Toshiba VF-MB1/S15 instruction manual Appendix, Function number

Page 38

E6581738

9. Appendix

Function number

0x5E: Read Request

0x5F: Write Request

0x5E: Positive response for Read request

0x5F: Positive response for Write request

0xDE: Negative response for Read request

0xDF: Negative response for Write request

Request ID

0x01: Request the value

0x02: Change the value

Response ID

0x01: Positive response for Request the value

0x02: Positive response for Change the value

0x81: Negative response for Request the value

0x82: Negative response for Change the value

Axis

0x00: (Fixed for PDP003Z)

Error number

0x00: Impermissible parameter number

0x01: Impermissible parameter number

0x02: Low or High limit exceeded

0x03: Faulty subindex

0x04: No array

0x05: Incorrect data type

0x06: Setting not permitted (may only be reset)

0x07: Description element cannot be changed

0x09: No description data available

0x0B: No operation priority

0x0F: No text array available

0x11: Request cannot be executed because of operating state

0x14: Value impermissible

0x15: Response too long

0x17: Write Req., Illegal format/format of the parameter data is not supported

0x18: Number of values are not consistent

0x19: Axis/DO non existent

0x20: Parameter text element cannot be changed

Format

0x01: Boolean

0x02: Integer 8

0x03: Integer 16

0x04: Integer 32

0x05: Unsigned 8

0x06: Unsigned 16

0x07: Unsigned 32

0x08: FloatingPoint

0x09: VisibleString

0x10: OctetString

0x12 TimeOfDay (with date indication) 0x13: TimeDifference

0x40: Zero

0x41: Byte

0x42: Word

0x43: Double word

0x44: Error

- 36E - - 36 -

Image 38
Contents Tosvert VF-MB1/S15 Contents Introduction Safety precautions E6581738 E6581738 E6581738 Exterior features Connection InformationStatus indicator DX Data exchange Green LEDVF-MB1/S15 Communication parameters Profile TelegramPDP003Z supports only speed control mode Bit Value Name STW Control Word DataZSW Status Word Data Bit Valure NameTmax Setpoint Actual value15s 20s 25s 30s ZSW BitState Machine Example 1 Hz Forward running and Deceleration stop Access to the Profibus parameter AK Request from Master to PDP003Z)Value Mode Profibus parameter PNUExample 1. Reading the PNU 922 Telegram 13 9AAccess to VF-MB1/S15 parameter Response Value 0x03E8 = 1000 10.00Hz Vendor Spec. Profile How to use Profibus MasterOverview of the VF-MB1/S15 parameter Bit Function2. fa23 Communication command Specified data output ST=ON ST=OFF E6581738 RES RY-RC Diagnostic Profibs DP-V1 Communication DP-V1 functionMaster VF-MB1/S15Example1. Read the PROFIdrive parameter 0x9F Example 2. Change the PROFIdrive parameter0x02 0x820xFD Example 3. Read the VF-MB1/S15 parameter0xE8 0x310x07 Example 4. Change the VF-MB1/S15 parameter0x30 Profibus Local/Remote Operation GSD fileAppendix Function number