4.1.How to use

The purposes are adjustment by real time command transmission, and the monitor of an operation state by using cyclic communication of PROFIBUS.

Example 1: Command transmitting

When you want to set "0xC400" to parameter fa06, set “1 (fa06)” to parameter c001.

And Since 0 and 1 byte of the PZD1 supports the parameter c001, if "0xC400" is set up here, "0xC400" will be set as fa06.

VF-MB1

PDP003Z

 

Parameter

Value

c001

1 (FA06)

c002

...

c003

...

...

...

"0xC400" is set as parameter fa06

PROFIBUS Master

PZD1

PZD2

PZD3

C4

00

...

...

...

...

 

Example 2: State monitoring

 

 

 

 

 

When you want to monitor the output current, set “3 (FD03)” to parameter c021.

 

 

The value of the parameter fd03 specified as 0 and1 byte of the PZD1 with the

 

 

parameter c021 is inputted.

 

 

 

 

VF-MB1

PDP003Z

 

 

PROFIBUS Master

 

 

 

 

 

Parameter

Value

 

 

 

 

c021

3 (FD03)

 

 

 

 

c022

...

 

 

 

 

c023

...

PZD1

PZD2

PZD3

...

...

xx

xx

 

 

The value of a parameter fd03 is outputted.

 

 

 

 

- 21 -

Image 23
Contents Tosvert VF-MB1/S15 Contents Introduction Safety precautions E6581738 E6581738 E6581738 Connection Information Exterior featuresDX Data exchange Green LED Status indicatorVF-MB1/S15 Communication parameters Telegram ProfileSTW Control Word Data PDP003Z supports only speed control mode Bit Value NameBit Valure Name ZSW Status Word DataZSW Bit Setpoint Actual value15s 20s 25s 30s TmaxState Machine Example 1 Hz Forward running and Deceleration stop AK Request from Master to PDP003Z) Access to the Profibus parameterProfibus parameter PNU Value Mode13 9A Example 1. Reading the PNU 922 TelegramAccess to VF-MB1/S15 parameter Response Value 0x03E8 = 1000 10.00Hz Vendor Spec. Profile Profibus Master How to useBit Function Overview of the VF-MB1/S15 parameter2. fa23 Communication command Specified data output ST=ON ST=OFF E6581738 RES RY-RC Diagnostic VF-MB1/S15 DP-V1 functionMaster Profibs DP-V1 CommunicationExample1. Read the PROFIdrive parameter 0x82 Example 2. Change the PROFIdrive parameter0x02 0x9F0x31 Example 3. Read the VF-MB1/S15 parameter0xE8 0xFD0x07 Example 4. Change the VF-MB1/S15 parameter0x30 GSD file Profibus Local/Remote OperationFunction number Appendix