Mitsubishi Electronics FR-A500L instruction manual ,B,C, Run, Ipf

Page 15

 

 

 

 

 

 

 

INSTALLATION AND WIRING

 

 

 

 

 

 

 

 

 

 

 

 

Type

Symbol

Terminal Name

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10E

 

10VDC, permissible load current

When the frequency setting potentiometer is

 

 

 

 

 

10mA

 

connected in the factory-set state, connect it to

 

 

 

 

 

Frequency setting

 

 

 

 

 

 

 

 

terminal 10.

 

 

 

 

 

 

power supply

5VDC, permissible load current

 

 

 

 

 

10

When it is connected to terminal 10E, change the

 

 

 

 

 

10mA

 

 

 

 

 

 

 

 

input specifications of terminal 2.

 

 

 

settingfrequencyAnalog

 

 

 

 

 

 

signalsInput

 

 

By entering 0 to 5VDC (0 to 10VDC), the maximum output frequency is reached at 5V

 

 

 

 

 

 

 

 

 

 

2

Frequency setting

(or 10V) and I/O are proportional. Switch between input 0 to 5VDC (factory setting)

 

 

 

 

(voltage)

and 0 to 10VDC from operation terminal. Input resistance 10kΩ . Maximum

 

 

 

 

 

 

 

 

 

 

 

permissible voltage 20V.

 

 

 

 

 

 

 

 

Frequency setting

By entering 4 to 20mADC, the maximum output frequency is reached at 20mA and I/O

 

 

 

 

4

are proportional. This input signal is valid only when the AU signal is on. Input

 

 

 

 

(current)

 

 

 

 

 

resistance 250 . Maximum permissible current 30mA.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

By entering 0 to ± 5VDC 0 to ± 10VDC, this signal is added to the frequency setting

 

 

 

 

1

Auxiliary frequency

signal of terminal 2 or 4. Switch between input 0 to ± 5VDC and 0 to ± 10VDC (factory

 

 

 

 

setting

setting) from operation terminal. Input resistance 10kΩ . Maximum permissible voltage

 

 

 

 

 

 

 

 

 

 

 

± 20V.

 

 

 

 

 

 

 

5

Frequency setting

Common to the frequency setting signal (terminal 2, 1 or 4) and analog output terminal

 

 

 

 

input common

AM. Do not earth.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Change-over contact output indicating that the output has been

 

 

 

 

Contact

 

 

stopped by the inverter protective function activated.

 

 

 

 

ABC

 

(continuity across A-C), normal: continuity across B-C

 

 

 

 

 

Alarm output

200VAC 0.3A, 30VDC 0.3A. Alarm: discontinuity across B-C

 

 

 

 

 

 

 

(discontinuity across A-C).

 

 

 

 

 

 

 

 

Switched low when the inverter output frequency is equal to or

 

 

 

 

 

RUN

Inverter running

higher than the starting frequency (factory set to 0.5Hz, variable).

 

 

 

 

 

Switched high during stop or DC dynamic brake operation(note1)

 

 

 

 

 

 

 

Permissible load 24VDC 0.1A.

 

Output terminal

 

 

 

 

 

 

Switched low when the output frequency has reached within ± 10%

 

 

 

 

 

 

of the set frequency (factory setting, variable). Switched high

function selection

 

 

 

 

SU

Up to frequency

(Pr. 190 to Pr.

 

 

 

 

during acceleration, deceleration or stop(note 1). Permissible load

 

 

signalsOutput

collectorOpen

 

 

24VDC 0.1A.

 

 

195) change

 

 

 

 

 

 

terminal functions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Switched low when the stall prevention function has caused stall

 

 

 

 

 

 

 

 

 

 

 

OL

Overload alarm

prevention to be activated. Switched high when stall prevention is

 

 

 

 

 

 

 

reset(note 1). Permissible load 24VDC 0.1A.

 

 

 

 

 

IPF

Instantaneous power

Switched low when instantaneous power failure or undervoltage

 

 

 

 

 

failure

protection is activated(note 1). Permissible load 24VDC 0.1A.

 

 

 

 

 

 

 

Switched low when the output frequency has reached or exceeded

 

 

 

 

 

FU

Frequency detection

the detection frequency set as appropriate. Switched high when

 

 

 

 

 

below the detection frequency(note 1). Permissible load 24VDC

 

 

 

 

 

 

 

0.1A

 

 

 

 

 

 

 

SE

Open collector output

Common to the RUN, SU, OL, IPF and FU terminals.

