PD-01 PROFIBUS-DP Module

Fault numbers for "Cannot process request" response

NO.

 

Meaning

0

Illegal Parameter number

Parameter does not exist

1

Parameter value cannot

Parameter is a read-only parameter

be modified

or can not change in current state

 

2

Minimum/maximum not

 

reached / exceeded

 

 

 

18

Other error

 

IND

Structure of IND for cyclical communication via PPOs

 

 

 

PKE

 

 

IND

PWE1

 

 

PWE2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

LOW

HIGH

LOW

HIGH

LOW

HIGH

LOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

14

13

12 11-8

7

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Para Page selection Not used

20 23 22 21 0

Function of Parameter Page Selection

Basic PNU

Page selection

Total PNU

(B.PNU bit 10-0 of PKE)

(P.PNU)

(B.PNU+P.PNU*2000)

0…1999

0

0…1999

 

 

 

0…1999

1

2000…3999

 

 

 

0…1999

2

4000…4999

 

 

 

 

 

 

0…1999

15

30000…31999

 

 

 

NOTE:

In IND, Bit 15 uses a multiplier of 20, so the value of Bit 15 for the access P2000- P3999 must be set to 1.

Parameter value (PWE) 3rd and 4th word

All parameters in VFD series Drives are 16-bit. A 16-bit parameter value is transferred in PWE2 (4th word). PWE1 (3rd word) must be set to 0 on the PROFIBUS-DP master in this case.

16DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

Image 19
Contents PROFIBUS-DP Module for VFD Series Drives Table of Contents Chapter Troubleshooting Chapter User Parameters Setting in GSD filePreface VFD-M Using this ManualReceiving and Inspection Delta AC Drive Firmware VersionSP LED NET LED OverviewFunctionality Technical informationProfibus IntroductionPROFIBUS-DP Installing the PD-01 InstallationRJ11 Dgnd Removing the PD-01Pin assignment of PROFIBUS-DP interface DB9 TerminatorA1 S B1 121ohm Communication Parameters setting in VFD series DrivesProfibus address Cyclical data of PD-01 via PROFIBUS-DP Extended configurationUseful data structure as defined in PROFIDrive Profile Control and Status words Default settings of PZD structureStatus word data from VFD series Drives to DP Request Identifier Meaning Accessing parameters via PKW areaResponse Identifier Meaning PNU PKE IND PWE1 PWE2 High LOWParameter value PWE 3rd and 4th word PKE Examples for PKW mechanism1034 VFD Response time about PD-01Max update time = T1 + T2 70ms + T3 = Vfddrv User Parameters Setting in GSD fileGSD file = VFD DrivesOrdernumber PZD PD-01 PROFIBUS-DP Module Uint User parameters in GSD fileName Type Description Default Data Input Name Type Description Default LossSPComTreat PD-01 PROFIBUS-DP Module OFF TroubleshootingTroubleshooting via LED displays LEDTroubleshooting via diagnostic data Code Meaning Corrective actives Troubleshooting via error codesCode Meaning Corrective actives Dimensions