Toshiba VF-MB1/S15 Example 2. Change the PROFIdrive parameter, 0x02, 0x9F, 0x82, 0x44

Page 34

E6581738

6.2.Example 2. Change the PROFIdrive parameter

6.2.1.Write Request data table (Change, set 0 to PNU 927 (0x039F))

Field

Description

Value

Header (DU0)

Function number

0x5F

Header (DU1)

Slot number (0)

0x00

Header (DU2)

Index (47)

0x2F

Header (DU3)

Length

0x0E

Request Header (Byte 1)

Request Reference

0x01

Request Header (Byte 2)

Request ID (0x02: Change) *

0x02

Request Header (Byte 3)

Axis

0x01

Request Header (Byte 4)

Number of Parameters

0x01

Parameter Address (Byte 1)

Attribute

0x10

Parameter Address (Byte 2)

Number of Elements

0x01

Parameter Address (Byte 3)

Parameter number (PNU), High byte

0x03

Parameter Address (Byte 4)

Parameter number (PNU), Low byte

0x9F

Parameter Address (Byte 5)

Subindex (IND), High byte

0x00

Parameter Address (Byte 6)

Subindex (IND), Low byte

0x00

Parameter Value (Byte 1)

Format *

0x06

Parameter Value (Byte 2)

Number of Value

0x01

Parameter Value (Byte 3)

Values, High byte

0x00

Parameter Value (Byte 4)

Values, Low byte

0x00

* Refer to Appendix.

 

 

Read Response data table (positive)

 

 

 

 

Field

Description

Value

Header DU0

Function number

0x5E

Header DU1

Slot number (0)

0x00

Header DU2

Index (47)

0x2F

Header DU3

Length

0x04

Request Header (Byte 1)

Request Reference (mirrored)

0x01

Request Header (Byte 2)

Response ID (0x02: Positive)

0x02

Request Header (Byte 3)

Axis (mirrored)

0x01

Request Header (Byte 4)

Number of Parameters

0x01

6.2.2.Read Response data table (negative, set 2 to PNU 927)

Field

Description

Value

Header DU0

Function number

0x5E

Header DU1

Slot number (0)

0x00

Header DU2

Index (47)

0x2F

Header DU3

Length

0x08

Request Header (Byte 1)

Request Reference (mirrored)

0x01

Request Header (Byte 2)

Response ID (0x82: Negative) *

0x82

Request Header (Byte 3)

Axis (mirrored)

0x01

Request Header (Byte 4)

Number of Parameters

0x01

Parameter Value (Byte 1)

Format (0x44: Error) *

0x44

Parameter Value (Byte 2)

Numner of Vlaues

0x01

Parameter Value (Byte 3)

Error number, High byte

0x00

Parameter Value (Byte 4)

Error number, Low byte

0x01

* Refer to Appendix.

- 32 -

Image 34
Contents Tosvert VF-MB1/S15 Contents Introduction Safety precautions E6581738 E6581738 E6581738 Exterior features Connection InformationStatus indicator DX Data exchange Green LEDVF-MB1/S15 Communication parameters Profile TelegramPDP003Z supports only speed control mode Bit Value Name STW Control Word DataZSW Status Word Data Bit Valure NameTmax Setpoint Actual value15s 20s 25s 30s ZSW BitState Machine Example 1 Hz Forward running and Deceleration stop Access to the Profibus parameter AK Request from Master to PDP003Z)Value Mode Profibus parameter PNUExample 1. Reading the PNU 922 Telegram 13 9AAccess to VF-MB1/S15 parameter Response Value 0x03E8 = 1000 10.00Hz Vendor Spec. Profile How to use Profibus MasterOverview of the VF-MB1/S15 parameter Bit Function2. fa23 Communication command Specified data output ST=ON ST=OFF E6581738 RES RY-RC Diagnostic Profibs DP-V1 Communication DP-V1 functionMaster VF-MB1/S15Example1. Read the PROFIdrive parameter 0x9F Example 2. Change the PROFIdrive parameter0x02 0x820xFD Example 3. Read the VF-MB1/S15 parameter0xE8 0x310x30 Example 4. Change the VF-MB1/S15 parameter0x07 Profibus Local/Remote Operation GSD fileAppendix Function number