Alliance Laundry Systems CI 1650/325, CI 2050/325 instruction manual 16A

Page 20

3

Electrical installation

The customer must install a circuit breaker for each machine.

Compare the type of network and its voltage with the data mentioned on the machine and pay attention to the instructions. For the connection, regulations according to VDE 0100 as well as the local valid regulations of the energy providing premises are to be taken into consideration.

It is very important to have the electric connections done by a qualified technician, in order to make sure that the installation is effected in accordance with the prevailing standards and instructions and the valid instructions where the machine is to be installed.

Make sure that the voltage, which is to be connected, corresponds to the voltage mentioned on the indication plate of the ironer inside the righthanded frame. The selected network connection cannot be less powerful than the H07RNF according to the VDE 0282 and should have a minimum diameter, which corresponds to the nominal electric power mentioned on the ironer.

Each machine must have a main switch. With this main switch, it is possible to cut the electrical equipment from the mains, also by persons who have not been trained in the field of electrotechnics. This is necessary for cleaning, maintenance and reparation activities, both for the machine itself and for the corresponding electrical equipment. In the guidance from the feeding to the electrical equipment, the main switch is always behind the proper mains connection.

The main switch can also be applied in the supply guidance separately. It needs to be placed very close to the machine so that there cannot be misunderstandings that the switch belongs to the machine.

When there are two or more main switches, there may not exist a dangerous situation when not all the main switches are disconnected at the same time. For each main switch, there must be a warning, which says that there is more than one feeding. If the main switches are placed far from each other (not usual and not recommended), a supply will have to be made which separates the main switches by disconnecting one of them. The control of this supply is in fact a safety-related control which applies EN 954-1. In practice, the supply will often be executed in category 1 (EN 954-1) with bipolar contacts.

Overview circuit breakers and wire section feeding cable per machine

 

Circuit breaker size

Cable section

Fuse

CI325 gas

25A

1,5mm²

16A

CI325 elec 3x230V

80A

16mm²

63A

CI325 elec 3x400V

63A

6mm²

40A

20

Image 20
Contents Part No. D1273 SeptemberPage Contents Safety Information Explanation of Safety MessagesPage Safety notice Important Safety Instructions Page Product description Intended useDescription of structural components Workplaces and noise level Technical data CI1650/325, CI2050/325 1650/325 2050/325Sound level measurement Warranty and service instructions Initial setup of the machine Transport and machine fasteningSetting up the machine 30 cmPage Page Page 16A Page Basic checks Ventilation of the roomAir filters Exhaust gasesOperation Operating devices and their positionStarting the machine Set the iron temperature FunctionsSet the ironing speed PedalReturn button not with guiding ribbons EndingFailure and information signals Page Page Page Machine function, adjustment and troubleshooting Description of machine functionsGeneral description of machine function Feeding sheets and towelsOperating the foot pedal option Setting the temperature AdviceSetting the speed Manual drive Adjustments of the machine Guiding ironing beltsTightening the drive chain Tightening the ironing belts Tightening the feeding belts Adjusting the gap between input table and main roll Fault Condition Possible cause TroubleshootingFault Cause Remedy After reset Fault Condition SolutionTemperature control Description of the control systemGeneral description of the control system Electric heating controlStart/stop function Control of exhaust ventilatorSpeed control Control panel and function keys Menu structure and how to enter Manual versionMenu structure Manu adjusting menu Coin adjusting menu Add XX default C1M coin 1 MediumC1H coin 1 High C2L coin 2 lowTechnical menu Kp Xxxx default gas 300 default elec Kd Xxxx default gas 1000 default elecKi Xxxx default gas 0.5 default elec Start PWM defaultREv Y/n default YES not adjustable with coin TMPDisplay menu Central panelSigma explorer DiSPMaintenance Safety adviceMaintenance scheme Daily maintenanceWeekly maintenance Monthly maintenancePage Page Half-yearly maintenance Feeding belts Ironer belts DriveScrapers