Emerson 54e pH/ORP instruction manual Troubleshooting Guidelines, Temperature Compensation Circuit

Page 69

MODEL 54e pH/ORP

SECTION 8.0

 

TROUBLESHOOTING

8.2 TROUBLESHOOTING GUIDELINES

NOTE

To clear any Fault message, press the

2key.

If no specific error message is being displayed, the fol- lowing procedure can identify the specific problem.

The only sure way to diagnose sensor related condi- tions is to isolate the pH sensor from the process, im- merse the sensor in a pH buffer solution, and observe the controller response.

For any given pH value, the millivolt reading at the controller should be approximately that shown in Figure 8-1, Theoretical pH vs. Millivolt Values.

Therefore, one way to check the controller is to see if the incoming millivolt signal corresponds to the proc- ess pH or the pH of a test buffer solution (see Figure 8-1). The displayed pH value can be changed by stan- dardizing, but the millivolt value (displayed under "Diagnostic variables", see Section 8.1) will always be the exact incoming value. Another good check of the controller is to check the slope obtained after per-form- ing the two-point calibration with two different buffer solutions, as described in Section 3.

If the controller reads correctly when the sensor is removed from the process and isolated in a container of buffer solution, then the sensor and controller are most likely functioning correctly. The problem is caused by something in the process such as:

Sensor "seeing" poorly mixed, non-homogeneous solution.

Sensor located too close to chemical feed lines or heat sources.

Air bubbles entrained in the process or entrapped around the sensor.

Voltage on the process due to static electricity buildup, improperly grounded recirculation pump motors, or some other electrical source.

A ground loop caused by improper sensor wiring, as outlined in Installation, Section 2.

A source of electrical noise which only takes effect when the sensor is immersed in the process.

Most of these problems can be eliminated by either moving the sensor or providing proper grounding.

TEMPERATURE COMPENSATION CIRCUIT

Troubleshooting Procedure

Use this procedure to diagnose problems in the tem- perature compensation circuit or as directed by the Troubleshooting Guide, Table 8-3. Refer to the appro- priate wiring diagram in Section 3.

To check the sensor:

1.Check the resistance of the RTD element at the end of the sensor lead. Do not include intercon- necting wire. Disconnect the red lead and white lead on the end of the sensor cable.

2.Check the resistance between the red and the white leads. If values do not agree within ±1% of those shown below, replace the sensor (see Step 4).

OHMS

AMBIENT TEMPERATURE

100.00

32°F/0°C

107.79

68°F/20°C

109.62

77°F/25°C

111.67

86°F/30°C

115.54

104°F/40°C

119.40

122°F/50°C

3.

Disconnect sensor leads from interconnecting wire prior to measuring resistance. Values shown are only accurate when measured at the end of the cable directly attached to the sensor. Allow enough time for the temperature compensation RTD embedded in the sensor to stabilize to the sur- rounding temperature. Temperature coefficient = 0.215 ohms per °F.

4.If the sensor is bad, you can replace the sensor, or you can clear the fault by switching to manual tem- perature compensation as a short-term solution. Refer to Section 3.5 to program for manual tem- perature compensation. If the temperature com- pensator RTD in the sensor is bad, the displayed temperature will be incorrect. Using manual tem- perature compensation will remove all temperature related faults.

