Emerson 54e pH/ORP instruction manual PID Control

Page 59

MODEL 54e pH/ORP

SECTION 6.0

 

THEORY OF OPERATION

6.9PID CONTROL (continued)

5.The reaction of the system, when graphed, will resemble Figure 6-2, showing a change in the measured variable over the change in time. After a period of time (the process delay time), the meas- ured variable will start to increase (or decrease) rapidly. At some further time the process will begin to change less rapidly as the process begins to sta- bilize from the imposed step change. It is important to collect data for a long enough period of time to see the process begin to level off to establish a tan- gent to the process reaction curve.

6.When sufficient data has been collected, return the output signal to its original value using the simulate test function. Maintain the controller in this manual mode until you are ready to initiate automatic PID control, after you have calculated the tuning con- stants.

Once these steps are completed, the resulting process reaction curve is used to obtain information about the overall dynamics of the system. It will be used to cal- culate the needed tuning parameters of the Model 54e pH/ORP controller.

NOTE

The tuning procedure outlined below is adapted from "Instrumentation and Process Measurement and Control", by Norman A. Anderson, Chilton Co., Radnor, Pennsylvania, ©1980.

Information derived from the process reaction curve will be used with the following empirical formulas to predict the optimum settings for proportional and inte- gral tuning parameters.

Four quantities are determined from the process reac- tion curve for use in the formulas: time delay (D), time period (L), a ratio of these two (R), and plant gain (C).

A line is drawn on the process reaction curve tangent to the curve at point of maximum rise (slope) as shown in Figure 6-2. The Time Delay (D), or lag time, extends from "zero time" on the horizontal axis to the point where the tangent line intersects the time axis. The Response Time period (L), extends from the end of delay period to the time at which the tangent line inter- sects the 100% reaction completion line representing the process stabilization value. The ratio (R) of the Response Time period to the Time Delay describes the dynamic behavior of the system.

In the example, the process Delay Time (D) was four seconds and the Response Time period (L) was 12 seconds, so:

R = L 12 seconds = 3

D4 seconds

The last parameter used in the equations is a plant gain

(C). The plant gain is defined as a percent change in the controlled variable divided by the percent change in manipulated variable; in other words, the change in the measured variable (pH, conductivity, temperature) divid- ed by the percent change in the analog output signal.

The percent change in the controlled variable is defined as the change in the measured variable (pH, conductivity, temperature) compared to the measure- ment range, the difference between the 20 mA (Hi) and 4 (or 0) mA (Lo) setpoints, which you determined when configuring the analog output.

In the example shown in Figure 6-2:

The percent change in pH was:

pH2 - pH1

x 100% =

8.2

- 7.2 pH

= 33.3%

 

 

 

 

pH “Hi” - pH “Lo”

9.0

- 6.0 pH

 

The change in the output signal was:

6 - 4 milliamps x 100% = 12.5%

20 - 4

So the Plant Gain is:

C = 33.3 = 2.66 12.5

Once R and C are calculated, the proportional and inte- gral bands can be determined as follows:

Proportional band (%) = P = 286 CR

Integral Time (seconds per repeat) = I = 3.33 D x C

So for the example:

P = 286 (2.66) = 254% 3

I = 3.33 (4 sec.) 2.66 = 36 seconds

To enter these parameters, use the procedure detailed in Section 5.6.

