Emerson FPC user manual Output Power Connections

Page 22

Installation Instructions

1.3.5Output Power Connections

Output circuit breaker(s) and/or panelboards with ground and neutral provisions are provided inside the unit for connecting load(s) as required. (See Figures 5 through 8.)

Flexible output distribution cables for use in data processing areas under a raised floor are optional and may be factory-supplied. Cable lengths and layout should be well-planned:

Cable access—Cable routes should follow aisles between equipment. This will facilitate access to cables for installation, routine inspection and alterations.

Cable length—Measure the distance to the load equipment following right-angle paths, rather than diagonally or directly. Always measure to the extreme far side of the equipment with respect to the unit to ensure adequate cable length.

Air circulation—Prevent restriction of airflow under the raised floor by running the flexible con- duits flat on the subfloor, in parallel paths.

For best performance, the Liebert FPC should be installed as close as practical to the load.

Initial system output loading should be between 50% and 75% of rated capacity. This allows the addi- tion of loads without immediately investing in another power conditioner. The high partial-load effi- ciency of the FPC permits such sizing without imposing an energy-use penalty during initial operation.

Balancing of loads is good design practice on any 3-phase system. Accordingly, each distribution panel is load-balanced at the factory, based on output branch circuit breaker sizes. All additions to the sys- tem should be arranged so as to preserve this balance.

For phase-shifted, multi-output units, to ensure proper harmonic current cancellation, the loads should be balanced across the multiple outputs as well. For example, with a dual-output unit, the loads should be balanced across the six output phases. For a quadruple output unit, the loads should be balanced across the 12 output phases.

! WARNING

Verify that all incoming line voltage (power) and low-voltage (control) circuits are de-energized and locked out before installing cables or output breakers or making connections, whether in the junction box or in the unit.

Verify that incoming line voltage circuits are de-energized and locked out before installing output breakers and cables.

Code Compliance—All output cables and connections must comply with the NEC and all other applicable codes.

Padlock-OffProvisions—All output cables without receptacles that are hard-wired to the load equipment must be equipped with a padlock-off accessory for the output circuit breaker. The padlock-off accessory is to be used to lock-out and tag the circuit breaker when service is performed on the hard-wired load equipment in accordance with OSHA safety rules.

18

Image 22
Contents Liebert FPC Page Table of Contents Figures Important Safety Instructions Unpacking and Preliminary Inspection Unpacking and InstallationHandling Considerations Inch cabinet weight Front Footprint and Floor cable accessCutout Dimensions cooling airflow FrontUnit Preparation Location ConsiderationsLiebert FPC heat output See Notes 2 Front and rear access is required. See Notes 1Full Load Heat Output Unit kVA BTU/Hr kW Floor Pedestal Installation Floor pedestal detailsInput Power Connections Additional Distribution Mounting & WiringPower and Control Wiring Liebert FDC Distribution MountingElectrical connection location for 23 584mm cabinet FPC15000 Rev FPC15002 Rev Suggested minimum input wire size data Main input circuit breaker interrupting rating Low-voltage control junction box dimensions, typical Junction Box InstallationMain input junction box electrical connections 4 wire Main input power junction box dimensions, typicalSystem Grounding Equipment GroundingMinimum grounding electrode conductor size AWG Signal Reference GridGrounding Electrode Conductor for FPCs With Transformer Output VoltageTypical Liebert FPC With transformer grounding arrangement SystemTypical Liebert FPC without transformer groundingOutput Power Connections Liebert FPC Unit EPO Liebert FPC+24VDC MainLow Voltage Terminal Strip WiringFactory Typical control wiring for units with monitoring Optional Customer Alarm Inputs SummaryInternal Inspection ChecklistsWarranty StartupBranch circuit breaker torque specifications Torque specifications, generalPanelboard main circuit breaker torque specifications Terminal block compression lug torque specificationsInspection Unit Serial Number Unit Model Number DateStartup Monitoring System Check-Out Customer Alarms Normal System Turn on Startup ProceduresNormal System Shutdown Manual RestartBasic Monitor Panel Units Without Monitoring Power Monitor PanelAlarm Present/Silence FPC16000Operating Instructions RS-232 Ascii port customer commands Ascii interface default parametersParameter Default Monitored parameters data definitions Field # Data item UnitsRepair Inspection and CleaningInspection Schedule Page Ti n Ne tIti That