Delta PD-01 user manual Troubleshooting via LED displays, Led, Off, Profibus

Page 32

PD-01 PROFIBUS-DP Module

Chapter 6 Troubleshooting

Troubleshooting via LED displays

Two LEDs, SP and NET LED, are used to monitor the PD-01 communication status.

Possible LED displays of NET LED:

LED

Indication

Corrective Actions

OFF

No Power Supply

Verify that the power supply of PD-01.

 

 

Check whether the power supply is

 

 

connected and that power is applied to

 

 

the PD-01 through the connector.

Red, flickering (rapid

Invalid PROFIBUS address

Check whether the switch value is

blinking)

set via switch

valid, valid value of slave is within

 

 

1-125. Set the valid value and re-power

Red, blinking

Communication link to

User parameter are sent by master

 

PROFIBUS, but No cyclical

(from GSD file), for example, if d_state

 

data exchanged, or

is set 1, ensure the data in Data Output

 

Extended user parameter

1 ~ Data Output 1 + dout_len are

 

error

continuous addresses. Otherwise,

 

 

PD-01 will not be able to pass the

 

 

Parameterization check.

Red ON

No connection to

1. Verify that network installation is OK.

 

PROFIBUS

2. Verify that PLC is working.

 

 

3. Verify that switch address setting is

 

 

correct.

Green, blinking

“Master” is in “Stop” mode,

Turn the KEY of PLC to RUN mode,

 

and cyclical process data

and send the control command to

 

exchange in progress, but

PD-01.

 

set-points invalid (control

 

 

word = 0)

 

Green ON

Cyclic data exchange in

 

 

progress and OK

 

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

29

Image 32
Contents PROFIBUS-DP Module for VFD Series Drives Table of Contents Chapter User Parameters Setting in GSD file Chapter TroubleshootingPreface Using this Manual Receiving and InspectionDelta AC Drive Firmware Version VFD-MOverview SP LED NET LEDTechnical information FunctionalityIntroduction ProfibusPROFIBUS-DP Installation Installing the PD-01RJ11 Removing the PD-01 Pin assignment of PROFIBUS-DP interface DB9Terminator DgndA1 S B1 121ohm Profibus address Parameters setting in VFD series DrivesCommunication Useful data structure as defined in PROFIDrive Profile Extended configurationCyclical data of PD-01 via PROFIBUS-DP Default settings of PZD structure Control and Status wordsStatus word data from VFD series Drives to DP Response Identifier Meaning Accessing parameters via PKW areaRequest Identifier Meaning Parameter value PWE 3rd and 4th word PKE IND PWE1 PWE2 High LOWPNU Examples for PKW mechanism PKE1034 Response time about PD-01 VFDMax update time = T1 + T2 70ms + T3 User Parameters Setting in GSD file GSD file= VFD Drives = VfddrvOrdernumber PZD PD-01 PROFIBUS-DP Module User parameters in GSD file UintName Type Description Default Data Input Name Type Description Default LossSPComTreat PD-01 PROFIBUS-DP Module Troubleshooting Troubleshooting via LED displaysLED OFFTroubleshooting via diagnostic data Troubleshooting via error codes Code Meaning Corrective activesCode Meaning Corrective actives Dimensions