Installation Instructions

To minimize disturbances from other loads in the building, the 3-phase power input to the FPC should be supplied directly from the service entrance or other power source (a dedicated power feeder).

The input feeder circuit should be sized in accordance with the NEC and any local building codes to ensure the feeder’s ability to safely carry the system’s full load current, including losses.

Input feeder conductors should be sized for no more than 2% voltage drop. If operation at undervolt- age conditions for extended periods of time is desired, the input feeders must be oversized.

Typical conductor size data is shown in Table 4. All connections must comply with the NEC and all other applicable codes.

For units with a transformer, the main input feeder should consist of 3-phase conductors and one (safety) ground conductor (3W + G).

For units without a transformer, the main input feeder must consist of 3-phase conductors, one neu- tral and one (safety) ground conductor (4W + G).

Figure 5 Electrical connection location for 23" (584mm) cabinet

15006 - Rev. 0

9

Image 13
Contents Liebert FPC Page Table of Contents Figures Important Safety Instructions Unpacking and Preliminary Inspection Unpacking and InstallationHandling Considerations Inch cabinet weight Cutout Dimensions cooling airflow Footprint and Floor cable accessFront FrontLocation Considerations Unit PreparationLiebert FPC heat output See Notes 2 Front and rear access is required. See Notes 1Full Load Heat Output Unit kVA BTU/Hr kW Floor pedestal details Floor Pedestal InstallationPower and Control Wiring Additional Distribution Mounting & WiringInput Power Connections Liebert FDC Distribution MountingElectrical connection location for 23 584mm cabinet FPC15000 Rev FPC15002 Rev Suggested minimum input wire size data Main input circuit breaker interrupting rating Main input junction box electrical connections 4 wire Junction Box InstallationLow-voltage control junction box dimensions, typical Main input power junction box dimensions, typicalEquipment Grounding System GroundingGrounding Electrode Conductor for FPCs With Transformer Signal Reference GridMinimum grounding electrode conductor size AWG Output VoltageSystemTypical Liebert FPC without transformer grounding Typical Liebert FPC With transformer grounding arrangementOutput Power Connections Liebert FPC +24VDC Liebert FPCUnit EPO MainLow Voltage Terminal Strip WiringFactory Optional Customer Alarm Inputs Summary Typical control wiring for units with monitoringWarranty ChecklistsInternal Inspection StartupPanelboard main circuit breaker torque specifications Torque specifications, generalBranch circuit breaker torque specifications Terminal block compression lug torque specificationsUnit Serial Number Unit Model Number Date InspectionStartup Monitoring System Check-Out Customer Alarms Normal System Shutdown Startup ProceduresNormal System Turn on Manual RestartAlarm Present/Silence Power Monitor PanelBasic Monitor Panel Units Without Monitoring FPC16000Operating Instructions RS-232 Ascii port customer commands Ascii interface default parametersParameter Default Field # Data item Units Monitored parameters data definitionsRepair Inspection and CleaningInspection Schedule Page Iti Ne tTi n That