Electrolux 137382100 A (1106) Gas supply requirements, Exhaust system requirements, Fire Hazard

Page 5

Installation Requirements

5

Gas supply requirements

WARNING

EXPLOSION HAZARD

Uncoated copper tubing will corrode when subjected to natural gas, causing gas leaks. Use ONLY black iron, stainless steel, or plastic- coated brass piping for gas supply.

1.Installation MUST conform with local codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (latest edition).

2.The gas supply line should be 1/2 inch (1.27 cm) pipe.

3.If codes allow, flexible metal tubing may be used to connect your dryer to the gas supply line. The tubing MUST be constructed of stainless steel or plastic-coated brass.

4.The gas supply line MUST have an individual shutoff valve installed in accordance with the

B149.1, Natural Gas and Propane Installation Code.

5.A 1/8 inch (0.32 cm) N.P.T. plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of the gas supply connection to the dryer.

6.The dryer MUST be disconnected from the gas supply piping system during any pressure testing of the gas supply piping system at test pressures in excess of 1/2 psig (3.45 kPa).

7.The dryer MUST be isolated from the gas supply piping system during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.45 kPa).

8.Connections for the gas supply must comply with the Standard for Connectors for Gas Appliances, ANSI Z21.24.

Exhaust system requirements

Use only 4 inch (102 mm) diameter (minimum) rigid or flexible metal duct and approved vent hood which has a swing-out damper(s) that open when the dryer is in operation. When the dryer stops, the dampers automatically close to prevent drafts and the entrance of insects and rodents. To avoid restricting the outlet, maintain a minimum of 12 inches (30.5 cm) clearance between the vent hood and the ground or any other obstruction.

WARNING

FIRE HAZARD

Failure to follow these instructions can create excessive drying times and fire hazards.

The following are specific requirements for proper and safe operation of your dryer.

WARNING

FIRE HAZARD

Do not install a clothes dryer with flexible plastic or metal foil venting materials. Flexible venting materials are known to collapse, be easily crushed and trap lint. These conditions will obstruct clothes dryer airflow and increase the risk of fire.

CorrectIncorrect

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correct

 

 

 

Incorrect

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If your present system is made up of plastic duct or metal foil duct, replace it with a rigid or semi- rigid metal duct. Also, ensure the present duct is free of any lint prior to installing dryer duct.

Image 5
Contents Installation Instructions Table of contents Important Safety InstructionsInstallation Checklist Installation RequirementsPre-installation requirements Please read and save this guide Questions?Wire receptacle Nema type 14-30R Wire receptacle Nema type 10-30RElectrical system requirements Electrical Requirements for Electric DryerExhaust system requirements Gas supply requirementsExplosion Hazard Fire HazardVent Hood Type Exhaust DirectionInstall male fittings in correct direction Manufactured or mobile home installationClearance requirements Do not Install Your DryerDryer dimensions Electrical installation Installation InstructionsGrounding requirements Electric dryer USA Electrical Shock HazardGrounding requirements Gas dryer USA and Canada Grounding requirements Electric dryer CanadaElectrical connection non-Canada 3 wire cord Electrical connection non-Canada 4 wire cord To dryer Gas connectionRubber Washers Must be Present Water connection Steam Model onlyWater connection, con’t Steam Model only General installation 2a2b Performing Installation CyclePreparing to reverse door swing Reversing DoorRemoving door and hardware Removing Trim RingRemoving Hinge from Front Panel Reversing door and hardwareReattaching Hinge to Front Panel Reversing Hardware on Front PanelRemoving Hole Plug Removing Latch IndicatorRemoving Striker Plate Reinserting Hole Plug Reinserting Latch IndicatorReattaching Latch Plate Reattaching door and hardware Replacement parts in U.S. and Canada AccessoriesOptions Electrical HazardInstallation Instructions Table des matières Mesures de sécurité importantesListe de vérification d’installation Exigences d’installationExigences avant linstallation Veuillez lire et conserver ce guideExigences des systèmes électriques Exigences dinstallationPrise à 4 alvéoles Nema type 14-30R Prise à 3 alvéoles Nema type 10-30RExigences du système dévacuation Exigences relatives à lalimentation en gazRisque Dexplosion Risque DincendieDirection D’ÉVACUATION Exigences du système dévacuation suiteInstallez les raccords mâles dans le bon sens Installation dans une maison usinée ou mobileExigences de dégagement Ninstallez PAS Votre SécheuseDimensions de sécheuse Risque DE Choc Électrique Installation électriqueExigences de mise à la terre Sécheuse électrique É.-U Exigences de mise à la terre Sécheuse à gaz É.-U. et Canada Instructions d’installationExigences de mise à la terre Sécheuse électrique Canada Fil neutre Connexion électrique sauf au Canada cordon à 3 filsBlanc à la borne centrale Argent du Connexion électrique sauf au Canada cordon à 4 filsConnexion de gaz Instructions dinstallationLES Rondelles EN Caoutchouc Doivent Être Présentes Raccordement deau modèles à la vapeur uniquementRaccordement deau, suite modèles à la vapeur uniquement Installation générale Programme dinstallation Préparation à linversion de la porte Inversion de la porteRetrait de la porte et de la quincaillerie Retrait de lanneau de garnitureRetrait de la charnière du panneau avant Inversion de la porte et de la quincaillerieRemontage de la charnière au panneau avant Inversion de la quincaillerie du panneau avantRetrait du bouchon Retrait de la plaque-percuteurRetrait du voyant de loquet Fixation de la plaque de loquet Réinstallation du voyant de loquetRéinstallation du bouchon Remontage de la porte et de la quincaillerie Risque Électrique AccessoiresPièces de rechange au Canada Installation Instructions Índice Instrucciones importantes de seguridadLea y conserve esta guía Requisitos de instalaciónLista de verificación de instalación Requisitos de preinstalaciónReceptáculo trifilar tipo Nema 10-30R Requisitos del sistema eléctricoReceptáculo tetrafilar tipo Nema 14-30R Requisitos Eléctricos DE LA Secadora EléctricaRequisitos del sistema de escape Requerimientos del suministro de gasPeligro DE Explosión Peligro DE IncendioDirección DEL Escape Requisitos del sistema de escape, continuaciónInstale los accesorios macho en la dirección correcta Instalación en una casa rodanteNo Instale LA Secadora Requisitos de despejeDimensiones de la secadora Peligro DE Descarga Eléctrica Instalación eléctricaRequisitos de conexión a tierra secadora eléctrica Canadá Instrucciones de instalaciónTornillo Verde Conexión eléctrica fuera de Canadá trifilarTornillo Verde De conexión Tierra Conexión eléctrica fuera de Canadá tetrafilarFlujo DE GAS Conexión de gasArandelas DE Goma Deben Estar Presentes Conexión de agua modelo al vapor solamenteConexión de agua modelo a vapor solamente Instalación general El ciclo de instalación realizará varias rutinas de diag Ejecución del ciclo de instalaciónPreparación para invertir la orientación de la puerta Inversión de la puertaDesinstalación de la puerta y los accesorios Desinstalación del anillo de molduraDesinstalación de la bisagra del panel delantero Inversión de la puerta y los accesoriosInversión de los accesorios del panel delantero Reinstalación de la bisagra en el panel delanteroDesinstalación del tapón para agujero Desinstalación de los accesorios de la puertaExtracción del indicador de pestillo Reinstalación del tapón para agujero Reinstalación del indicador de pestilloReinstalación de la placa del pestillo Reinstalación de la puerta y los accesorios Piezas de repuesto en los Estados Unidos OpcionesAccesorios Page Page