PD-01 PROFIBUS-DP Module
00 – Normal
01 – CRC check failure
02 – VFD series Drive returns error code
03 – Communication is time out and disconnected
Byte 9 indicates the error code when byte 8 is 02 (VFD series Drive returns error code). Refer to the Section 6.3 for the meanings of invalid code.
Other word, user can get the diagnostic data via PZD area any time.
Address | 0x7500 | 0x7501 | 0x7502 | 0x7503 | 0x7504 | |||||
High | Low | High | Low | High | Low | High | Low | High | Low | |
| byte | byte | byte | byte | byte | byte | byte | byte | byte | byte |
| SP | Error |
|
|
|
|
|
|
|
|
Meaning | comm |
|
| Reserved, read to 0 |
|
| ||||
code |
|
|
|
| ||||||
| status |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
User can get these data through “Data Output 1”, or 2, or 3, or 4 in user parameters. For example, if set the “Data Output 1” to 0x7500 means get the diagnostic data from 0x7500, and get the return data from address 0x7500 in 1st word of PZD area.
NOTE:
These special addresses are
Troubleshooting via error codes
If there is a communication error detected between
VFD series Drives can process the message from
| Code | Meaning | Corrective actives |
|
| 01 | Illegal command code | 1. Check the Request Identifier in PKW area. |
|
|
| The command code received in the |
| |
|
| command message is not available |
| |
|
| 2. |
| |
|
| for the drives. |
|
|
| 02 | Illegal data address | 1. Check the Parameter number in PKW area, |
|
|
| The data address received in the | and refer the user manual of VFD Drives. |
|
|
| command message is not available | 2. Check the settings of user parameters “Data |
|
|
| for the drives. | Input 1” to “Data Input 4” and “Data Output |
|
|
|
| 1” to “Data Output 4”, and refer to the user |
|
|
|
| manual of VFD series Drives. |
|
|
|
| 3. |
|
|
|
|
|
|
|
|
|
|
|
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED | 31 |
|