PROTECTIVE FUNCTIONS

 

 

 

 

 

 

Operation

Parameter

 

 

 

Panel

 

 

 

Unit

Name

Description

 

Display

 

(FR-PU04)

 

 

 

(FR-DU04)

 

 

 

 

 

 

 

 

 

 

When the operation panel power (P5S of the PU connector) is shorted,

 

 

 

Operation panel power short

this function shuts off the power output. At this time, the operation panel

 

E.CTE



(parameter unit) cannot be used and RS-485 communication from the PU

 

circuit

 

 

 

connector cannot be made. To reset, enter the RES signal or switch

 

 

 

 

 

 

 

 

power off, then on again.

 

 

 

 

 

 

 

 

 

Inverters of 7.5K or less contains a brake resistor. When the regenerative

 

 

 

 

brake duty from the motor has reached 85% of the specified value, pre-

 

 

 

Brake resistor overheat

alarm (RB indication) occurs. If the specified value is exceeded, the brake

 





circuit operation is stopped temporarily to protect the brake resistor from

 

protection

 

 

 

overheating. (If the brake is operated in this state, regenerative

 

 

 

 

 

 

 

 

overvoltage shut-off will occur.) When the brake resistor has cooled, the

 

 

 

 

brake operation is resumed.

 

 

 

 

 

 

E.MB1 to



Brake sequence error

This function stops the inverter output if a sequence error occurs during

 

MB7

the use of the brake sequence function (Pr. 278 to Pr. 285).

 

 

 

 

 

 

 

 

 

E.14

E.14

DC fuse blown

The inverter output will stop if the DC fuse blows.

 

 

 

 

 

 

 

 

 

Brake unit cooling fin overheat, control board ambient temperature error,

 

E.15

E.15

Main circuit error

output overcurrent, cooling fan power supply error, capacitor overcurrent,

 

cooling fin overheat, gate power supply error.

 

 

 

 

 

 

 

 

Refer to the next page (page 27) for details.

 

Note: 1. If Pr. 195 (A, B, C terminal function selection) is as set in the factory.

2.The terminals used must be allocated using Pr. 190 to Pr. 195.

3.External thermal relay operation is only activated when "OH" is set in any of Pr. 180 to Pr. 186 (input terminal function selection).

4.Indicates that the stall prevention operation level has been set to 150% (factory setting). If this value is changed, stall prevention is operated at the new value.

5.Resetting method

When the protective function is activated and the inverter stops its output (the motor is coasted to a stop), the inverter is kept stopped. Unless reset, the inverter cannot restart. To reset the inverter, use any of the following methods: switch power off once, then on again; short reset terminal RES- SD for more than 0.1 seconds, then open; press the [RESET] key of the parameter unit (use the help function of the parameter unit). If RES-SD is kept shorted, the operation panel will show "Err." or the parameter unit will show that the inverter is being reset.

26

Image 37
Contents FR-A500L This section is specifically about safety matters Fire Prevention Electric Shock PreventionInjury Prevention Wiring Transportation and installationAdditional instructions Trial runOperation Maintenance, inspection and parts replacementEmergency stop Disposing of the inverterContents Chapter Outline Installation Precautions for operationWiring Pre-Operation InformationBasic configuration Basic ConfigurationNFB ELB Name DescriptionChapter Instructions for installation InstallationAt 5cm 1.97 inch Terminal connection diagram WiringDescription of main circuit terminals Symbol Terminal Name DescriptionDescription of control circuit terminals Terminal Name DescriptionRUN ,B,CIPF Wiring instructions Wiring of the main circuit800 2300 Terminal block layoutP1, P, N Connection procedure Connection of the power supply and motorNA version(OR Version) Wiring of the control circuitChanging the control logic RUN DC24V How to use terminals STOP, CS and PC For RS-485 communication Connection to the PU connectorDesign information Chapter Operation Chapter Parameters Parameters Parameter ListDU/PU main display data selection F4 fourth frequency voltage 173 201 Can be accessed when Pr = Protective Functions Error alarm definitions Errors AlarmsOperation Parameter Unit Name DescriptionOLT OHTSTP OPTMB7 CTECharge Alarm Main circuit error E,15 detailsName Details Correspondences between digital and actual characters To know the operating status at the occurrence of alarmResetting the inverter Alarm code outputAlarm Code Alarm Output across B-C FR-DU04 Operation PanelChecking the operation panel display at alarm stop TroubleshootingOperation Panel Check Point Remedy Display Check Point Remedy Speed greatly differs from the setting Faults and check pointsMotor remains stopped Motor rotates in opposite directionPower lamp is not lit Operation mode is not changed properlyMotor current is large Speed does not increasePrecautions for maintenance and inspection Precautions for Maintenance and InspectionCheck items Periodic inspectionDielectric strength test Insulation resistance test using meggerDescription Method Criterion Instrument Daily Daily and Periodic InspectionChecking method PreparationModule device numbers and terminals to be checked Cooling fan Replacement of partsSmoothing capacitors RelaysMeasurement of voltages and currents Measurement of main circuit voltages, currents and power10VDC Measuring Point Measuring Instrument5VDC Chapter Specifications Model specifications Standard specificationCommon specifications FR-PU04 AlarmFR-A540L-450K, 375K Outline drawingsFR-A540L-540K~800K P5S RDB RDA SDB SDAAppendices Appendix AppendixFront Check the air flow direction Wiring between cooling fan and terminals is as followsEF-40ETB R G Converter EF-30ETB Control Inverter MT-BR5MT-BR5 TH1 TH2 PR PR E Resistor Temperature Abnormal SignalsShipment case example