NOTE:
Table above is for reference only, please check VFD series Drives user manual for
details.
Accessing parameters via PKW area
In cyclical data,
PKW have at least 4 words:
Word 1 | Parameter ID (PKE) |
|
|
| |||
| 15 | 12 |
| 11 | 10 |
| 0 |
| AK |
|
| SPM | Parameter number (PNU) |
| |
Word 2 | Parameter |
|
| ||||
| 15 |
|
|
| 8 | 7 | 0 |
Word 3 | PWE1 |
| reserved in |
|
| ||
Word 4 | PWE2 |
| parameter value of read/write |
|
PKE
Bits 0 to 10 (PNU) contain the number of the relevant parameter.
Bit 11 is reserved.
Bits 12 to 15 (AK) contain the request or the response identifier.
Request identifier (master | ||
| Request Identifier | Meaning |
| 0 | No request |
| 1 | Request parameter value |
| 2 | Modify parameter value (word) |
Response identifier
Response Identifier | Meaning |
0 | No response |
1 | Transfer parameter value (word) |
7 | Cannot process request (with error number) |
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED | 15 |