Toshiba instruction manual Overview of the VF-MB1/S15 parameter, Bit Function

Page 24

E6581738

4.2.The overview of the VF-MB1/S15 parameter

Refer to a communication functional description (E6581726/E6581913) for details.

4.2.1.fa06 (Communication command1)

bit

Function

0

 

1

Note

 

Preset speed

 

 

 

 

0

operation frequencies

Preset speed operation is disabled

 

 

1

 

 

Preset speed

or preset speed operation

 

 

1

operation frequencies

frequencies (1-15) are set by

 

 

2

specifying bits for preset speed

 

 

Preset speed

operation frequencies 1-4.

 

 

2

operation frequencies

(0000: Preset speed operation OFF,

 

 

3

001-1111: Setting of preset speed

 

 

Preset speed

operation frequencies (1-15)

 

3operation frequencies 4

 

4

Motor selection (1 or 2)

Motor 1

Motor 2

THR 1: pt = setting value, thr

THR 2: pt = 0, f170,

(THR 2 selection)

(THR 1)

(THR 2)

 

 

f171, f172, f173

 

 

 

 

 

5

PI D control

Normal operation

PI D off

-

 

 

Acceleration/decele-

Acceleration/decel

Acceleration/dec

 

6

ration pattern selection

eration pattern 1

eleration pattern

AD1: acc, dec

 

 

(1 or 2)

(AD1)

2

AD2: f500, f501

 

 

(AD2 selection)

(AD2)

 

 

 

 

 

7

DC braking

OFF

Forced DC

-

braking

 

 

 

 

 

 

8

Jog run

OFF

Jog run

-

9

Forward/reverse run

Forward run

Reverse run

-

selection

 

 

 

 

 

10

Run/stop

Stop

Run

-

11

Coast stop command

Standby

Cost stop

-

 

12

Emergency stop

OFF

Emergency stop

Always enable, "E" trip

13

Fault reset

OFF

Reset

No data is returned from the drive

14

Frequency priority

OFF

Enabled

Enabled regardless of the setting

selection

of fmod

 

 

 

 

15

Command priority

OFF

Enabled

Enabled regardless of the setting

selection

of cmod

 

 

 

 

* VF-S15:When 14(sr0) is set to fmod, preset speed operation frequency 0 is selected.

- 22 -

Image 24
Contents Tosvert VF-MB1/S15 Contents Introduction Safety precautions E6581738 E6581738 E6581738 Exterior features Connection InformationStatus indicator DX Data exchange Green LEDVF-MB1/S15 Communication parameters Profile TelegramPDP003Z supports only speed control mode Bit Value Name STW Control Word DataZSW Status Word Data Bit Valure NameSetpoint Actual value 15s 20s 25s 30sTmax ZSW BitState Machine Example 1 Hz Forward running and Deceleration stop Access to the Profibus parameter AK Request from Master to PDP003Z)Value Mode Profibus parameter PNUExample 1. Reading the PNU 922 Telegram 13 9AAccess to VF-MB1/S15 parameter Response Value 0x03E8 = 1000 10.00Hz Vendor Spec. Profile How to use Profibus MasterOverview of the VF-MB1/S15 parameter Bit Function2. fa23 Communication command Specified data output ST=ON ST=OFF E6581738 RES RY-RC Diagnostic DP-V1 function MasterProfibs DP-V1 Communication VF-MB1/S15Example1. Read the PROFIdrive parameter Example 2. Change the PROFIdrive parameter 0x020x9F 0x82Example 3. Read the VF-MB1/S15 parameter 0xE80xFD 0x31Example 4. Change the VF-MB1/S15 parameter 0x300x07 Profibus Local/Remote Operation GSD fileAppendix Function number