53

Image 59
Contents Model 54e pH/ORP PH/ORP Hart Analyzer/ControllerElectrical Shock Hazard Essential InstructionsPage Section Title Description and SpecificationsModel 54E PH/ORP Microprocessor Analyzer Table No Title Appendix TitleList of Tables About This Document Table of Contents List of FiguresDescription of Controls Section Description and SpecificationsGeneral Description Current Outputs Specifications Physical Specifications GeneralPower Relative Humidity 95%, non condensing AlarmsRecommended Sensors Analyzer Specifications @ 25CPart NO. Description Ordering InformationCode Options Unpacking and Inspection Section InstallationMechanical Installation Locating the ControllerPanel Mounting Alarm Relay Output Wiring Section WiringPower Input Wiring Analog Output Wiring454EPH02 Tions will Result in Controller MALFUNC- Tion PH Sensor WiringPH Sensor Compatibility 454EPH01 Cable Dressing Final Electrical Check Wiring to Model Introduction Section CalibrationTemperature Calibration Hold Mode OffAdjust temp 25.1 C Automatic TWO-POINT Calibration Autocal bufferBuffer 1 -- Wait Calibration Notes Auto buffer cal doneUse the arrow keys to select the correct buffer Manual TWO-POINT Calibration Calibrate pointPt 04.00pH 25C Pt calibration doneSINGLE-POINT pH Calibration Standardize 7.01 pH59.16 mV/pH Temperature Compensation OptionsTemp comp Auto Output trimTrim Outputs Hold ModeOutput trim PH Settings List Section Software ConfigurationRanges Factory Settings User Settings Diagnostics Section Outline of Menu Levels Setpoint 07.00 pH Alarm High 14.00pHChanging Alarm Setpoints Simulate testsChanging Output Setpoints PID only Setpoint 7.00 pH4mA 0.00 pH 20mA 2.00 pH Setpoint + 06.90 pHMA +00.00 pH OutputOutput MA 0.00 pH 20 mA 14.00 pH Output 1 12.00 mASimulated tests Alarm setpoints Output setpointsTest output Test alarm Testing Outputs and AlarmsTest alarm 1 Open Test alarm 1 OpenMeasure pH Display right AL2Security Caution Display contrast Timeout OnOutput Control Parameters Control ModeDisplay Changing Output ParametersRange 4-20 mA Fault 22.00 mARange 4-20 mAl Hold Disable feature Fault 22.00mAOutput 2 control Output 2 setup Hold feature setupInterval timer AlarmsAlarm 3 control Relay Default None Alarm LowSetpoint 0.01 pH Delay 0 sec Hysteresis 0.01 pH Delay 0 secURV 2.00 pH Relay default NoneSetpoint +07.00 pH Time period 30 secAlarm 4 Setup Alarm FaultFeed limit Disable Timeout 3600 secOn time 120 sec Timer DisableRecovery 600 sec Interval Timer Examples Zero offset 60 mV DiagnosticsDiagnostics Off Stabilize pH 0.01 pH Stabilize time 10 sec DiagnosticsAuto Calibration Setup Autocal StandardStandard Buffers Auto Calibration SetupSection Theory of Operation Continuous Sensor DiagnosticsSee .8 for instructions on chang- ing these setpoints Interval TimerTypical set points Time Proportional Control TPC Mode Code Alarm RelaysAnalog Outputs Normal ModeAction Definitions Controller Mode PriorityController Mode Priority Chart Condition DefinitionsMeasurement and Set Point Feedback Control PID Control Mode CombinationsPID Control Code PID ControlControl Loop Adjustment and Tuning Proportional Mode GainProportional Gain Plus Integral Reset Process Reaction Curve Process Reaction Curve MethodPID Control Level 1 3 Password Privileges Section Special Procedures and FeaturesPassword Protection Lock all Configuring SecuritySecurity Custom CurveSensor iso 07.00 pH Solution Temperature CompensationTemp coeff +.000 Operate iso +07.00 pH Troubleshooting is easy as 1, 2, 3… Section TroubleshootingDiagnostic Messages Description of problem Diagnostic MessagesSymptom Action Quick Troubleshooting GuideDiagnostic Variables Theoretical pH vs. Millivolt Values at 25C 77F Ohms Ambient Temperature Troubleshooting GuidelinesTemperature Compensation Circuit Troubleshooting ProcedureController preamp check Figure Preamplifier Troubleshooting ProcedurePreamp in a junction box Figure Junction Box Preamplifier Check No Power Troubleshooting GuideCoated glass electrode Clean with soft cloth and clean water Password protected Part Number Description Replacement PartsGeneral Warranty RepairNON-WARRANTY Repair Section Return of MaterialQuick Startup ORP Appendix a ORP ConfigurationItem Choices ORP Settings User Settings Table A-1. ORP Settings ListDiagnostics Section Choices ORP Settings User SettingsSimulated tests Output setpointsORP Calibration Standardize 400 mVSensor or Circuit Board only Return of Materials RequestReturn of Material WarrantySpecifications subject to change without notice