Mitsubishi Electronics FR-A500L instruction manual Can be accessed when Pr =

Page 33

PARAMETERS

Func-

Parameter

 

 

 

 

Minimum

Factory Setting

Refer To

Name

Setting Range

Setting

Page:

tion

Number

 

 

 

 

Increments

 

 

 

<Note9>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

functions

278

Brake opening frequency (Note 3)

0 to 30Hz

0.01Hz

 

3Hz

142

279

(Note 3)

 

 

 

 

 

 

 

 

 

Brake opening current (Note 3)

0 to 200%

0.1%

 

130%

142

 

280

Brake opening current detection time

0 to 2 sec

0.1 sec

0.3 sec

142

 

 

sequence

 

 

 

 

 

 

 

 

 

 

281

Brake operation time at start (Note 3)

0 to 5 sec

0.1 sec

0.3 sec

142

 

 

282

Brake operation frequency (Note 3)

0 to 30Hz

0.01Hz

 

6Hz

142

 

283

Brake operation time at stop (Note 3)

0 to 5 sec

0.1 sec

0.3 sec

142

Brake

284

Deceleration detection function selection

0, 1

 

1

 

0

142

(Note 3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

285

Overspeed detection frequency

0 to 30Hz, 9999

0.01Hz

 

9999

142

 

*570

CT/VT Selection

0, 1

 

1

 

0

151

functions

900

FM terminal calibration



 



 



152

901

AM terminal calibration



 



 



152

 

902

Frequency setting voltage bias

0 to 10V

 

0 to 60Hz

0.01Hz

0V

 

0Hz

154

Calibration

903

Frequency setting voltage gain

0 to 10V

 

1 to

0.01Hz

5V

 

60Hz

154

 

400Hz

 

<50Hz>

905

Frequency setting current gain

0 to 20mA

 

0.01Hz

20mA

 

154

 

 

 

 

 

 

 

 

 

 

904

Frequency setting current bias

0 to 20mA

 

0 to 60Hz

0.01Hz

4mA

 

0Hz

154

 

 

 

 

 

1 to

 

 

 

60Hz

 

 

 

 

 

 

400Hz

 

 

 

<50Hz>

 

Additional function

990

Buzzer control

0, 1

 

1

 

1

156

 

 

 

 

 

 

 

 

 

 

 

991

Parameter unit parameters

Refer to the parameter unit instruction manual for details.

 

 

 

 

 

 

 

 

 

 

 

 

Note: 1. Indicates the parameter settings which are ignored when the advanced magnetic flux vector control mode is selected.

2.The half-tone screened parameters allow their settings to be changed during operation if 0 (factory setting) has been set in Pr. 77. (Note that the Pr. 72 and Pr. 240 settings cannot be changed during external operation.)

3.Can be set when Pr. 80, 81 9999, Pr. 60 = 7 or 8.

4.Can be accessed when Pr. 80, 81 9999, Pr. 77 = 801.

5.Can be accessed when Pr. 270 = 1 or 3, Pr. 80, 81 9999.

6.The setting range and min. setting unit will differ according to the Pr. 71 "applied motor" setting value.

7.Can be accessed when Pr. 29 = 3.

8.Parameters marked asterisk (*) on top are different setting range, factory setting or function from FR-A540L.

9.Page numbers correspond to A540/A560L instruction manual, IB07401-0x.

23

Image 33
Contents FR-A500L This section is specifically about safety matters Electric Shock Prevention Fire PreventionInjury Prevention Wiring Transportation and installationAdditional instructions Trial runOperation Maintenance, inspection and parts replacementEmergency stop Disposing of the inverterContents Chapter Outline Installation Precautions for operationWiring Pre-Operation InformationBasic configuration Basic ConfigurationNFB ELB Name DescriptionChapter Instructions for installation InstallationAt 5cm 1.97 inch Terminal connection diagram WiringDescription of main circuit terminals Symbol Terminal Name DescriptionDescription of control circuit terminals Terminal Name Description,B,C RUNIPF Wiring instructions Wiring of the main circuit800 2300 Terminal block layoutP1, P, N Connection procedure Connection of the power supply and motorNA version(OR Version) Wiring of the control circuitChanging the control logic RUN DC24V How to use terminals STOP, CS and PC For RS-485 communication Connection to the PU connectorDesign information Chapter Operation Chapter Parameters Parameters Parameter ListDU/PU main display data selection F4 fourth frequency voltage 173 201 Can be accessed when Pr = Protective Functions Error alarm definitions Errors AlarmsOperation Parameter Unit Name DescriptionOLT OHTSTP OPTMB7 CTEMain circuit error E,15 details Charge AlarmName Details Correspondences between digital and actual characters To know the operating status at the occurrence of alarmResetting the inverter Alarm code outputAlarm Code Alarm Output across B-C FR-DU04 Operation PanelTroubleshooting Checking the operation panel display at alarm stopOperation Panel Check Point Remedy Display Check Point Remedy Speed greatly differs from the setting Faults and check pointsMotor remains stopped Motor rotates in opposite directionPower lamp is not lit Operation mode is not changed properlyMotor current is large Speed does not increasePrecautions for maintenance and inspection Precautions for Maintenance and InspectionCheck items Periodic inspectionDielectric strength test Insulation resistance test using meggerDescription Method Criterion Instrument Daily Daily and Periodic InspectionPreparation Checking methodModule device numbers and terminals to be checked Cooling fan Replacement of partsSmoothing capacitors RelaysMeasurement of voltages and currents Measurement of main circuit voltages, currents and powerMeasuring Point Measuring Instrument 10VDC5VDC Chapter Specifications Model specifications Standard specificationCommon specifications FR-PU04 AlarmFR-A540L-450K, 375K Outline drawingsFR-A540L-540K~800K P5S RDB RDA SDB SDAAppendices Appendix AppendixFront Wiring between cooling fan and terminals is as follows Check the air flow directionEF-40ETB R G Converter EF-30ETB Control Inverter MT-BR5MT-BR5 TH1 TH2 PR PR E Resistor Temperature Abnormal SignalsShipment case example