Installation Instructions
Figure 2 Typical cabinet and floor planning dimension data, 47" (1194mm) cabinet 50-300kVA 
Overall Dim.
 and bezel
 and bezel
projection
Overhead clearance 
of 18" (457mm) recommended
for cooling airflow
Minimum side clearance
of 42" (1067mm) recommended for service access if unit is equipped with distribution monitoring option
Overall Dimension 48.6" (1235mm)  including side panels
including side panels
| 
 | 
 | 1.3" | |
| 
 | 
 | (33mm) | |
| 
 | 33.8" (859mm) | 6" (152mm) | |
| 
 | 35" (889mm) | ||
| 
 | 1.3" | ||
| 
 | 6" (152mm) | ||
| (33mm) | |||
| 
 | |||
| 
 | Front | Shaded area indicates | |
| 
 | 
 | ||
| Footprint and Floor cable access and | |||
| (1995mm) | Cutout Dimensions cooling airflow | ||
| Shaded areas indicate | 47" | .4" | 
| 36 | ||
| recommended clearance | (1194mm) | (925mm) | 
of 42" (1067mm) at front and
| rear for service access | Unit Base Outline | |
| Cabinet Dimensional Data | ||
| 
 | 
For units with bottom cable access, clearance of 6" (152mm) below unit is recommended for cooling airflow and cable entry/exit
36.4" (925mm)
Unit Base Outline 
Front
 47" (1194mm) 43.8"
 47" (1194mm) 43.8"
(1112mm) 
 1.5" (38mm)
 1.5" (38mm)
2.3" (58mm)
| Floor Pedestals | Dia. location | |
| available from | 3/4" (19mm) | |
| typical | ||
| 6" (152mm) to | ||
| 
 | ||
| 18" (457mm) | 
 | 
Optional Floor Pedestals
(152mm) 6"
 6"
9/16" (14mm) diameter; 4 holes typical
6" (152mm)
| Table 2 | 
 | |||
| 
 | 
 | 
 | 
 | 
 | 
| Unit | 
 | 
 | Weight, lb (kg) | |
| 
 | 
 | 
 | 
 | |
| kVA | 
 | 60 Hz | 50 Hz | Without Transformer | 
| 
 | 
 | 
 | 
 | 
 | 
| 50 | 
 | 1891 (858) | 1966 (892) | 1335 (606) | 
| 75 | 
 | 1995 (905) | 2095 (950) | 1335 (606) | 
| 100 | 
 | 2191 (994) | 2316 (1051) | 1335 (606) | 
| 125 | 
 | 2298 (1042) | 2423 (1099) | 1360 (617) | 
| 150 | 
 | 2490 (1129) | 2640 (1198) | 1360 (617) | 
| 200 | 
 | 2610 (1184) | 2810 (1275) | 1360 (617) | 
| 225 | 
 | 2800 (1270) | 3000 (1361) | 1390 (631) | 
| 300 | 
 | 2845(1290) | 3045 (1381) | 1390 (631) | 
4