Emerson FPC user manual Front, Footprint and Floor cable access, Cutout Dimensions cooling airflow

Page 8

Installation Instructions

Figure 2 Typical cabinet and floor planning dimension data, 47" (1194mm) cabinet 50-300kVA

Overall Dim.

39-1/2" (1003mm) Including hinge and bezel

projection

Overhead clearance

of 18" (457mm) recommended

for cooling airflow

Minimum side clearance

of 42" (1067mm) recommended for service access if unit is equipped with distribution monitoring option

Overall Dimension 48.6" (1235mm) including side panels

 

 

1.3"

 

 

(33mm)

 

33.8" (859mm)

6" (152mm)

 

35" (889mm)

 

1.3"

 

6" (152mm)

(33mm)

 

 

Front

Shaded area indicates

 

 

78-1/2"

Footprint and Floor cable access and

(1995mm)

Cutout Dimensions cooling airflow

Shaded areas indicate

47"

.4"

36

recommended clearance

(1194mm)

(925mm)

of 42" (1067mm) at front and

rear for service access

Unit Base Outline

Cabinet Dimensional Data

 

For units with bottom cable access, clearance of 6" (152mm) below unit is recommended for cooling airflow and cable entry/exit

36.4" (925mm)

Unit Base Outline

Front

47" (1194mm) 43.8"

(1112mm) 1.5" (38mm)

2.3" (58mm)

Floor Pedestals

Dia. location

available from

3/4" (19mm)

typical

6" (152mm) to

 

18" (457mm)

 

Optional Floor Pedestals

(152mm) 6"

9/16" (14mm) diameter; 4 holes typical

6" (152mm)

Table 2

47-inch cabinet weight

 

 

 

 

 

Unit

 

 

Weight, lb (kg)

 

 

 

 

kVA

 

60 Hz

50 Hz

Without Transformer

 

 

 

 

 

50

 

1891 (858)

1966 (892)

1335 (606)

75

 

1995 (905)

2095 (950)

1335 (606)

100

 

2191 (994)

2316 (1051)

1335 (606)

125

 

2298 (1042)

2423 (1099)

1360 (617)

150

 

2490 (1129)

2640 (1198)

1360 (617)

200

 

2610 (1184)

2810 (1275)

1360 (617)

225

 

2800 (1270)

3000 (1361)

1390 (631)

300

 

2845(1290)

3045 (1381)

1390 (631)

4

Image 8
Contents Liebert FPC Page Table of Contents Figures Important Safety Instructions Handling Considerations Unpacking and InstallationUnpacking and Preliminary Inspection Inch cabinet weight Footprint and Floor cable access Cutout Dimensions cooling airflowFront FrontUnit Preparation Location ConsiderationsFull Load Heat Output Unit kVA BTU/Hr kW See Notes 2 Front and rear access is required. See Notes 1Liebert FPC heat output Floor Pedestal Installation Floor pedestal detailsAdditional Distribution Mounting & Wiring Power and Control WiringInput Power Connections Liebert FDC Distribution MountingElectrical connection location for 23 584mm cabinet FPC15000 Rev FPC15002 Rev Suggested minimum input wire size data Main input circuit breaker interrupting rating Junction Box Installation Main input junction box electrical connections 4 wireLow-voltage control junction box dimensions, typical Main input power junction box dimensions, typicalSystem Grounding Equipment GroundingSignal Reference Grid Grounding Electrode Conductor for FPCs With TransformerMinimum grounding electrode conductor size AWG Output VoltageTypical Liebert FPC With transformer grounding arrangement SystemTypical Liebert FPC without transformer groundingOutput Power Connections Liebert FPC Liebert FPC +24VDCUnit EPO MainFactory WiringLow Voltage Terminal Strip Typical control wiring for units with monitoring Optional Customer Alarm Inputs SummaryChecklists WarrantyInternal Inspection StartupTorque specifications, general Panelboard main circuit breaker torque specificationsBranch circuit breaker torque specifications Terminal block compression lug torque specificationsInspection Unit Serial Number Unit Model Number DateStartup Monitoring System Check-Out Customer Alarms Startup Procedures Normal System ShutdownNormal System Turn on Manual RestartPower Monitor Panel Alarm Present/SilenceBasic Monitor Panel Units Without Monitoring FPC16000Operating Instructions Parameter Default Ascii interface default parametersRS-232 Ascii port customer commands Monitored parameters data definitions Field # Data item UnitsInspection Schedule Inspection and CleaningRepair Page Ne t ItiTi n That