E6581738
3.7.1.3. Example 3. Reading the status monitor parameter (fe02 (The operation frequency))
AK = 6 (Request parameter value (array))
SPM = 0
PNU = 1
IND = 0xFE02(fe02 communication number)
PKE
0 | 1 | 1 | 0 | 0 | 0 | 0 | 0 |
| 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | |
| 6 |
|
|
|
|
| 0 |
|
|
|
| 0 |
|
|
| 1 |
|
Requirement |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
PKW |
|
|
|
|
|
|
|
|
|
|
|
| PZD |
|
|
|
|
PKE |
|
| IND |
|
| PWE |
|
|
|
|
|
|
|
|
|
| |
60 | 01 |
| FE | 02 |
|
| 00 | 00 |
| 00 |
| 00 | ・・・ | ・・・ |
|
|
|
Response (Value: 0x03E8 (= 1000 |
|
|
|
|
|
|
|
| |||||||||
40 | 01 |
| FE | 02 |
|
| 00 | 00 |
| 03 |
| E8 | ・・・ | ・・・ |
|
|
|
*The status monitor parameter can not be changed.
3.7.1.4.Example 4. Changing the basic parameter (acc (acceleration time))
AK = 7 (Change parameter value (array))
SPM = 0
PNU = 1
IND = 0x0009 (acc communication number)
PKE
0 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | |
|
| 7 |
|
|
|
| 0 |
|
|
| 0 |
|
|
| 1 |
|
Requirement (acc = 7.0 sec. |
|
|
|
|
|
|
| |||||||||
PKW |
|
|
|
|
|
|
|
|
|
|
| PZD |
|
|
|
|
PKE |
|
| IND |
|
| PWE |
|
|
|
|
|
|
|
|
| |
70 |
| 01 | 00 | 09 |
|
| 00 | 00 | 00 |
| 46 | ・・・ | ・・・ |
|
|
|
Response
40 | 01 | 00 | 09 | 00 | 00 | 00 | 46 |
・・・ ・・・
*When the “Acceleration time” is set to 7.0 sec., set the following value. (The unit of the “Acceleration time” is according to the parameter f519.)
7.0/0.1 = 70 = 0x0046 (hexadecimal number)
Notes
When the control power is shut off by the instantaneous power failure, communication will be unavailable for a while.
The Life of EEPROM is approximately 100,000 times. Avoid writing a command more than 100,000 times to the same parameter of the drive and the communication board.
- 19 -