Toshiba Understanding VF-S15 Parameters: Access and Configuration Guide

Page 20

E6581738

3.7.Access to VF-MB1/S15 parameter

When access to VF-MB1/S15 parameter, set “1” to the PNU. The communication number of the drive parameter is set to the subindex IND.

Refer to the drive instruction manual about the communication number and unit.

*This procedure changes the value of VF-MB1/S15 EEPROM.

3.7.1.Examples of reading or changing VF-MB1/S15 parameter

3.7.1.1. Example 1. Reading the basic parameter (cmod (command mode selection))

AK = 6 (Request parameter value (array))

SPM = 0

PNU = 1

IND = 0x0003 (cmod communication number)

PKE

0

1

1

0

0

0

0

0

0

0

0

0

0

0

0

1

 

6

 

 

 

 

 

0

 

 

 

0

 

 

 

1

 

Requirement

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKW

 

 

 

 

 

 

 

 

 

 

 

PZD

 

 

 

 

PKE

 

 

IND

 

 

PWE

 

 

 

 

 

 

 

 

 

60

01

 

00

03

 

 

00

00

00

 

00

・・・

・・・

 

 

 

Response (Value: 0x0001 = Operation panel))

40

01

00

03

00

00

00

01

・・・ ・・・

3.7.1.2. Example 2. Reading the extended parameter (f219 (VIC input point 2 frequency))

AK = 6 (Request parameter value (array))

SPM = 0

PNU = 1

IND = 0x0219 (f219 communication number)

PKE

0

1

1

0

0

0

0

0

0

0

0

0

0

0

0

1

 

6

 

 

 

 

 

0

 

 

 

0

 

 

 

1

 

Requirement

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKW

 

 

 

 

 

 

 

 

 

 

 

PZD

 

 

 

 

PKE

 

 

IND

 

 

PWE

 

 

 

 

 

 

 

 

 

60

01

 

02

19

 

 

00

00

00

 

00

・・・

・・・

 

 

 

Response (Value: 0x1770 (= 6000 -> 60.00Hz *))

40

01

02

19

00

00

17

70

・・・ ・・・

*“0x1770” as reading value of “VIC input point 2 frequency” is 0x1770 = 6000 (decimal number)

Since the unit of “VIC input point 2 frequency” is 0.01Hz, set the following value. 6000×0.01 = 60.00Hz

- 18 -

Image 20
Contents Tosvert VF-MB1/S15 Contents Introduction Safety precautions E6581738 E6581738 E6581738 Exterior features Connection InformationStatus indicator DX Data exchange Green LEDVF-MB1/S15 Communication parameters Profile TelegramPDP003Z supports only speed control mode Bit Value Name STW Control Word DataZSW Status Word Data Bit Valure NameSetpoint Actual value 15s 20s 25s 30sTmax ZSW BitState Machine Example 1 Hz Forward running and Deceleration stop Access to the Profibus parameter AK Request from Master to PDP003Z)Value Mode Profibus parameter PNUExample 1. Reading the PNU 922 Telegram 13 9AAccess to VF-MB1/S15 parameter Response Value 0x03E8 = 1000 10.00Hz Vendor Spec. Profile How to use Profibus MasterOverview of the VF-MB1/S15 parameter Bit Function2. fa23 Communication command Specified data output ST=ON ST=OFF E6581738 RES RY-RC Diagnostic DP-V1 function MasterProfibs DP-V1 Communication VF-MB1/S15Example1. Read the PROFIdrive parameter Example 2. Change the PROFIdrive parameter 0x020x9F 0x82Example 3. Read the VF-MB1/S15 parameter 0xE80xFD 0x310x07 Example 4. Change the VF-MB1/S15 parameter0x30 Profibus Local/Remote Operation GSD fileAppendix Function number