| INSTALLATION AND WIRING |
| |
|
|
|
|
|
|
|
|
|
|
| Type | Symbol | Terminal Name |
|
| Description |
|
| |
|
|
|
|
|
|
|
|
| |
|
|
| 10E |
| 10VDC, permissible load current | When the frequency setting potentiometer is |
| ||
|
|
|
| 10mA |
| connected in the |
| ||
|
|
|
| Frequency setting |
|
| |||
|
|
|
|
|
| terminal 10. |
|
| |
|
|
|
| power supply | 5VDC, permissible load current |
|
| ||
|
|
| 10 | When it is connected to terminal 10E, change the |
| ||||
|
|
|
| 10mA |
|
| |||
|
|
|
|
|
| input specifications of terminal 2. |
| ||
|
| settingfrequencyAnalog |
|
|
|
|
| ||
| signalsInput |
|
| By entering 0 to 5VDC (0 to 10VDC), the maximum output frequency is reached at 5V |
| ||||
|
|
|
|
|
| ||||
|
|
| 2 | Frequency setting | (or 10V) and I/O are proportional. Switch between input 0 to 5VDC (factory setting) |
| |||
|
|
| (voltage) | and 0 to 10VDC from operation terminal. Input resistance 10kΩ . Maximum |
| ||||
|
|
|
|
| |||||
|
|
|
|
| permissible voltage 20V. |
|
|
|
|
|
|
|
| Frequency setting | By entering 4 to 20mADC, the maximum output frequency is reached at 20mA and I/O |
| |||
|
|
| 4 | are proportional. This input signal is valid only when the AU signal is on. Input |
| ||||
|
|
| (current) |
| |||||
|
|
|
| resistance 250 . Maximum permissible current 30mA. |
|
| |||
|
|
|
|
| Ω |
|
|
|
|
|
|
|
|
| By entering 0 to ± 5VDC 0 to ± 10VDC, this signal is added to the frequency setting |
| |||
|
|
| 1 | Auxiliary frequency | signal of terminal 2 or 4. Switch between input 0 to ± 5VDC and 0 to ± 10VDC (factory |
| |||
|
|
| setting | setting) from operation terminal. Input resistance 10kΩ . Maximum permissible voltage |
| ||||
|
|
|
|
| |||||
|
|
|
|
| ± 20V. |
|
|
|
|
|
|
| 5 | Frequency setting | Common to the frequency setting signal (terminal 2, 1 or 4) and analog output terminal |
| |||
|
|
| input common | AM. Do not earth. |
|
|
|
| |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| |||
|
| Contact |
|
| stopped by the inverter protective function activated. |
|
| ||
|
| A,B,C |
| (continuity across |
|
| |||
|
|
| Alarm output | 200VAC 0.3A, 30VDC 0.3A. Alarm: discontinuity across |
|
| |||
|
|
|
|
| (discontinuity across |
|
|
| |
|
|
|
|
| Switched low when the inverter output frequency is equal to or |
|
| ||
|
|
| RUN | Inverter running | higher than the starting frequency (factory set to 0.5Hz, variable). |
|
| ||
|
|
| Switched high during stop or DC dynamic brake operation(note1) |
|
| ||||
|
|
|
|
| Permissible load 24VDC 0.1A. |
| Output terminal |
| |
|
|
|
|
| Switched low when the output frequency has reached within ± 10% |
| |||
|
|
|
|
| of the set frequency (factory setting, variable). Switched high | function selection |
| ||
|
|
| SU | Up to frequency | (Pr. 190 to Pr. |
| |||
|
|
| during acceleration, deceleration or stop(note 1). Permissible load |
| |||||
| signalsOutput | collectorOpen |
|
| 24VDC 0.1A. |
|
| 195) change |
|
|
|
|
|
| terminal functions. |
| |||
|
|
|
|
|
|
|
| ||
|
|
|
|
| Switched low when the stall prevention function has caused stall |
| |||
|
|
|
|
|
|
| |||
|
|
| OL | Overload alarm | prevention to be activated. Switched high when stall prevention is |
|
| ||
|
|
|
|
| reset(note 1). Permissible load 24VDC 0.1A. |
|
| ||
|
|
| IPF | Instantaneous power | Switched low when instantaneous power failure or undervoltage |
|
| ||
|
|
| failure | protection is activated(note 1). Permissible load 24VDC 0.1A. |
|
| |||
|
|
|
|
| Switched low when the output frequency has reached or exceeded |
|
| ||
|
|
| FU | Frequency detection | the detection frequency set as appropriate. Switched high when |
|
| ||
|
|
| below the detection frequency(note 1). Permissible load 24VDC |
|
| ||||
|
|
|
|
| 0.1A |
|
|
|
|
|
|
| SE | Open collector output | Common to the RUN, SU, OL, IPF and FU terminals. |
|
| ||
|
|
| common |
|
| ||||
|
|
|
|
|
|
|
|
| |
|
| Pulse |
|
|
|
| Factory setting of output item: |
|
|
|
| FM | For meter | One selected from 16 monitoring | Frequency |
|
| ||
|
| items, such as output frequency, | Permissible load current 1mA |
| |||||
|
|
|
|
| |||||
|
|
|
|
| is output(note 2). |
| 1440 pulses/second. at 60Hz |
| |
|
| Analog |
|
| The output signal is proportional | Factory setting of output item: |
|
| |
|
| AM | Analog signal output | to the magnitude of each | Frequency |
|
| ||
|
|
|
|
| |||||
|
|
| monitoring item. |
| Output signal 0 to 10VDC |
| |||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| Permissible load current 1mA |
| |
| Communication | RS485 |
|
| With the operation panel connector, communication can be made through |
| |||
|
|
|
|
|
| ||||
|
|
|
|
| ∙ Conforming Standard | : EIA Standard |
|
| |
|
|
| | PU connector | ∙ Transmission format | : |
|
| |
|
|
|
|
| ∙ Communication speed : Maximum 19200 baud rates |
|
| ||
|
|
|
|
| ∙ Overall length | : 500m |
|
|
|
|
|
|
|
|
|
|
|
|
|
Note1: Low indicates that the open collector outputting transistor is on (conducts). High indicates that the transistor is off (does not conduct).
Note2: Not output while the inverter is reset.
7