Toshiba VF-MB1/S15 instruction manual Example 1 Hz Forward running and Deceleration stop

Page 16

E6581738

3.4.1.Examples of driving by the State Machine

When using the PROFIdrive profile, the frequency reference is set to HSW. The setting value “0x0000” - ”0x4000” is equivalent to ”0” - ”Base frequency (parameter fh)”. When the reverse operation, the frequency reference is set with two's complement of the forward frequency reference. During running, HIW shows a output frequency.

*fmod or cmod is set to “Communication option” on these examples.

3.4.1.1.Example 1. 60Hz Forward running and Deceleration stop

Set ”0x4000” to HSW and the following is set to STW in order.

0000 0100 0000 0110 (= 0x0406)

“READY TO SWITCH-ON”

0000 0100 0000 0111 (= 0x0407)

“READY TO OPERATE”

0000 0100 0111 1111 (= 0x047F)

“OPERATION”

0000 0100 0111 1110 (= 0x047E) “OFF1 ACTIVE (Normal Stop)”

3.4.1.2.Example 2. 30Hz Reverse running

When the reverse operation, “0xE000” is set to HSW. “0xE000” is two's complement of the “0x2000” as the forward frequency reference 30Hz.

The Setup to STW is same as the Example 1.

3.4.1.3. Example 3. Inching and pause

the following is set to STW in order.

0000 0100 0000 0110 (= 0x0406)

“READY TO SWITCH-ON”

0000 0100 0000 0111 (= 0x0407)

“READY TO OPERATE”

0000 0101 0000 1111 (= 0x050F) “Jogging 1 ACTIVE”

0000 0100 0100 1111 (= 0x040F) “Jogging 1 PAUSE”

* The inching frequency is according to the parameter c154, c155 on VF-MB1/S15.

- 14 -

Image 16
Contents Tosvert VF-MB1/S15 Contents Introduction Safety precautions E6581738 E6581738 E6581738 Exterior features Connection InformationStatus indicator DX Data exchange Green LEDVF-MB1/S15 Communication parameters Profile TelegramPDP003Z supports only speed control mode Bit Value Name STW Control Word DataZSW Status Word Data Bit Valure NameSetpoint Actual value 15s 20s 25s 30sTmax ZSW BitState Machine Example 1 Hz Forward running and Deceleration stop Access to the Profibus parameter AK Request from Master to PDP003Z)Value Mode Profibus parameter PNUExample 1. Reading the PNU 922 Telegram 13 9AAccess to VF-MB1/S15 parameter Response Value 0x03E8 = 1000 10.00Hz Vendor Spec. Profile How to use Profibus MasterOverview of the VF-MB1/S15 parameter Bit Function2. fa23 Communication command Specified data output ST=ON ST=OFF E6581738 RES RY-RC Diagnostic DP-V1 function MasterProfibs DP-V1 Communication VF-MB1/S15Example1. Read the PROFIdrive parameter Example 2. Change the PROFIdrive parameter 0x020x9F 0x82Example 3. Read the VF-MB1/S15 parameter 0xE80xFD 0x310x30 Example 4. Change the VF-MB1/S15 parameter0x07 Profibus Local/Remote Operation GSD fileAppendix Function number