2.Technical Gas Data a. Gas Specifications
| TYPE OF GAS |
| ||
|
|
|
|
|
| NATURAL | LIQUID PROPANE | ||
|
|
|
|
|
Manifold Pressure* | 3.5 inches W.C. | 8.7 mb | 10.5 inches W.C. | 26.1 mb |
|
|
|
|
|
6.0 - 12.0 inches W.C. | 14.92 - 29.9 mb | 10.5 inches W.C. | 26.1 mb | |
|
|
|
|
|
Shaded areas are stated in metric equivalents
*Measured at outlet side of gas valve pressure tap when gas valve is on.
b.Gas Connections
Run a
Inlet connection
1)Natural Gas
Pressure regulation is controlled by both gas valve’s internal regulators. Incoming supply pressure must be consistently between a minimum of 6.0 inches (14.92 mb) water column (W.C.) and a maximum of 12.0 inches (29.9 mb) water column.
2)Liquid Propane (L.P.) Gas
Dryers made for use with L.P. gas have both of their gas valves internal pressure regulators blocked open so that the gas pressure must be regulated upstream of the dryer. The pressure is measured at each gas valve pressure tap must be a consistent 10.5 inches (26.1 mb) water column. There is no regulator or regulation provided in an L.P. gas dryer. The water column must be regulated at the source (L.P. tank) or external regulator/regulation must be added to each dryer.