Delta PD-01 user manual Code Meaning Corrective actives

Page 35

PD-01 PROFIBUS-DP Module

Code

Meaning

Corrective actives

03

Illegal data value

1. Check the parameter data (PWE2) in PKW

 

The data value received in the

area, and refer the user manual of VFD series

 

command message is not

Drives.

 

available for the drives.

2. Check the PLC program to confirm the data

 

 

that transmitted to PD-01 from master is valid.

 

 

3. Re-supply power to PD-01.

 

 

 

04

Slave device failure

1. Check all data in PKW.

 

The drive is unable to perform the

 

2. Re-supply power to PD-01.

 

requested action.

 

VFD series Drives will not respond message to PD-01 if it receives an invalid message from PD-01, but error code shown in the table below will be displayed on the digital keypad.

Code

Meaning

Corrective actives

05

Reserved

 

06

AC Drive is busy

 

07

Reserved

 

08

Reserved

1. Please refer to section 4.2 in this manual

09

Check sum is error

and check the setting of VFD series Drives.

10

Time out

2. If the error still exists, return it to factory.

11

Baud rate or protocol is invalid

 

12

Message is too short

 

13

Message is too long

 

14

Message contain invalid character

 

32DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

Image 35
Contents PROFIBUS-DP Module for VFD Series Drives Table of Contents Chapter Troubleshooting Chapter User Parameters Setting in GSD filePreface VFD-M Using this ManualReceiving and Inspection Delta AC Drive Firmware VersionSP LED NET LED OverviewFunctionality Technical informationProfibus IntroductionPROFIBUS-DP Installing the PD-01 InstallationRJ11 Dgnd Removing the PD-01Pin assignment of PROFIBUS-DP interface DB9 TerminatorA1 S B1 121ohm Profibus address Parameters setting in VFD series DrivesCommunication Useful data structure as defined in PROFIDrive Profile Extended configurationCyclical data of PD-01 via PROFIBUS-DP Control and Status words Default settings of PZD structureStatus word data from VFD series Drives to DP Response Identifier Meaning Accessing parameters via PKW areaRequest Identifier Meaning Parameter value PWE 3rd and 4th word PKE IND PWE1 PWE2 High LOWPNU PKE Examples for PKW mechanism1034 VFD Response time about PD-01Max update time = T1 + T2 70ms + T3 = Vfddrv User Parameters Setting in GSD fileGSD file = VFD DrivesOrdernumber PZD PD-01 PROFIBUS-DP Module Uint User parameters in GSD fileName Type Description Default Data Input Name Type Description Default LossSPComTreat PD-01 PROFIBUS-DP Module OFF TroubleshootingTroubleshooting via LED displays LEDTroubleshooting via diagnostic data Code Meaning Corrective actives Troubleshooting via error codesCode Meaning Corrective actives Dimensions