Toshiba VF-MB1/S15 Access to the Profibus parameter, AK Request from Master to PDP003Z)

Page 17

E6581738

3.5.Access to the PROFIBUS parameter

In the cyclic PROFIBUS-DP communication, the parameter data is transferred via Telegram 100, 101. If the requirement is not executed, the cause is distinguished by octet 7 and 8.

 

PKW

 

 

 

 

PZD

 

(Parameter ID/value)

 

Process data (cyclically)

 

 

 

 

 

PZD1

 

PZD2

PKE

IND

 

PWE

 

STW

 

HSW

 

 

 

 

 

ZSW

 

HIW

Octet 1 Octet 2

Octet 3 Octet 4 Octet 5

Octet 6 Octet 7

Octet 8

 

 

 

PKE (Parameter ID)

15 14 13 12

11

10

9

8

7

6

5

4

3

2

1

0

AK

SPM

PNU

(Task ID/Response ID)

 

(Parameter number)

AK (Request from Master to PDP003Z

Request ID

Function

Note

0

No task

 

1

Request parameter value

for PNU access

2

Change parameter value (word)

for PNU access

6

Request parameter value (array)

for PNU access, VF-MB1/S15 parameter

 

 

access

7

Change parameter value (array)

for PNU access, VF-MB1/S15 parameter

 

 

access

AK (Response from PDP003Z to Master)

Response ID

Function

0No response

1Transfer parameter value (word)

4

Transfer parameter value (array)

7Task can not be executed, followed by error number 0 = Illegal parameter number

1 = Parameter value cannot be changed

2 = Lower or upper limit violated

3 = Erroneous sub index

11 = No parameter change rights

17 = Task cannot be executed due to operating status (e.g. parameter is currently read-only)

18 = Other error

102 = Request not supported

SPM: always 0.

- 15 -

Image 17
Contents Tosvert VF-MB1/S15 Contents Introduction Safety precautions E6581738 E6581738 E6581738 Connection Information Exterior featuresDX Data exchange Green LED Status indicatorVF-MB1/S15 Communication parameters Telegram ProfileSTW Control Word Data PDP003Z supports only speed control mode Bit Value NameBit Valure Name ZSW Status Word Data15s 20s 25s 30s Setpoint Actual valueTmax ZSW BitState Machine Example 1 Hz Forward running and Deceleration stop AK Request from Master to PDP003Z) Access to the Profibus parameterProfibus parameter PNU Value Mode13 9A Example 1. Reading the PNU 922 TelegramAccess to VF-MB1/S15 parameter Response Value 0x03E8 = 1000 10.00Hz Vendor Spec. Profile Profibus Master How to useBit Function Overview of the VF-MB1/S15 parameter2. fa23 Communication command Specified data output ST=ON ST=OFF E6581738 RES RY-RC Diagnostic Master DP-V1 functionProfibs DP-V1 Communication VF-MB1/S15Example1. Read the PROFIdrive parameter 0x02 Example 2. Change the PROFIdrive parameter0x9F 0x820xE8 Example 3. Read the VF-MB1/S15 parameter0xFD 0x310x07 Example 4. Change the VF-MB1/S15 parameter0x30 GSD file Profibus Local/Remote OperationFunction number Appendix