E6581738
4.1.How to use
The purposes are adjustment by real time command transmission, and the monitor of an operation state by using cyclic communication of PROFIBUS.
Example 1: Command transmitting
When you want to set "0xC400" to parameter fa06, set “1 (fa06)” to parameter c001.
And Since 0 and 1 byte of the PZD1 supports the parameter c001, if "0xC400" is set up here, "0xC400" will be set as fa06.
| PDP003Z |
| |
Parameter | Value |
c001 | 1 (FA06) |
c002 | ... |
c003 | ... |
... | ... |
"0xC400" is set as parameter fa06 |
PROFIBUS Master
PZD1 | PZD2 | PZD3 | |||
C4 | 00 | ... | ... | ... | ... |
| Example 2: State monitoring |
|
|
|
|
| When you want to monitor the output current, set “3 (FD03)” to parameter c021. |
| |||
| The value of the parameter fd03 specified as 0 and1 byte of the PZD1 with the |
| |||
| parameter c021 is inputted. |
|
|
|
|
PDP003Z |
|
| PROFIBUS Master | ||
|
|
|
|
| |
Parameter | Value |
|
|
|
|
c021 | 3 (FD03) |
|
|
|
|
c022 | ... |
|
|
|
|
c023 | ... | PZD1 | PZD2 | PZD3 | |
... | ... | xx | xx | ||
|
| ||||
The value of a parameter fd03 is outputted. |
|
|
|
|
- 21 -