6.1.Example1. Read the PROFIdrive parameter

6.1.1.Write Request data table (Read PNU 964 (0x03C4) IND 4)

Field

Description

Value

Header DU0

Function number

0x5F

Header DU1

Slot number (0)

0x00

Header DU2

Index (47)

0x2F

Header DU3

Length

0x0E

Request Header (Byte 1)

Request Reference

0x01

Request Header (Byte 2)

Request ID (0x01: Request)

0x01

Request Header (Byte 3)

Axis

0x01

Request Header (Byte 4)

Number of Parameters

0x01

Parameter Address (Byte 1)

Attribute (0x10: Value)

0x10

Parameter Address (Byte 2)

Number of Elements

0x01

Parameter Address (Byte 3)

Parameter number (PNU), High byte

0x03

Parameter Address (Byte 4)

Parameter number (PNU), Low byte

0xC4

Parameter Address (Byte 5)

Subindex (IND), High byte

0x00

Parameter Address (Byte 6)

Subindex (IND), Low byte

0x04

6.1.2.Read Response data table (positive)

Field

Description

Value

Header DU0

Function number

0x5E

Header DU1

Slot number (0)

0x00

Header DU2

Index (47)

0x2F

Header DU3

Length

0x08

Request Header (Byte 1)

Request Reference (mirrored)

0x01

Request Header (Byte 2)

Response ID *

0x01

Request Header (Byte 3)

Axis (mirrored)

0x01

Request Header (Byte 4)

Number of Parameters

0x01

Parameter Value (Byte 1)

Format *

0x06

Parameter Value (Byte 2)

Number of Values

0x01

Parameter Value (Byte 3)

Values, High byte

0x0A **

Parameter Value (Byte 4)

Values, Low byte

0x90 **

*Refer to Appendix.

**Value 0x0A90 is "2704" in decimal. This means "April 27".

- 31 -

Image 33
Contents Tosvert VF-MB1/S15 Contents Introduction Safety precautions E6581738 E6581738 E6581738 Connection Information Exterior featuresDX Data exchange Green LED Status indicatorVF-MB1/S15 Communication parameters Telegram ProfileSTW Control Word Data PDP003Z supports only speed control mode Bit Value NameBit Valure Name ZSW Status Word Data15s 20s 25s 30s Setpoint Actual valueTmax ZSW BitState Machine Example 1 Hz Forward running and Deceleration stop AK Request from Master to PDP003Z) Access to the Profibus parameterProfibus parameter PNU Value Mode13 9A Example 1. Reading the PNU 922 TelegramAccess to VF-MB1/S15 parameter Response Value 0x03E8 = 1000 10.00Hz Vendor Spec. Profile Profibus Master How to useBit Function Overview of the VF-MB1/S15 parameter2. fa23 Communication command Specified data output ST=ON ST=OFF E6581738 RES RY-RC Diagnostic Master DP-V1 functionProfibs DP-V1 Communication VF-MB1/S15Example1. Read the PROFIdrive parameter 0x02 Example 2. Change the PROFIdrive parameter0x9F 0x820xE8 Example 3. Read the VF-MB1/S15 parameter0xFD 0x31Example 4. Change the VF-MB1/S15 parameter 0x300x07 GSD file Profibus Local/Remote OperationFunction number Appendix