Page 70

Restoring the Controller to Factory Defaults

Although rare, you may experience a condition when you need to perform a total reset of the controller. To do so, perform the following procedure.

Note: All parameters you set are lost when doing this procedure, including passwords and OEM Service settings.

Follow these steps to restore the controller to factory defaults.

1.Remove power from the controller.

2.Press and hold the CLEAR key.

3.Re-apply power while holding down the CLEAR key.

During initialization, the screen displays a message indicating that factory default settings are set.

Verifying Software Checksums

Follow these steps to verify software checksum values.

1.Remove power from the controller.

2.Press and hold the SET key.

3.Re-apply power while holding down the SET key.

During initialization, the screen displays a message while the controller calculates the software check sum. This number is in hexadecimal format (Base 16) and displays in numbers and letters.

Example: 0x1FC9 is a valid checksum format.

ROM CHECKSUM: 0x0000

PRESS YES TO RESUME

2–Pump 12-Station Controllers

Chapter 8: Service Only Information

69

Image 70
Contents SCC 2-Pump 12-Station Controllers Write Down Your Serial Numbers Here For Future ReferenceParts and Service Department Event of Shipping Damage Shipping InformationUnpacking and Inspection If the Shipment is Not CompleteReturns Warranty ReturnsCredit Returns Table of Contents Maintenance How to Use This Manual SafetySafety Symbols Used in this Manual Controller Safety Tags Wear Safety Glasses and Work GlovesResponsibility General ResponsibilityReporting a Safety Defect Maintenance ResponsibilityOperator Responsibility Models Covered in This Manual Functional DescriptionGeneral Description Mechanical Features Standard FeaturesOptional Features Electrical FeaturesSafety Device Lock-Outs Safety Devices and InterlocksSafety Circuit Standards Fail Safe OperationPump 12-Station Controllers Functional Description Uncrating InstallationMaking Control Panel Power Drop Wiring Connections Mounting the Control PanelConnecting the Control Panel to Vacuum Hoppers Connecting the Control Panel to the Pump PackageTypical 24-Volt Junction Box Wiring Diagram DC Controller Power Sources SetupMain Power InputsGaining Access to the Menu System Menu Tree StructureOperation Mode, Station Settings Menu Station SETTINGS? NO/YESStation Settings Menu Operation MODE? NO/YESALL Sightglass MODE? NO/YES ALL Normal MODE? NO/YESStation 1 Normal =NORMAL N=SIGHTGLS Set Dump Delay, Station Settings Menu SET Dump DELAY? NO/YESDump Delay 11 15.0s To Select a Station Press StationSET Input DELAY? NO/YES Set Input Delay, Station Settings MenuSet Station Alarms, Station Settings Menu SET Station ALARMS? NO/YESInput DLY 11 0.250s Alarm 11 Enabled =ENABLE N=DISABLE To Select a Station Press Hopper Alarm After 3 Loads Press Enter to SaveAssign PUMPSTATION? NO/YES Assigning a Pump to a StationStation 10 Pump Select Pump 1 or Setting the Pump Mode Pump SETTINGS? NO/YESPump Settings Menu Pump MODE? NO/YESSET Active Pump Select Pump 1 or Changing Blowback Settings, Pump Settings Menu Blowback SETTINGS? NO/YESEnable BLOWBACK? NO/YES Select Pump 1 or USE Keypad to EnterOn Time 0.500 s Blowback Pulses Setting for PumpOFF Time 0.500 s Idle Delay TIME? NO/YES Blbk After 12 Loads Setting for PumpIdle Delay Time Settings, Pump Settings Menu System Settings Menu Idle Time 10.000 sService Settings Menu Saving Controller Settings to Flash MemoryOperation Load Time 10 63secController Description and Operation SectionText Area STATION-- Offline Time --- Logo Pump Modes Single Pump ModeDual Pump Mode P1S----- Offline P2S----- OfflineStation Icons Station Icon Segments Label DescriptionStatus Indicators Status Indicator Icons Label DescriptionKey Descriptions Controller KeypadLabel Description Operation Operation StatesRuns but no station loads Shut-Down Maintenance Updating Bios SoftwareBios Connection, Electrical Diagram Drawing A0560970LEGEND Troubleshooting General TroubleshootingSee -5 on Page 75 for Writing Parameters To FLASH-PLEASE Wait Saving Backup Controller Recovery using Flash Memory TechnologyWarranty Restrictions WarrantyWarranty Specifications AppendixWarranty Liabilities Customer ResponsibilitiesDrawings and Diagrams Pump 12 station Controller Control PanelSpare Parts List Places A0560974 Power cord A0560954ENCL, CARLON, Mount FLNG, MNK10L A0560974 RECT, BRIDGE, 25 AMPS, GBPC2510 Controller Identification Serial Number Tag Technical Assistance Contact InformationService Settings Menu Service Only InformationRamp UP DLY 1.500s Setting for Pump n Setting the Ramp Up TimeSetting the Ramp Down Time Ramp DN DLY 8.000s Setting for Pump nSET Ramp Down TIME? NO/YES Setting the Pump Stage Time Stage Delay 3.000sSET Pump Stage TIME? NO/YES Blink Delay .500s SET LCD Blink DELAY? NO/YESSetting the LCD Blink Delay Hivac Delay 3.000s Setting for Pump n HI VAC Sensor DELAY? NO/YESSetting the Hi Vacuum Sensor Delay HV Vent DLY 10.000s Setting for Pump n HI VAC Vent DELAY? NO/YESSetting the Hi Vacuum Vent Delay HI VAC Load COUNT? NO/YES Setting the Hi Vacuum Load CountHV Load CNT BNK0 BNK1 Using the Installation Aids MenusInput MONITOR? NO/YES Input Monitor ScreenAutomatic or MANUAL? =AUTO Y=MANUAL Output CONTROL? NO/YESOutput Control Menu OUTBNK0 OUTBNK1 Using the OEM Service Menu OEM Menu Access Is NOW AvailableOEM SETTINGS? NO/YES Other Controller Restricted AreasRecovering Passwords PWL11111 PWL22222 PWL33333 PWL44444Press YES to Resume Restoring the Controller to Factory DefaultsROM Checksum Verifying Software Checksums