Sterling 882.00249.00 manual ALL Normal MODE? NO/YES, ALL Sightglass MODE? NO/YES

Page 21

To set all the stations to Normal mode and return to the Station Settings menu:

Press the YES key at the following screen prompt.

ALL NORMAL MODE?

NO/YES

This function lets you use the fast setup feature of the controller. Normal mode is the factory default, so if no sight glass loaders are on your system, you won’t need to alter this setting.

Pressing the NO key moves to the All Sight Glass Mode screen. Again, this function lets you quickly change all stations to Sight Glass mode if all stations have sight glass loaders.

ALL SIGHTGLASS MODE?

NO/YES

To move on to the individual settings screen:

Press the NO key.

The following screen displays.

STATION: 1 NORMAL

Y=NORMAL N=SIGHTGLS

Starting with Hopper 1, the controller now lets you individually set the operation mode of each station.

1.Press the YES key to set the station to Normal mode.

2.Press the NO key to set the station to the Sight Glass mode.

3.Press the SET key to save the new setting into controller memory and increment to the next station in sequence.

4.Press the CLEAR key to exit to the Station Settings menu.

2–Pump 12-Station Controllers

Chapter 3: Installation

20

Image 21
Contents Write Down Your Serial Numbers Here For Future Reference SCC 2-Pump 12-Station ControllersParts and Service Department Unpacking and Inspection Shipping InformationEvent of Shipping Damage If the Shipment is Not CompleteWarranty Returns ReturnsCredit Returns Table of Contents Maintenance Safety How to Use This ManualSafety Symbols Used in this Manual Wear Safety Glasses and Work Gloves Controller Safety TagsGeneral Responsibility ResponsibilityMaintenance Responsibility Reporting a Safety DefectOperator Responsibility Functional Description Models Covered in This ManualGeneral Description Optional Features Standard FeaturesMechanical Features Electrical FeaturesSafety Circuit Standards Safety Devices and InterlocksSafety Device Lock-Outs Fail Safe OperationPump 12-Station Controllers Functional Description Making Control Panel Power Drop Wiring Connections InstallationUncrating Mounting the Control PanelConnecting the Control Panel to the Pump Package Connecting the Control Panel to Vacuum HoppersTypical 24-Volt Junction Box Wiring Diagram Main Power Setup DC Controller Power Sources InputsMenu Tree Structure Gaining Access to the Menu SystemStation Settings Menu Station SETTINGS? NO/YESOperation Mode, Station Settings Menu Operation MODE? NO/YESALL Normal MODE? NO/YES ALL Sightglass MODE? NO/YESStation 1 Normal =NORMAL N=SIGHTGLS Dump Delay 11 15.0s SET Dump DELAY? NO/YESSet Dump Delay, Station Settings Menu To Select a Station Press StationSet Input Delay, Station Settings Menu SET Input DELAY? NO/YESSET Station ALARMS? NO/YES Set Station Alarms, Station Settings MenuInput DLY 11 0.250s Alarm 11 Enabled =ENABLE N=DISABLE Assign PUMPSTATION? NO/YES Alarm After 3 Loads Press Enter to SaveTo Select a Station Press Hopper Assigning a Pump to a StationStation 10 Pump Select Pump 1 or Pump Settings Menu Pump SETTINGS? NO/YESSetting the Pump Mode Pump MODE? NO/YESSET Active Pump Select Pump 1 or Enable BLOWBACK? NO/YES Blowback SETTINGS? NO/YESChanging Blowback Settings, Pump Settings Menu Select Pump 1 or USE Keypad to EnterBlowback Pulses Setting for Pump On Time 0.500 sOFF Time 0.500 s Blbk After 12 Loads Setting for Pump Idle Delay TIME? NO/YESIdle Delay Time Settings, Pump Settings Menu Idle Time 10.000 s System Settings MenuSaving Controller Settings to Flash Memory Service Settings MenuLoad Time 10 63sec OperationSection Controller Description and OperationText Area Dual Pump Mode Pump Modes Single Pump ModeSTATION-- Offline Time --- Logo P1S----- Offline P2S----- OfflineStation Icon Segments Label Description Station IconsStatus Indicator Icons Label Description Status IndicatorsController Keypad Key DescriptionsLabel Description Operation States OperationRuns but no station loads Shut-Down Updating Bios Software MaintenanceBios Connection, Electrical Diagram Drawing A0560970LEGEND General Troubleshooting TroubleshootingSee -5 on Page 75 for Controller Recovery using Flash Memory Technology Writing Parameters To FLASH-PLEASE Wait Saving BackupWarranty Specifications WarrantyWarranty Restrictions AppendixCustomer Responsibilities Warranty LiabilitiesPump 12 station Controller Control Panel Drawings and DiagramsPlaces A0560974 Power cord A0560954 Spare Parts ListENCL, CARLON, Mount FLNG, MNK10L A0560974 RECT, BRIDGE, 25 AMPS, GBPC2510 Technical Assistance Contact Information Controller Identification Serial Number TagRamp UP DLY 1.500s Setting for Pump n Service Only InformationService Settings Menu Setting the Ramp Up TimeRamp DN DLY 8.000s Setting for Pump n Setting the Ramp Down TimeSET Ramp Down TIME? NO/YES Stage Delay 3.000s Setting the Pump Stage TimeSET Pump Stage TIME? NO/YES SET LCD Blink DELAY? NO/YES Blink Delay .500sSetting the LCD Blink Delay HI VAC Sensor DELAY? NO/YES Hivac Delay 3.000s Setting for Pump nSetting the Hi Vacuum Sensor Delay HI VAC Vent DELAY? NO/YES HV Vent DLY 10.000s Setting for Pump nSetting the Hi Vacuum Vent Delay Setting the Hi Vacuum Load Count HI VAC Load COUNT? NO/YESHV Load CNT Input MONITOR? NO/YES Using the Installation Aids MenusBNK0 BNK1 Input Monitor ScreenOutput CONTROL? NO/YES Automatic or MANUAL? =AUTO Y=MANUALOutput Control Menu OUTBNK0 OUTBNK1 OEM SETTINGS? NO/YES OEM Menu Access Is NOW AvailableUsing the OEM Service Menu Other Controller Restricted AreasPWL11111 PWL22222 PWL33333 PWL44444 Recovering PasswordsROM Checksum Restoring the Controller to Factory DefaultsPress YES to Resume Verifying Software Checksums