Toshiba VF-MB1/S15 instruction manual Response Value 0x03E8 = 1000 10.00Hz

Page 21

E6581738

3.7.1.3. Example 3. Reading the status monitor parameter (fe02 (The operation frequency))

AK = 6 (Request parameter value (array))

SPM = 0

PNU = 1

IND = 0xFE02(fe02 communication number)

PKE

0

1

1

0

0

0

0

0

 

0

0

0

0

0

0

0

1

 

6

 

 

 

 

 

0

 

 

 

 

0

 

 

 

1

 

Requirement

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKW

 

 

 

 

 

 

 

 

 

 

 

 

PZD

 

 

 

 

PKE

 

 

IND

 

 

PWE

 

 

 

 

 

 

 

 

 

 

60

01

 

FE

02

 

 

00

00

 

00

 

00

・・・

・・・

 

 

 

Response (Value: 0x03E8 (= 1000 -> 10.00Hz))

 

 

 

 

 

 

 

 

40

01

 

FE

02

 

 

00

00

 

03

 

E8

・・・

・・・

 

 

 

*The status monitor parameter can not be changed.

3.7.1.4.Example 4. Changing the basic parameter (acc (acceleration time))

AK = 7 (Change parameter value (array))

SPM = 0

PNU = 1

IND = 0x0009 (acc communication number)

PKE

0

1

1

1

0

0

0

0

0

0

0

0

0

0

0

1

 

 

7

 

 

 

 

0

 

 

 

0

 

 

 

1

 

Requirement (acc = 7.0 sec. -> 70 (= 0x0046) *)

 

 

 

 

 

 

 

PKW

 

 

 

 

 

 

 

 

 

 

 

PZD

 

 

 

 

PKE

 

 

IND

 

 

PWE

 

 

 

 

 

 

 

 

 

70

 

01

00

09

 

 

00

00

00

 

46

・・・

・・・

 

 

 

Response

40

01

00

09

00

00

00

46

・・・ ・・・

*When the “Acceleration time” is set to 7.0 sec., set the following value. (The unit of the “Acceleration time” is according to the parameter f519.)

7.0/0.1 = 70 = 0x0046 (hexadecimal number)

Notes

When the control power is shut off by the instantaneous power failure, communication will be unavailable for a while.

The Life of EEPROM is approximately 100,000 times. Avoid writing a command more than 100,000 times to the same parameter of the drive and the communication board.

- 19 -

Image 21
Contents Tosvert VF-MB1/S15 Contents Introduction Safety precautions E6581738 E6581738 E6581738 Connection Information Exterior featuresDX Data exchange Green LED Status indicatorVF-MB1/S15 Communication parameters Telegram ProfileSTW Control Word Data PDP003Z supports only speed control mode Bit Value NameBit Valure Name ZSW Status Word Data15s 20s 25s 30s Setpoint Actual valueTmax ZSW BitState Machine Example 1 Hz Forward running and Deceleration stop AK Request from Master to PDP003Z) Access to the Profibus parameterProfibus parameter PNU Value Mode13 9A Example 1. Reading the PNU 922 TelegramAccess to VF-MB1/S15 parameter Response Value 0x03E8 = 1000 10.00Hz Vendor Spec. Profile Profibus Master How to useBit Function Overview of the VF-MB1/S15 parameter2. fa23 Communication command Specified data output ST=ON ST=OFF E6581738 RES RY-RC Diagnostic Master DP-V1 functionProfibs DP-V1 Communication VF-MB1/S15Example1. Read the PROFIdrive parameter 0x02 Example 2. Change the PROFIdrive parameter0x9F 0x820xE8 Example 3. Read the VF-MB1/S15 parameter0xFD 0x31Example 4. Change the VF-MB1/S15 parameter 0x300x07 GSD file Profibus Local/Remote OperationFunction number Appendix