Mitsubishi Electronics FR-A500L Wiring of the control circuit, NA version(OR Version)

Page 20

INSTALLATION AND WIRING

2.2.3 Wiring of the control circuit

(1) Wiring instructions

1)Terminals SD, SE and 5 are common to the I/O signals and isolated from each other. These common terminals must not be connected to each other or earthed.

2)Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main and power circuits (including the 200V relay sequence circuit).

3)The frequency input signals to the control circuit are micro currents. When contacts are required, use two or more parallel micro signal contacts or a twin contact to prevent a contact fault.

4)It is recommended to use the cables of 0.75mm2 gauge for connection to the control circuit terminals.

If the cable gauge used is 1.25mm2 or more, the front cover may be lifted when there are many cables running or the cables are run improperly, resulting in an operation panel or parameter unit contact fault.

(2) Terminal block layout

zNA versionOR Version

In the control circuit of the inverter, the terminals are arranged as shown below:

Terminal screw size: M3.5

A

 

B

 

C

 

PC

 

AM

 

10E

10

2

5

 

4

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RL

RM

 

RH

 

RT

 

 

AU

STOP

MRS

RES

 

SD

FM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SE

 

RUN

 

SU

 

IPF

 

OL

 

FU

SD

STF

STR

 

JOG

 

CS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

zEC version

Terminal screw size : M3

A

B

C

SD

AM 10E 10

2

5

4

1

RL RM RH RT AU

SE

RUN SU

LPF OL FU STOP MRS RES

PC

STF STR JOG CS FM SD

<Wiring procedure>

1)For the wiring of the control circuit, strip the sheaths of the cables and use them as they are.

Strip the sheath to the following dimension. If too much is stripped this may cause a short circuit with the neighboring cable. If too little stripped this may cause cable disconnection.

6mm ± 1mm

2)Loosen the terminal screw and insert the cable into the terminal.

3)Tighten the screw to the specified torque.

Undertigthening can cause cable disconnection or malfunction. Overtightening can cause a short

circuit or malfunction due to the screw or unit damaged. Tightening torque : 5 to 6 kgfcm

Note : Wire the stripped cable by twisting it to prevent it from becoming loose. (Do not plate the cable with solder.)

Note : 1. Use a NFB (No fuse breakers) or fuse on the inverter input (primary) side.

2.Make sure that the control circuit terminal wiring does not touch power circuit terminals (or screws) or conducting power circuit.

12

Image 20
Contents FR-A500L This section is specifically about safety matters Injury Prevention Electric Shock PreventionFire Prevention Transportation and installation WiringAdditional instructions Trial runMaintenance, inspection and parts replacement OperationEmergency stop Disposing of the inverterContents Chapter Outline Precautions for operation InstallationWiring Pre-Operation InformationBasic Configuration Basic configurationNFB ELB Name DescriptionChapter Installation Instructions for installationAt 5cm 1.97 inch Wiring Terminal connection diagramSymbol Terminal Name Description Description of main circuit terminalsDescription of control circuit terminals Terminal Name DescriptionIPF ,B,CRUN Wiring of the main circuit Wiring instructionsTerminal block layout 800 2300P1, P, N Connection of the power supply and motor Connection procedureWiring of the control circuit NA version(OR Version)Changing the control logic RUN DC24V How to use terminals STOP, CS and PC Connection to the PU connector For RS-485 communicationDesign information Chapter Operation Chapter Parameters Parameter List ParametersDU/PU main display data selection F4 fourth frequency voltage 173 201 Can be accessed when Pr = Protective Functions Errors Alarms Error alarm definitionsOperation Parameter Unit Name DescriptionOHT OLTSTP OPTCTE MB7Name Details Main circuit error E,15 detailsCharge Alarm To know the operating status at the occurrence of alarm Correspondences between digital and actual charactersAlarm code output Resetting the inverterAlarm Code Alarm Output across B-C FR-DU04 Operation PanelOperation Panel Check Point Remedy Display TroubleshootingChecking the operation panel display at alarm stop Check Point Remedy Faults and check points Speed greatly differs from the settingMotor remains stopped Motor rotates in opposite directionOperation mode is not changed properly Power lamp is not litMotor current is large Speed does not increasePrecautions for Maintenance and Inspection Precautions for maintenance and inspectionCheck items Periodic inspectionInsulation resistance test using megger Dielectric strength testDaily and Periodic Inspection Description Method Criterion Instrument DailyModule device numbers and terminals to be checked PreparationChecking method Replacement of parts Cooling fanSmoothing capacitors RelaysMeasurement of main circuit voltages, currents and power Measurement of voltages and currents5VDC Measuring Point Measuring Instrument10VDC Chapter Specifications Standard specification Model specificationsCommon specifications Alarm FR-PU04Outline drawings FR-A540L-450K, 375KFR-A540L-540K~800K SDA P5S RDB RDA SDBAppendices Front AppendixAppendix EF-40ETB R G Converter EF-30ETB Control Inverter Wiring between cooling fan and terminals is as followsCheck the air flow direction Resistor Temperature Abnormal Signals MT-BR5MT-BR5 TH1 TH2 PR PR EShipment case example