6
+
X X X X
-
+
X X X X
-
+
X X . X
-
+
X X
-
+
X X
-
+
X X
-
+
Remark:
kp XXXX [default: gas 300] [default: elec 400]
Value of the proportion of the P.I.D. regulator for the burner. Press the return button to choose this option.
kd XXXX [default: gas 1000] [default: elec 3000]
Differential value of the P.I.D. regulator for the burner. Press the return button to choose this option.
ki XXXX [default: gas 0.5] [default: elec 2.0]
Integrator value of the P.I.D. regulator for the burner. Press the return button to choose this option.
Start PWM [default: 40]
At the moment of ignition of the burner: as long as there is no feedback measured, this value will be sent (only with gas heating).
Minimum PWM (default: 25)
When the measured signal is smaller, this value will be sent (only with gas heating).
PWM XX
Test signal to check the PWM of the burner. The chosen value (25%, 50% or 100%) will be sent during normal operation, independently of the temperature. After a voltage interruption, PWM will automatically be put on "none" (only with gas heating).
L.r or Lr.SS [default: L.r]
This parameter affects the function of the frequency converter and must therefore never be changed, unless another type of converter is built in. Press the return button to choose this option.
Settings kp, kd, ki, SPW, MPW and PWM are not possible when heat = steam.
53