Sterling 882.00249.00 manual General Troubleshooting

Page 47

Chapter 6: Troubleshooting

6-1

General Troubleshooting

 

Problem

 

Possible cause

Solution

 

 

The controller panel is not

Plug in the controller panel.

 

 

plugged in.

 

 

 

 

 

The external disconnect

Close the switch (on).

The controller panel doesn’t light

(recommended) in the dedicated

up at all.

 

circuit is open (off).

 

 

 

Fuse/circuit breaker in the power

Replace/reset.

 

 

drop is blown/tripped.

 

 

 

 

 

Broken controller power switch.

Replace.

 

 

 

Reset the overload and check

 

 

The motor overload has tripped.

the motor for the proper amp

A pump package doesn’t run,

 

draw on tag.

even though it is on line and its

Main fuse in power drop or

 

indicator is lit.

 

optional fused disconnect has

Replace the fuse.

 

 

blown.

 

 

 

Motor contact is faulty.

Repair or replace as required.

 

 

The bin below it is full if its

Normal operation. When the

 

 

level drops, material conveys to

 

 

amber indicator light is off.

 

 

the hopper.

 

 

 

 

 

The hopper is off line.

Using the controller, place the

 

 

hopper on line.

A vacuum hopper is being

 

The convey time for the hopper

Using the controller, enter a

bypassed in the loading cycle.

is set to zero.

reasonable convey time.

 

 

The field-installed station bypass

Normal operation. Set the switch

 

 

switch is simulating a Bin Full

so the hopper is back in the

 

 

condition.

loading sequence.

 

 

The field-installed station bypass

Repair, replace, or rewire.

 

 

switch is bad or mis-wired.

 

 

 

 

 

Conveying times are too long

Time the hopper(s) during

 

 

loading, and set conveying times

 

 

(Time Fill mode only).

 

 

to a few seconds less.

 

 

 

Vacuum hoppers are over-filling.

Maximum conveying times are

Check proximity sensors for

proper operation and proper

 

 

too long and the PCB does not

wiring to the PCB. Repair as

 

 

recognize the Hopper Full

needed. Reset the conveying

 

 

proximity switch(es).

times to a reasonable value, and

 

 

 

adjust as needed.

2–Pump 12-Station Controllers

Chapter 6: Troubleshooting

46

Image 47
Contents Write Down Your Serial Numbers Here For Future Reference SCC 2-Pump 12-Station ControllersParts and Service Department If the Shipment is Not Complete Shipping InformationUnpacking and Inspection Event of Shipping DamageCredit Returns Warranty ReturnsReturns Table of Contents Maintenance Safety Symbols Used in this Manual SafetyHow to Use This Manual Wear Safety Glasses and Work Gloves Controller Safety TagsGeneral Responsibility ResponsibilityOperator Responsibility Maintenance ResponsibilityReporting a Safety Defect General Description Functional DescriptionModels Covered in This Manual Electrical Features Standard FeaturesOptional Features Mechanical FeaturesFail Safe Operation Safety Devices and InterlocksSafety Circuit Standards Safety Device Lock-OutsPump 12-Station Controllers Functional Description Mounting the Control Panel InstallationMaking Control Panel Power Drop Wiring Connections UncratingConnecting the Control Panel to the Pump Package Connecting the Control Panel to Vacuum HoppersTypical 24-Volt Junction Box Wiring Diagram Inputs SetupMain Power DC Controller Power SourcesMenu Tree Structure Gaining Access to the Menu SystemOperation MODE? NO/YES Station SETTINGS? NO/YESStation Settings Menu Operation Mode, Station Settings MenuStation 1 Normal =NORMAL N=SIGHTGLS ALL Normal MODE? NO/YESALL Sightglass MODE? NO/YES To Select a Station Press Station SET Dump DELAY? NO/YESDump Delay 11 15.0s Set Dump Delay, Station Settings MenuSet Input Delay, Station Settings Menu SET Input DELAY? NO/YESInput DLY 11 0.250s SET Station ALARMS? NO/YESSet Station Alarms, Station Settings Menu Alarm 11 Enabled =ENABLE N=DISABLE Assigning a Pump to a Station Alarm After 3 Loads Press Enter to SaveAssign PUMPSTATION? NO/YES To Select a Station Press HopperStation 10 Pump Select Pump 1 or Pump MODE? NO/YES Pump SETTINGS? NO/YESPump Settings Menu Setting the Pump ModeSET Active Pump Select Pump 1 or Select Pump 1 or USE Keypad to Enter Blowback SETTINGS? NO/YESEnable BLOWBACK? NO/YES Changing Blowback Settings, Pump Settings MenuOFF Time 0.500 s Blowback Pulses Setting for PumpOn Time 0.500 s Idle Delay Time Settings, Pump Settings Menu Blbk After 12 Loads Setting for PumpIdle Delay TIME? NO/YES Idle Time 10.000 s System Settings MenuSaving Controller Settings to Flash Memory Service Settings MenuLoad Time 10 63sec OperationText Area SectionController Description and Operation P1S----- Offline P2S----- Offline Pump Modes Single Pump ModeDual Pump Mode STATION-- Offline Time --- LogoStation Icon Segments Label Description Station IconsStatus Indicator Icons Label Description Status IndicatorsLabel Description Controller KeypadKey Descriptions Operation States OperationRuns but no station loads Shut-Down Updating Bios Software MaintenanceBios Connection, Electrical Diagram Drawing A0560970LEGEND General Troubleshooting TroubleshootingSee -5 on Page 75 for Controller Recovery using Flash Memory Technology Writing Parameters To FLASH-PLEASE Wait Saving BackupAppendix WarrantyWarranty Specifications Warranty RestrictionsCustomer Responsibilities Warranty LiabilitiesPump 12 station Controller Control Panel Drawings and DiagramsPlaces A0560974 Power cord A0560954 Spare Parts ListENCL, CARLON, Mount FLNG, MNK10L A0560974 RECT, BRIDGE, 25 AMPS, GBPC2510 Technical Assistance Contact Information Controller Identification Serial Number TagSetting the Ramp Up Time Service Only InformationRamp UP DLY 1.500s Setting for Pump n Service Settings MenuSET Ramp Down TIME? NO/YES Ramp DN DLY 8.000s Setting for Pump nSetting the Ramp Down Time SET Pump Stage TIME? NO/YES Stage Delay 3.000sSetting the Pump Stage Time Setting the LCD Blink Delay SET LCD Blink DELAY? NO/YESBlink Delay .500s Setting the Hi Vacuum Sensor Delay HI VAC Sensor DELAY? NO/YESHivac Delay 3.000s Setting for Pump n Setting the Hi Vacuum Vent Delay HI VAC Vent DELAY? NO/YESHV Vent DLY 10.000s Setting for Pump n HV Load CNT Setting the Hi Vacuum Load CountHI VAC Load COUNT? NO/YES Input Monitor Screen Using the Installation Aids MenusInput MONITOR? NO/YES BNK0 BNK1Output Control Menu Output CONTROL? NO/YESAutomatic or MANUAL? =AUTO Y=MANUAL OUTBNK0 OUTBNK1 Other Controller Restricted Areas OEM Menu Access Is NOW AvailableOEM SETTINGS? NO/YES Using the OEM Service MenuPWL11111 PWL22222 PWL33333 PWL44444 Recovering PasswordsVerifying Software Checksums Restoring the Controller to Factory DefaultsROM Checksum Press YES to Resume