 

 

 

 

 

common

 

 

 

 

 

 

 

 

 

 

 

 

 

Pulse

 

 

 

 

Factory setting of output item:

 

 

 

 

FM

For meter

One selected from 16 monitoring

Frequency

 

 

 

 

items, such as output frequency,

Permissible load current 1mA

 

 

 

 

 

 

 

 

 

 

 

is output(note 2).

 

1440 pulses/second. at 60Hz

 

 

 

Analog

 

 

The output signal is proportional

Factory setting of output item:

 

 

 

 

AM

Analog signal output

to the magnitude of each

Frequency

 

 

 

 

 

 

 

 

 

 

monitoring item.

 

Output signal 0 to 10VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Permissible load current 1mA

 

 

Communication

RS485

 

 

With the operation panel connector, communication can be made through RS-485.

 

 

 

 

 

 

 

 

 

 

 

 

Conforming Standard

: EIA Standard RS-485

 

 

 

 

 



PU connector

Transmission format

: Multi-drop link

 

 

 

 

 

 

 

Communication speed : Maximum 19200 baud rates

 

 

 

 

 

 

 

Overall length

: 500m

 

 

 

 

 

 

 

 

 

 

 

 

 

Note1: Low indicates that the open collector outputting transistor is on (conducts). High indicates that the transistor is off (does not conduct).

Note2: Not output while the inverter is reset.

7

Image 15
Contents FR-A500L This section is specifically about safety matters Electric Shock Prevention Fire PreventionInjury Prevention Trial run Transportation and installationWiring Additional instructionsDisposing of the inverter Maintenance, inspection and parts replacementOperation Emergency stopContents Chapter Outline Pre-Operation Information Precautions for operationInstallation WiringName Description Basic ConfigurationBasic configuration NFB ELBChapter Instructions for installation InstallationAt 5cm 1.97 inch Terminal connection diagram WiringTerminal Name Description Symbol Terminal Name DescriptionDescription of main circuit terminals Description of control circuit terminals,B,C RUNIPF Wiring instructions Wiring of the main circuit800 2300 Terminal block layoutP1, P, N Connection procedure Connection of the power supply and motorNA version(OR Version) Wiring of the control circuitChanging the control logic RUN DC24V How to use terminals STOP, CS and PC For RS-485 communication Connection to the PU connectorDesign information Chapter Operation Chapter Parameters Parameters Parameter ListDU/PU main display data selection F4 fourth frequency voltage 173 201 Can be accessed when Pr = Protective Functions Unit Name Description Errors AlarmsError alarm definitions Operation ParameterOPT OHTOLT STPMB7 CTEMain circuit error E,15 details Charge AlarmName Details Correspondences between digital and actual characters To know the operating status at the occurrence of alarmOperation Panel Alarm code outputResetting the inverter Alarm Code Alarm Output across B-C FR-DU04Troubleshooting Checking the operation panel display at alarm stopOperation Panel Check Point Remedy Display Check Point Remedy Motor rotates in opposite direction Faults and check pointsSpeed greatly differs from the setting Motor remains stoppedSpeed does not increase Operation mode is not changed properlyPower lamp is not lit Motor current is largePeriodic inspection Precautions for Maintenance and InspectionPrecautions for maintenance and inspection Check itemsDielectric strength test Insulation resistance test using meggerDescription Method Criterion Instrument Daily Daily and Periodic InspectionPreparation Checking methodModule device numbers and terminals to be checked Relays Replacement of partsCooling fan Smoothing capacitorsMeasurement of voltages and currents Measurement of main circuit voltages, currents and powerMeasuring Point Measuring Instrument 10VDC5VDC Chapter Specifications Model specifications Standard specificationCommon specifications FR-PU04 AlarmFR-A540L-450K, 375K Outline drawingsFR-A540L-540K~800K P5S RDB RDA SDB SDAAppendices Appendix AppendixFront Wiring between cooling fan and terminals is as follows Check the air flow directionEF-40ETB R G Converter EF-30ETB Control Inverter MT-BR5MT-BR5 TH1 TH2 PR PR E Resistor Temperature Abnormal SignalsShipment case example
Related manuals
Manual 64 pages 26.15 Kb