Delta PD-01 user manual Examples for PKW mechanism, Pke

Page 20

PD-01 PROFIBUS-DP Module

Examples for PKW mechanism

Example 1: Read data of parameter P0003

To read value of P0003, set the request ID to 1 (request parameter value - word). Because P0003 is less than 2000, the Para Page Select is 0, thus, the data sequence are as follows:

Master PD-01

: 1003 0000 0000 0000

request value of P0003

PD-01 Master

: 1003 0000 0000 1770

 

Request

Word 1

(PKE)

1003

 

 

 

Word 2

(IND)

0000

 

 

 

Word 3

(PWE1)

0000

 

 

 

Word 4

(PWE2)

0000

 

 

 

Response

Word 1

(PKE)

1003

 

 

 

Word 2

(IND)

0000

 

 

 

Word 3

(PWE1)

0000

 

 

 

Word 4

(PWE2)

1770

 

 

 

PD-01 responds the value of P0003. All parameters in VFD series Drives are 16-bit value, so the value is transferred in PWE2 (4th word). The value of P0003 is 0x1770 (6000 decimal), in VFD-M series Drives, it is “Maximum Output Frequency”.

Example 2: Read command frequency in VFD series Drives (0x2102)

To read value of command frequency, set the request ID to1, we should set the Para Page Select because the parameter address is greater than 2000. The address 0x2102 is 8450 in decimal, if set Page Select to 4, then the Basic PNU is 8450 –

4*2000 = 450 (0x1c2), thus, the data sequence are as follows:

Master PD-01 : 11C2

2000 0000 0000

request value of address

0x2102

 

 

PD-01 Master : 11C2

2000 0000 0868

 

Request

Word 1

(PKE)

11C2

 

 

 

Word 2

(IND)

2000

 

 

 

Word 3

(PWE1)

0000

 

 

 

Word 4

(PWE2)

0000

 

 

 

Response

Word 1

(PKE)

11C2

 

 

 

Word 2

(IND)

2000

 

 

 

Word 3

(PWE1)

0000

 

 

 

Word 4

(PWE2)

0868

 

 

 

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

17

Image 20
Contents PROFIBUS-DP Module for VFD Series Drives Table of Contents Chapter User Parameters Setting in GSD file Chapter TroubleshootingPreface Using this Manual Receiving and InspectionDelta AC Drive Firmware Version VFD-MOverview SP LED NET LEDTechnical information FunctionalityIntroduction ProfibusPROFIBUS-DP Installation Installing the PD-01RJ11 Removing the PD-01 Pin assignment of PROFIBUS-DP interface DB9Terminator DgndA1 S B1 121ohm Profibus address Parameters setting in VFD series DrivesCommunication Useful data structure as defined in PROFIDrive Profile Extended configurationCyclical data of PD-01 via PROFIBUS-DP Default settings of PZD structure Control and Status wordsStatus word data from VFD series Drives to DP Response Identifier Meaning Accessing parameters via PKW areaRequest Identifier Meaning Parameter value PWE 3rd and 4th word PKE IND PWE1 PWE2 High LOWPNU Examples for PKW mechanism PKE1034 Response time about PD-01 VFDMax update time = T1 + T2 70ms + T3 User Parameters Setting in GSD file GSD file= VFD Drives = VfddrvOrdernumber PZD PD-01 PROFIBUS-DP Module User parameters in GSD file UintName Type Description Default Data Input Name Type Description Default LossSPComTreat PD-01 PROFIBUS-DP Module Troubleshooting Troubleshooting via LED displaysLED OFFTroubleshooting via diagnostic data Troubleshooting via error codes Code Meaning Corrective activesCode Meaning Corrective actives Dimensions