Floor cable accessCutout Dimensions cooling airflow FrontUnit Preparation Location ConsiderationsLiebert FPC heat output See Notes 2 Front and rear access is required. See Notes 1Full Load Heat Output Unit kVA BTU/Hr kW Floor Pedestal Installation Floor pedestal detailsInput Power Connections Additional Distribution Mounting & WiringPower and Control Wiring Liebert FDC Distribution MountingElectrical connection location for 23 584mm cabinet FPC15000 Rev FPC15002 Rev Suggested minimum input wire size data Main input circuit breaker interrupting rating Low-voltage control junction box dimensions, typical Junction Box InstallationMain input junction box electrical connections 4 wire Main input power junction box dimensions, typicalSystem Grounding Equipment GroundingMinimum grounding electrode conductor size AWG Signal Reference GridGrounding Electrode Conductor for FPCs With Transformer Output VoltageTypical Liebert FPC With transformer grounding arrangement SystemTypical Liebert FPC without transformer groundingOutput Power Connections Liebert FPC Unit EPO Liebert FPC+24VDC MainLow Voltage Terminal Strip WiringFactory Typical control wiring for units with monitoring Optional Customer Alarm Inputs SummaryInternal Inspection ChecklistsWarranty StartupBranch circuit breaker torque specifications Torque specifications, generalPanelboard main circuit breaker torque specifications Terminal block compression lug torque specificationsInspection Unit Serial Number Unit Model Number DateStartup Monitoring System Check-Out Customer Alarms Normal System Turn on Startup ProceduresNormal System Shutdown Manual RestartBasic Monitor Panel Units Without Monitoring Power Monitor PanelAlarm Present/Silence FPC16000Operating Instructions RS-232 Ascii port customer commands Ascii interface default parametersParameter Default Monitored parameters data definitions Field # Data item UnitsRepair Inspection and CleaningInspection Schedule Page Ti n Ne tIti That