PROTECTIVE FUNCTIONS
(5) Motor current is large.
∙Check that the load is not too heavy.
∙Check that the torque boost (Pr. 0, Pr. 46, Pr. 112) setting is not too large.
(6) Speed does not increase.
∙Check that the maximum frequency (Pr. 1) setting is correct.
∙Check that the load is not too heavy. (In agitators, etc., load may become heavy in winter.)
∙Check that the torque boost (Pr. 0, Pr. 46, Pr. 112) setting is not too large to activate the stall prevention function.
(7) Speed varies during operation.
During operation under advanced magnetic flux vector control, the output frequency varies with load fluctuation between 0 and 2Hz. This is a normal operation and is not a fault.
1)Inspection of load
∙Check that the load is not varying.
2)Inspection of input signal
∙Check that the frequency setting signal is not varying.
∙Check that the frequency setting signal is not affected by induced noise.
3)Others
∙Check that the settings of the applied motor capacity (Pr. 80) and the number of applied motor poles (Pr. 81) are correct for the inverter and motor capacities in advanced magnetic flux vector control.
∙Check that the wiring length is within 30m in advanced magnetic flux vector control.
∙Check that the wiring length is correct in V/F control.
(8) Operation mode is not changed properly.
If the operation mode is not changed properly, check the following:
1. External input signal ・・・・・・ Check that the STF or STR signal is off.
When it is on, the operation mode cannot be changed.
2. Parameter setting ・・・・・・・・ Check the Pr. 79 setting.
When the setting of Pr. 79 "operation mode selection" is "0" (factory setting), switching input power on places the inverter in the external operation mode. Press the operation panel's [MODE] key three times and press the [UP] key (press the [PU] key for the parameter unit
(9) Operation panel (FR-DU04) display is not provided.
∙Make sure that the operation panel is connected securely with the inverter.
(10)POWER lamp is not lit.
∙Make sure that the wiring and installation are correct.