Toshiba VF-MB1/S15 instruction manual Profibus parameter PNU, Value Mode

Page 18

E6581738

3.6.PROFIBUS parameter (PNU)

PNU

R/W

data type

 

Note

915

R

Array [6]

PNU 915, IND 0 = the drive parameter c001

 

 

Unsigned16

PNU 915, IND 1 = the drive parameter c002

 

 

 

PNU 915, IND 2 = the drive parameter c003

 

 

 

PNU 915, IND 3 = the drive parameter c004

 

 

 

PNU 915, IND 4 = the drive parameter c005

 

 

 

PNU 915, IND 5 = the drive parameter c006

916

R

Array [6]

PNU 916, IND 0 = the drive parameter c021

 

 

Unsigned16

PNU 916, IND 1 = the drive parameter c022

 

 

 

PNU 916, IND 2 = the drive parameter c023

 

 

 

PNU 916, IND 3 = the drive parameter c024

 

 

 

PNU 916, IND 4 = the drive parameter c025

 

 

 

PNU 916, IND 5 = the drive parameter c026

918

R

Unsigned16

Station address monitor (same as the drive parameter c150).

922

R

Unsigned16

Telegram selection

 

 

 

1, 100, 101, 102

927

R/W

Unsigned16

Operator control rights (parameter identification, PKW).

 

 

 

Value: Mode

 

 

 

0: Parameters cannot be written, only read

 

 

 

 

(927 can be written).

 

 

 

1: Parameters can be written and read (default).

928

R

Unsigned16

Control rights (process data, PZD).

 

 

 

1: PZD part is enabled.

930

R

Unsigned16

Operating mode

 

 

 

1 supports the speed control mode and the speed

 

 

 

setpoint channel comprises RFG functionality.

944

R

Unsigned16

Fault message counter

947

R

Array [1]

Fault number

 

 

Unsigned16

 

 

963

R

Unsigned16

Detected baud rate:

 

 

 

0 =

9.6 kbit/s

 

 

 

1 =

19.2 kbit/s

 

 

 

2 =

93.75 kbit/s

 

 

 

3 =

187.5 kbit/s

 

 

 

4 =

500 kbit/s

 

 

 

6 =

1.5 Mbit/s

 

 

 

7 =

3 Mbit/s

 

 

 

8 =

6 Mbit/s

 

 

 

9 =

12 Mbit/s

964

R

Array [5]

Drive Unit identification

 

 

Unsigned16

IND 0 = PDP003Z ID (0x0C24)

 

 

 

IND 1 = Manufacturer-ID (0x0190)

 

 

 

IND 2 = VF-MB1/S15 CPU1 version

 

 

 

IND 3 = VF-MB1/S15 firmware release year (yyyy)

 

 

 

IND 4 = VF-MB1/S15 firmware release date (ddmm)

965

R

Octet String2

Profile number of the PDP003Z (Profidrive, V4.1)

- 16 -

Image 18
Contents Tosvert VF-MB1/S15 Contents Introduction Safety precautions E6581738 E6581738 E6581738 Exterior features Connection InformationStatus indicator DX Data exchange Green LEDVF-MB1/S15 Communication parameters Profile TelegramPDP003Z supports only speed control mode Bit Value Name STW Control Word DataZSW Status Word Data Bit Valure NameTmax Setpoint Actual value15s 20s 25s 30s ZSW BitState Machine Example 1 Hz Forward running and Deceleration stop Access to the Profibus parameter AK Request from Master to PDP003Z)Value Mode Profibus parameter PNUExample 1. Reading the PNU 922 Telegram 13 9AAccess to VF-MB1/S15 parameter Response Value 0x03E8 = 1000 10.00Hz Vendor Spec. Profile How to use Profibus MasterOverview of the VF-MB1/S15 parameter Bit Function2. fa23 Communication command Specified data output ST=ON ST=OFF E6581738 RES RY-RC Diagnostic Profibs DP-V1 Communication DP-V1 functionMaster VF-MB1/S15Example1. Read the PROFIdrive parameter 0x9F Example 2. Change the PROFIdrive parameter0x02 0x820xFD Example 3. Read the VF-MB1/S15 parameter0xE8 0x31Example 4. Change the VF-MB1/S15 parameter 0x300x07 Profibus Local/Remote Operation GSD fileAppendix Function number