Delta PD-01 user manual Troubleshooting via diagnostic data

Page 33

PD-01 PROFIBUS-DP Module

Possible LED displays of SP LED:

LED

Indication

Corrective Actions

OFF

No Power Supply

Verify that the power supply of PD-01.

 

 

Check whether the power supply is

 

 

connected and that power is applied to

 

 

the PD-01 through the connector.

Red, blinking

CRC check fault

Check your communication setting in

 

 

AC Drive (9600, <8,N,2>, RTU)

 

 

 

Red ON

Connection failure, or

1. Check whether the connections

 

No connection

between AC Drive and RS485 of

 

 

PD-01 are all correct

 

 

2. Re-wire the connections between AC

 

 

Drive and ensure that the wire

 

 

specification is correct.

Green, blinking

AC Drive returns error code

1. Check the AC Drive type and version.

 

 

Not all Delta VFD series Drive are

 

 

supported.

 

 

2. Check the PLC program, and ensure

 

 

the operating address in PD-01 is

 

 

correct.

Green ON

Normal

 

NOTE:

If both SP LED and NET LED are in steady orange, it indicates that PD-01 has entered into the “test mode”. Please do not set the value of address switch of PD-01 to 0XFF at this time. Be sure to set other value and energize PD-01 again.

Troubleshooting via diagnostic data

PD-01 provides 16 bytes diagnostic data when the alarm occurs and when user parameter setting “LossSPComTreat” is set to “Continue data exchange and report alarm”. It includes 6 bytes standard diagnostic data and 10 bytes device related diagnostic data. The following table shows the meanings of the 16 bytes:

Byte 1-6

Byte 7

Byte 8

Byte 9

Byte 10

 

 

 

 

Byte 16

Standard

Length in bytes

SP communication

Error code

Reserved

diagnostic data

 

status

 

 

Byte 7 indicates the length of device related diagnostic data including itself, so if byte 7 is 10 (0Ahex), it indicate device related to diagnostic data have 10 bytes (including byte 7).

Byte 8 indicates the SP communication status when the alarm occurs, and the valid value should be as follows:

30 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

Image 33
Contents PROFIBUS-DP Module for VFD Series Drives Table of Contents Chapter Troubleshooting Chapter User Parameters Setting in GSD filePreface Receiving and Inspection Using this ManualDelta AC Drive Firmware Version VFD-MSP LED NET LED OverviewFunctionality Technical informationProfibus IntroductionPROFIBUS-DP Installing the PD-01 InstallationRJ11 Pin assignment of PROFIBUS-DP interface DB9 Removing the PD-01Terminator DgndA1 S B1 121ohm Parameters setting in VFD series Drives CommunicationProfibus address Extended configuration Cyclical data of PD-01 via PROFIBUS-DPUseful data structure as defined in PROFIDrive Profile Control and Status words Default settings of PZD structureStatus word data from VFD series Drives to DP Accessing parameters via PKW area Request Identifier MeaningResponse Identifier Meaning PKE IND PWE1 PWE2 High LOW PNUParameter value PWE 3rd and 4th word PKE Examples for PKW mechanism1034 VFD Response time about PD-01Max update time = T1 + T2 70ms + T3 GSD file User Parameters Setting in GSD file= VFD Drives = VfddrvOrdernumber PZD PD-01 PROFIBUS-DP Module Uint User parameters in GSD fileName Type Description Default Data Input Name Type Description Default LossSPComTreat PD-01 PROFIBUS-DP Module Troubleshooting via LED displays TroubleshootingLED OFFTroubleshooting via diagnostic data Code Meaning Corrective actives Troubleshooting via error codesCode Meaning Corrective actives Dimensions