63

Image 69
Contents Model 54e pH/ORP PH/ORP Hart Analyzer/ControllerElectrical Shock Hazard Essential InstructionsPage Description and Specifications Model 54E PH/ORP Microprocessor AnalyzerSection Title Appendix Title List of TablesTable No Title About This Document Table of Contents List of FiguresSection Description and Specifications General DescriptionDescription of Controls Power Specifications Physical Specifications GeneralRelative Humidity 95%, non condensing Alarms Current OutputsRecommended Sensors Analyzer Specifications @ 25COrdering Information Code OptionsPart NO. Description Mechanical Installation Section InstallationLocating the Controller Unpacking and InspectionPanel Mounting Power Input Wiring Section WiringAnalog Output Wiring Alarm Relay Output Wiring454EPH02 PH Sensor Wiring PH Sensor CompatibilityTions will Result in Controller MALFUNC- Tion 454EPH01 Cable Dressing Final Electrical Check Wiring to Model Introduction Section CalibrationHold Mode Off Adjust temp 25.1 CTemperature Calibration Autocal buffer Buffer 1 -- WaitAutomatic TWO-POINT Calibration Auto buffer cal done Use the arrow keys to select the correct bufferCalibration Notes Pt 04.00pH 25C Calibrate pointPt calibration done Manual TWO-POINT CalibrationSINGLE-POINT pH Calibration Standardize 7.01 pHTemp comp Auto Temperature Compensation OptionsOutput trim 59.16 mV/pHHold Mode Output trimTrim Outputs PH Settings List Section Software ConfigurationRanges Factory Settings User Settings Diagnostics Section Outline of Menu Levels Changing Alarm Setpoints Alarm High 14.00pHSimulate tests Setpoint 07.00 pH4mA 0.00 pH 20mA 2.00 pH Setpoint 7.00 pHSetpoint + 06.90 pH Changing Output Setpoints PID onlyOutput OutputMA 0.00 pH 20 mA 14.00 pH Output 1 12.00 mA MA +00.00 pHTest output Test alarm Alarm setpoints Output setpointsTesting Outputs and Alarms Simulated testsTest alarm 1 Open Test alarm 1 OpenMeasure pH Display right AL2Security Caution Display contrast Timeout OnDisplay Control ModeChanging Output Parameters Output Control ParametersFault 22.00 mA Range 4-20 mAlRange 4-20 mA Output 2 control Output 2 setup Fault 22.00mAHold feature setup Hold Disable featureAlarms Alarm 3 controlInterval timer Setpoint 0.01 pH Delay 0 sec Alarm LowHysteresis 0.01 pH Delay 0 sec Relay Default NoneSetpoint +07.00 pH Relay default NoneTime period 30 sec URV 2.00 pHFeed limit Disable Alarm FaultTimeout 3600 sec Alarm 4 SetupTimer Disable Recovery 600 secOn time 120 sec Interval Timer Examples Diagnostics Diagnostics OffZero offset 60 mV Auto Calibration Setup DiagnosticsAutocal Standard Stabilize pH 0.01 pH Stabilize time 10 secStandard Buffers Auto Calibration SetupSection Theory of Operation Continuous Sensor DiagnosticsInterval Timer Typical set pointsSee .8 for instructions on chang- ing these setpoints Time Proportional Control TPC Mode Code Alarm RelaysAnalog Outputs Normal ModeController Mode Priority Chart Controller Mode PriorityCondition Definitions Action DefinitionsPID Control Code PID Control Mode CombinationsPID Control Measurement and Set Point Feedback ControlProportional Mode Gain Proportional Gain Plus Integral ResetControl Loop Adjustment and Tuning Process Reaction Curve Process Reaction Curve MethodPID Control Section Special Procedures and Features Password ProtectionLevel 1 3 Password Privileges Security Configuring SecurityCustom Curve Lock allSolution Temperature Compensation Temp coeff +.000Sensor iso 07.00 pH Operate iso +07.00 pH Troubleshooting is easy as 1, 2, 3… Section TroubleshootingDiagnostic Messages Description of problem Diagnostic MessagesSymptom Action Quick Troubleshooting GuideDiagnostic Variables Theoretical pH vs. Millivolt Values at 25C 77F Temperature Compensation Circuit Troubleshooting GuidelinesTroubleshooting Procedure Ohms Ambient TemperaturePreamplifier Troubleshooting Procedure Preamp in a junction box FigureController preamp check Figure Junction Box Preamplifier Check No Power Troubleshooting GuideCoated glass electrode Clean with soft cloth and clean water Password protected Part Number Description Replacement PartsNON-WARRANTY Repair Warranty RepairSection Return of Material GeneralQuick Startup ORP Appendix a ORP ConfigurationItem Choices ORP Settings User Settings Table A-1. ORP Settings ListDiagnostics Section Choices ORP Settings User SettingsSimulated tests Output setpointsORP Calibration Standardize 400 mVSensor or Circuit Board only Return of Materials RequestReturn of Material WarrantySpecifications subject to change without notice