3.2.STW Control Word Data

PDP003Z supports only speed control mode.

Bit

Value

Name

Note

 

 

 

 

0

1

ON

“Switched on” condition

0

OFF

Normal stop.

 

 

 

 

 

1

1

No Coast Stop

All "Coast Stop (OFF2)" commands are withdrawn

0

Coast Stop (OFF 2)

Coast stop.

 

 

 

 

 

2

1

No Quick Stop

All "Quick Stop (OFF3)" commands are withdrawn.

0

Quick Stop (OFF 3)

Quick Stop

 

 

 

 

 

3

1

Enable Operation

The drive then runs-up to the setpoint.

0

Disable Operation

Normal stop.

 

 

 

 

 

4

1

Enable Ramp Generator

-

0

Reset Ramp Generator

Output of the RFG is set to 0.

 

 

 

 

 

5

1

Unfreeze Ramp Generator

-

0

Freeze Ramp Generator

Freeze the actual setpoint entered by the RFG *.

 

 

 

 

 

6

1

Enable Setpoint

The value selected at the input of the RFG is switched-in.

0

Disable Setpoint

The value selected at the input of the RFG is set to 0.

 

 

 

 

 

7

1

Fault Acknowledge

Fault reset (0 -> 1)

0

No meaning

-

 

 

 

 

 

8

1

JOG 1 ON **

VF-MB1/S15 drives with JOG 1 speed 1 (c154).

0

JOG 1 OFF

Jogging stop, if "JOG 1" was previously ON. Stop drive

 

 

according to VF-MB1/S15 setting parameter.

 

 

 

9

1

JOG 2 ON **

VF-MB1/S15 drives with JOG 2 speed 2 (c155).

0

JOG 2 OFF

Jogging stop, if "JOG 2" was previously ON. Stop drive

 

 

according to VF-MB1/S15 setting parameter.

 

 

 

10

1

Control By PLC

The control word and main setpoint are activated.

0

No Control By PLC

The control word and main setpoint are inactivated.

 

 

 

 

 

11

---

Device-specification

(Reserved.)

 

 

 

 

12

1

Net Control

PDP003Z control is enabled.

 

 

 

 

0

Local Control

PDP003Z control is disabled.

 

 

 

 

13

1

Net Reference

PDP003Z reference is enabled.

0

Local Reference

PDP003Z reference is disabled.

 

 

 

 

 

14

---

Device-specification

(Reserved.)

 

 

 

 

15

---

Device-specification

(Reserved.)

 

 

 

 

*RFG: Ramp Function Generator

**Operation is enabled, drive is in standstill and STW1 bit 4, 5, 6 = 0.

- 10 -

Image 12
Contents Tosvert VF-MB1/S15 Contents Introduction Safety precautions E6581738 E6581738 E6581738 Exterior features Connection InformationStatus indicator DX Data exchange Green LEDVF-MB1/S15 Communication parameters Profile TelegramPDP003Z supports only speed control mode Bit Value Name STW Control Word DataZSW Status Word Data Bit Valure NameSetpoint Actual value 15s 20s 25s 30sTmax ZSW BitState Machine Example 1 Hz Forward running and Deceleration stop Access to the Profibus parameter AK Request from Master to PDP003Z)Value Mode Profibus parameter PNUExample 1. Reading the PNU 922 Telegram 13 9AAccess to VF-MB1/S15 parameter Response Value 0x03E8 = 1000 10.00Hz Vendor Spec. Profile How to use Profibus MasterOverview of the VF-MB1/S15 parameter Bit Function2. fa23 Communication command Specified data output ST=ON ST=OFF E6581738 RES RY-RC Diagnostic DP-V1 function MasterProfibs DP-V1 Communication VF-MB1/S15Example1. Read the PROFIdrive parameter Example 2. Change the PROFIdrive parameter 0x020x9F 0x82Example 3. Read the VF-MB1/S15 parameter 0xE80xFD 0x31Example 4. Change the VF-MB1/S15 parameter 0x300x07 Profibus Local/Remote Operation GSD fileAppendix Function number