Toshiba VF-MB1/S15 instruction manual E6581738

Page 28

E6581738

4.2.8.fd03 (Output current (real time))

The output current is read into 0.01% of units and by the hexadecimal number.

For example, when the output current of the rated current 4.8A drive is 50% (2.4A), 0x1388 (hexadecimal number) is read out.

Since the minimum unit is 0.01%,

 

 

0x1388 (Hex.) = 5000 (Dec.) * 0.01 = 50 (%)

 

 

Also about the following parameters, these are the same as this.

 

 

- fd05 (Output voltage (real time))

Unit: 0.01%

(V)

- fd04 (Voltage at DC bus (real time))

Unit: 0.01%

(V)

- fd18 (Torque)

Unit: 0.01%

(Nm)*

*When the motor information connected to the drive set to the parameter (f405 - f415), torque monitor value "100%" is same as the rated torque of a motor in general.

4.2.9.fe35, fe36, fe37 (Monitoring of the analog input VIA, VIB, VIC)

VIA terminal board monitor: "Communication Number fe35"

VIB terminal board monitor: "Communication Number fe36"

VIC terminal board monitor: "Communication Number fe37"

These monitors can also be used as A/D converters irrespective of the drive's control.

VIA / VIC terminal board monitor is capable of reading the data from external devices in a range of 0.01 to 100.00% (unsigned data: 0x0000 to 0x2710).

VIB terminal board monitor is capable of reading the data from external devices in a range of -100.00 to 100.00% (signed data: 0xD8F0 to 0x2710).

If analog input mode is selected with the frequency setting mode selection parameter, however, keep in mid that any data entered via an analog terminal is regarded as a frequency command.

4.2.10.fe14 (Cumulative run time)

The operated cumulative time is read by the hexadecimal number.

For example, when cumulative operation time is 18 hours, 0x12 (18 hours) is read. 0x12 (Hex.) = 18 (Dec., hour)

4.2.11.fe40 (Analog output (FM))

The output value of FM terminal is read.

The value range is set to 0 to 10000 (0x2710).

- 26 -

Image 28
Contents Tosvert VF-MB1/S15 Contents Introduction Safety precautions E6581738 E6581738 E6581738 Exterior features Connection InformationStatus indicator DX Data exchange Green LEDVF-MB1/S15 Communication parameters Profile TelegramPDP003Z supports only speed control mode Bit Value Name STW Control Word DataZSW Status Word Data Bit Valure NameSetpoint Actual value 15s 20s 25s 30sTmax ZSW BitState Machine Example 1 Hz Forward running and Deceleration stop Access to the Profibus parameter AK Request from Master to PDP003Z)Value Mode Profibus parameter PNUExample 1. Reading the PNU 922 Telegram 13 9AAccess to VF-MB1/S15 parameter Response Value 0x03E8 = 1000 10.00Hz Vendor Spec. Profile How to use Profibus MasterOverview of the VF-MB1/S15 parameter Bit Function2. fa23 Communication command Specified data output ST=ON ST=OFF E6581738 RES RY-RC Diagnostic DP-V1 function MasterProfibs DP-V1 Communication VF-MB1/S15Example1. Read the PROFIdrive parameter Example 2. Change the PROFIdrive parameter 0x020x9F 0x82Example 3. Read the VF-MB1/S15 parameter 0xE80xFD 0x310x30 Example 4. Change the VF-MB1/S15 parameter0x07 Profibus Local/Remote Operation GSD fileAppendix Function number