Toshiba VF-MB1/S15 instruction manual Profibus Local/Remote Operation, GSD file

Page 37

E6581738

7. PROFIBUS Local/Remote Operation

The example below shows how to configure the VF-MB1 for local/remote operation.

<Terminal function>

 

F terminal

RUN command

R terminal

Local (Terminal in this example) / PROFIBUS switching

VIA terminal

Operation frequency command

<Wiring>

 

Variable resistor for adjustment 10k ohm

Operation command

Local/PROFIBUS

Switch

VF-MB1

 

PP

 

VIA

 

CC

 

SW1

F

 

SOURCE

SINK

R

 

P24

 

OUT

 

<Parameter setting>

cmod (command mode selection) = 0 (terminal board) fmod (frequency setting mode selection 1) = 1 (VIA)

f112 (input terminal selection 2 (R)) = 48 (Local/PROFIBUS control)

<Operation>

R-CC terminal open:

VF-MB1 is controlled as slave device of PROFIBUS. R-CC terminal closed:

F-CC terminal short to RUN F-CC terminal open to STOP

Output frequency is set up by the VIA signal input.

8. GSD file

As for acquisition of an GSD file for VF-MB1 and VF-S15, please contact your Toshiba distributor.

- 35 -

Image 37
Contents Tosvert VF-MB1/S15 Contents Introduction Safety precautions E6581738 E6581738 E6581738 Connection Information Exterior featuresDX Data exchange Green LED Status indicatorVF-MB1/S15 Communication parameters Telegram ProfileSTW Control Word Data PDP003Z supports only speed control mode Bit Value NameBit Valure Name ZSW Status Word Data15s 20s 25s 30s Setpoint Actual valueTmax ZSW BitState Machine Example 1 Hz Forward running and Deceleration stop AK Request from Master to PDP003Z) Access to the Profibus parameterProfibus parameter PNU Value Mode13 9A Example 1. Reading the PNU 922 TelegramAccess to VF-MB1/S15 parameter Response Value 0x03E8 = 1000 10.00Hz Vendor Spec. Profile Profibus Master How to useBit Function Overview of the VF-MB1/S15 parameter2. fa23 Communication command Specified data output ST=ON ST=OFF E6581738 RES RY-RC Diagnostic Master DP-V1 functionProfibs DP-V1 Communication VF-MB1/S15Example1. Read the PROFIdrive parameter 0x02 Example 2. Change the PROFIdrive parameter0x9F 0x820xE8 Example 3. Read the VF-MB1/S15 parameter0xFD 0x310x30 Example 4. Change the VF-MB1/S15 parameter0x07 GSD file Profibus Local/Remote OperationFunction number Appendix