Controller Recovery using Flash Memory Technology

It is possible for a write error to occur while information is being saved in the controller’s memory. If this occurs, the system always saves a backup of the data.

To recover from a write failure:

Shut off the controller, wait 15 seconds, then restart the controller.

The boot sequence detects the write error and attempts to restore the backup file.

It is also possible, although rare, that the backup and original file could both become corrupt. If this occurs, then reset the controller to factory default parameters before proceeding. However, all parameters you’ve previously stored are lost and you’ll need to set up the controller from the beginning. You should record what settings you use in the controller

system if this occurs.

The following screens display while the controller writes to flash memory. Again, do not cycle power while these two screens display.

WRITING PARAMETERS

TO FLASH-PLEASE WAIT

SAVING BACKUP

TO FLASH-PLEASE WAIT

Note: The controller needs about 30 seconds for saving to flash memory. If the controller doesn’t clear this display within 60 seconds, you may need to cycle power. This rare type of problem is caused by a write failure not detected by the controller. This rare condition usually requires a complete factory default reset for full recovery.

2–Pump 12-Station Controllers

Chapter 6: Troubleshooting

48

Image 49
Contents Write Down Your Serial Numbers Here For Future Reference SCC 2-Pump 12-Station ControllersParts and Service Department Unpacking and Inspection Shipping InformationEvent of Shipping Damage If the Shipment is Not CompleteReturns Warranty ReturnsCredit Returns Table of Contents Maintenance How to Use This Manual SafetySafety Symbols Used in this Manual Wear Safety Glasses and Work Gloves Controller Safety TagsGeneral Responsibility ResponsibilityReporting a Safety Defect Maintenance ResponsibilityOperator Responsibility Models Covered in This Manual Functional DescriptionGeneral Description Optional Features Standard FeaturesMechanical Features Electrical FeaturesSafety Circuit Standards Safety Devices and InterlocksSafety Device Lock-Outs Fail Safe OperationPump 12-Station Controllers Functional Description Making Control Panel Power Drop Wiring Connections InstallationUncrating Mounting the Control PanelConnecting the Control Panel to the Pump Package Connecting the Control Panel to Vacuum HoppersTypical 24-Volt Junction Box Wiring Diagram Main Power SetupDC Controller Power Sources InputsMenu Tree Structure Gaining Access to the Menu SystemStation Settings Menu Station SETTINGS? NO/YESOperation Mode, Station Settings Menu Operation MODE? NO/YESALL Sightglass MODE? NO/YES ALL Normal MODE? NO/YESStation 1 Normal =NORMAL N=SIGHTGLS Dump Delay 11 15.0s SET Dump DELAY? NO/YESSet Dump Delay, Station Settings Menu To Select a Station Press StationSet Input Delay, Station Settings Menu SET Input DELAY? NO/YESSet Station Alarms, Station Settings Menu SET Station ALARMS? NO/YESInput DLY 11 0.250s Alarm 11 Enabled =ENABLE N=DISABLE Assign PUMPSTATION? NO/YES Alarm After 3 Loads Press Enter to SaveTo Select a Station Press Hopper Assigning a Pump to a StationStation 10 Pump Select Pump 1 or Pump Settings Menu Pump SETTINGS? NO/YESSetting the Pump Mode Pump MODE? NO/YESSET Active Pump Select Pump 1 or Enable BLOWBACK? NO/YES Blowback SETTINGS? NO/YESChanging Blowback Settings, Pump Settings Menu Select Pump 1 or USE Keypad to EnterOn Time 0.500 s Blowback Pulses Setting for PumpOFF Time 0.500 s Idle Delay TIME? NO/YES Blbk After 12 Loads Setting for PumpIdle Delay Time Settings, Pump Settings Menu Idle Time 10.000 s System Settings MenuSaving Controller Settings to Flash Memory Service Settings MenuLoad Time 10 63sec OperationController Description and Operation SectionText Area Dual Pump Mode Pump Modes Single Pump ModeSTATION-- Offline Time --- Logo P1S----- Offline P2S----- OfflineStation Icon Segments Label Description Station IconsStatus Indicator Icons Label Description Status IndicatorsKey Descriptions Controller KeypadLabel Description Operation States OperationRuns but no station loads Shut-Down Updating Bios Software MaintenanceBios Connection, Electrical Diagram Drawing A0560970LEGEND General Troubleshooting TroubleshootingSee -5 on Page 75 for Controller Recovery using Flash Memory Technology Writing Parameters To FLASH-PLEASE Wait Saving BackupWarranty Specifications WarrantyWarranty Restrictions AppendixCustomer Responsibilities Warranty LiabilitiesPump 12 station Controller Control Panel Drawings and DiagramsPlaces A0560974 Power cord A0560954 Spare Parts ListENCL, CARLON, Mount FLNG, MNK10L A0560974 RECT, BRIDGE, 25 AMPS, GBPC2510 Technical Assistance Contact Information Controller Identification Serial Number TagRamp UP DLY 1.500s Setting for Pump n Service Only InformationService Settings Menu Setting the Ramp Up TimeSetting the Ramp Down Time Ramp DN DLY 8.000s Setting for Pump nSET Ramp Down TIME? NO/YES Setting the Pump Stage Time Stage Delay 3.000sSET Pump Stage TIME? NO/YES Blink Delay .500s SET LCD Blink DELAY? NO/YESSetting the LCD Blink Delay Hivac Delay 3.000s Setting for Pump n HI VAC Sensor DELAY? NO/YESSetting the Hi Vacuum Sensor Delay HV Vent DLY 10.000s Setting for Pump n HI VAC Vent DELAY? NO/YESSetting the Hi Vacuum Vent Delay HI VAC Load COUNT? NO/YES Setting the Hi Vacuum Load CountHV Load CNT Input MONITOR? NO/YES Using the Installation Aids MenusBNK0 BNK1 Input Monitor ScreenAutomatic or MANUAL? =AUTO Y=MANUAL Output CONTROL? NO/YESOutput Control Menu OUTBNK0 OUTBNK1 OEM SETTINGS? NO/YES OEM Menu Access Is NOW AvailableUsing the OEM Service Menu Other Controller Restricted AreasPWL11111 PWL22222 PWL33333 PWL44444 Recovering PasswordsROM Checksum Restoring the Controller to Factory DefaultsPress YES to Resume Verifying Software Checksums